Testing & Code Compliance
UL LISTE D
General
Specification
Commercial Grade
In-Wall Occupancy/Vacancy Sensor
Model #: MWOS
Integrated PIR and Ultrasonic sensor technology to detect very fine motion and provide accurate motion sensing
Allows to choose triggering when both technologies detect motion or when only PIR detects motion
Less false trigger, fast ON/OFF; commercial grade sensor for closet, garage, hotels, meeting room, work places
Adjustable timeout from 15 seconds to 30 minutes; Walk-Through mode: 3 minutes if no activity after first 30
seconds
Description: This Multi-Technology Wall Switch Sensor combine advanced passive infrared (PIR) and ultrasonic
technologies into one unit. The combined technologies helps eliminate false triggering even in difficult applications.
Selectable operating modes allow the sensor to turn a load on, and hold it on as long as either or both technologies
detect occupancy . After no movement is detected for the selected time delay, the lights switch off.
A "walk-through" mode can turn lights off after only 3 minutes, if no activity is detected after 30 seconds following an
occupancy detection.
This sensor also contains a light level sensor. If adequate daylight is present, the sensor holds the load OFF until light
levels drop, even if the area is occupied.
Features:
Load Requirments:
Walk-Through Mode.......................3 minutes if no activity after 30 sec.
PIR Adjustment...............................................High or Low (DIP switch)
Adjustment Time Delay................................................. 5Sec to 30Mins
Light Level Adjustment.................................100 Lux --daylight(trimpot)
Operation Temperature................................................... 32° F--131° F
Test Mode ....................... 5 sec. at initial power up or DIP switch reset
Ultrasonic Adjustment .........................
Minimum to Maximum (trimpot)
Voltage ................................................................ 120/277VAC,50/60Hz
Motor .............................................................. 1/4HP-120VAC,50/60Hz
Incandescent....................................................800W-120VAC,50/60Hz
Fluorescent.........................800VA-120VAC,1600VA-277VAC,50/60Hz
Resistive...........................................................800W-120VAC,50/60Hz
Specifications:

Installation & wiring
*
Coverage area
Line(Hot), Red lead to Load wire, White lead to Neutral wire, Green
4. Gently position wires in wall box, attach sensor switch to the box.
3. Mount device “TOP”up.
5. Restore power at circuit breaker or fuse, wait
Wiring Diagram:
2. Connect lead wires as WIRING DIAGRAM (see Figure 1): Black lead to
6. Remove the small cover plate.
8. Replace the small cover plate after testing and adjustment.
lead to Ground.
one
minute.
1. Make sure that the power has been turned OFF at the circuit breaker.
Neutral
White
Hot
Black
Ground
Green
Load
Red
Neutral(White)
Load
40'
Top View
20'
10'
20'
10'
20'
5'
4'
Figure 1
7. Locate the adjustment trimpots on the control panel to perform test
and adjustment.
PIR Coverage: 1200 ft
Ultrasonic Coverage: 400 ft
2
2

Mode
OFF
Description
after set time delay.
Position
Left
Center
Right
Occupancy Mode:
Vacancy Mode: Manual On only,
automatic Off after set time delay.
React to the push-button
Manually toggles
Manually toggles
Automatic On, automatic Off
Band switch prescription.
On / Off the load.
On/Off the load.
OCC
VAC
None
Circuit is permanently opened.
(switched off)
5 Minutes
Walk Through
The MWOS has 7 DIP switches under the cover. They are used to
delay, trigger mode, walk through mode feature
Sensitivity
50%
100%
Disabled
Enabled
Time Delay
5 Sec/Test
30 Seconds
10 Minutes
15 Minutes
20 Minutes
25 Minutes
30 Minutes
1
7
4
5
6
=OFF =ON =Factory Setting
Trigger Mode
Initial
Trigger
Load Output
Maintain
Re-trigger
2
3
Both
Either
Either
PIR
PIR
PIR
Both
Both
Both
US
US
US
Option 1
Option 2
Option 3
Option 4
set sensitivity, time
settings.
Adj ustment
DIP Switch Setting
OFF OCC VAC
1
4
2
3
1
4
2
3
LIGHT
ULTRASONIC
OFF OCC VAC
Control Panel Cover
Mounting Yoke
ULTRASONIC
LIGHT
PIR Lens
Ultrasonic Cones
Detection LEDs
Red=PIR
Blue=Ultrasonic
ON
OFF
1 2 3 4 5 6 7