SERVICING
Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any
substance which may corrode refrigerant containing components, unless the components are
constructed of materials which are inherently resistant to being corroded or are suitably protected
against being so corroded.
Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and component inspection
procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the
circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to
continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the
equipment so all parties are advised.
Initial safety checks shall include:
Those capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking.
That there no live electrical components and wiring are exposed while charging, recovering or purging
the system.
That there is continuity of earth bonding.
WARNING!
Install the unit in rooms which exceed 8 m².
Do not install the unit in a place where inflammable gas may leak.