ComponentsComponents
PAGE 40
4
5
6
7
8
9
1. If in COOL or DRY mode: Compressor running (Thermal ON), then condensate pump is energized
•When compressor stops (Thermal OFF), condensate pump runs for an additional 5 minutes
2. If in COOL or DRY modes and compressor is running (Thermal ON) and the float switch opens for 5 minutes
•Compressor will stop, the pump will continue to run
•If the float switch does not close, error code will display and pump continues to run
•If the float switch does close, the pump will continue to run for 5 additional minutes
3. During standby (Thermal OFF) in COOL/DRY modes or in HEAT and FAN modes and float switch opens for 2 seconds,
the condensate pump is energized.
•If the float switch closes, the pump will run an additional 5 minutes
•If the float does not close, the pump continues to run and error code is displayed
8
6
4
7
5
Control Board
ECU for calculation of inverter capacity and temperature control.
Piping Temperature Sensor
The Piping Temperature Sensor senses indoor coil temperature in the cooling mode and in the heating mode. This sensor is
used for Anti Freezing and Anti Cold Blow cycles. The sensor also provides critical temperature information to the ECU that
Condensate Pump
Gravity Drain Ports
WiFi
The unit comes shipped with a WiFi module that provides control via a smartphone app.