21
Position Amperage (A) Circuit Breaker Rating
0 Not in Use N/A
1 16 20
2 24 30
3 32 40
4 40 50
5 48 60
6 50 70
7 Not in Use N/A
8 Not in Use N/A
9 Not in Use N/A
NOTE
When the rotary switch is at 0, 7, 8 or 9, the corresponding amperage will still be 16, 50, 50, and 50,
respectively.
The maximum current is limited by the power rating of a charger as follows:
— For 9.6 kW model: 40 A
— For 12 kW model: 50 A
CAUTION
To reduce the risk of fire, only connect your charger to a circuit with a branch circuit over-current protection
of 125% of the selected maximum amperage setting of the device in accordance with ANSI/NFPA 70 (US) CSA
C22.1 (Canada).