Tripp Lite 5P1550GR-L Eaton 5P 1550VA 1100W 230V Line-Interactive UPS, C14 Input, 6 C13 Outlets, Lithium-ion Battery, True Sine Wave, Cybersecure Network Card Option, 1U

Installation and User Manual - Page 12

For 5P1550GR-L.

PDF File Manual, 21 pages, Read Online | Download pdf file

5P1550GR-L photo
Loading ...
Loading ...
Loading ...
Page 12
P-164000734 Rev 01
2. Presentation
Description Available Settings Default Settings
In/Out Settings
Load segments
- Auto shutdown
delay
[Disable] [0s] [1 s] [2 s]…[65354 s]
During a power outage,
authorizes UPS to turn off power to
equipment connected to Group 1
and/or Group 2 outlets.
This feature allows the shedding of
non-critical loads in order to conserve
battery power for critical loads
connected to the Primary group.
Group 1: Disable
Group 2: Disable
Overload
prealarm
[10 %] [15 %] [20 %] ... [100 %] [105 %]
Sets critical percentage of load where
alarm overload alarm occurs.
[105 %]
ON/OFF Settings
Cold start [Disable] [Enable]
Enables the product to be started on
battery power.
First cold start is always disabled.
Enable
Forced reboot [Disable] [Enable]
If mains recover during a shutdown
sequence:
- if enabled, shutdown sequence will
complete and wait 10 seconds prior
to restart
- if disabled, shutdown sequence will
not complete and restart will occur
immediately.
Enable
Auto restart [Disable] [Enable]
Enables the product to restart
automatically when mains recovers
after a complete battery discharge.
Enable
Energy saving [Disable] [Enable]
If enabled, UPS will shutdown after
5 min of back-up time, if no load is
detected on the output.
Disable
Sleep mode [Disable] [Enable]
If disabled, LCD and communication
will turn OFF immediately after UPS
is OFF.
If enabled, LCD and communication
stays ON 1h30 min after UPS is OFF.
Disable
Remote command [Disable] [Enable]
If enabled, shutdown or restart
commands from software are
authorized.
Enable
RPO delay
[0 s] [1s ] [2 s]...[180 s]
Delays remote power off command
[0 s]
Battery Settings
Low battery
warning
[1 %] [2 %] ... [100 %]
The alarm triggers when the set
percentage of battery capacity is
reached during a back-up time.
20 %
Restart battery
level
[1 %] [2 %] ... [100 %]
If set, automatic restart will occur
only when percentage of battery
charge is reached.
0 %