II / Assembly and Installation
Air Chutes (If equipped or as an optional accessory) - Install supply air flanges to the
front of your KwiKool unit above the control panel. (See instructions in the air chute kit
for specific procedures).
A.
B.
Air Chutes - Conditioned air supply,
if equipped or as an optional accessory.
Condensate Tank - 5-gal Condensate
Tank with float assembly for automatic
cutoff.
Condensate Water Outlet -
1/4” OD barbed fitting
Condensate Float Switch Jack -
Connects to the condensate tank or is bypassed by
the factory installed male bypass switch plug pictured
Power cord with plug -
available on 1.1-ton thru 2.5-ton models
Condensate Tank - KwiKool systems come standard with an external 5-gallon
condensate tank. The external condensate tank is equipped with a float switch that
shuts your KwiKool down and alerts operators with an alarm and display CF
(“Condensate Full”) when the condensate tank is full. This prevents accidental water
overflow on the floor. The alarm will clear automatically upon emptying the 5 gallon tank
and reconnecting it. If connecting to a permanent drain, do NOT connect or use the
equipped tank. To use the external condensate tank, remove the factory installed
condensate float switch bypass plug on your KwiKool unit and install the male connector
jack supplied on the condensate tank. Next connect the factory supplied ¼” ID conden-
sate tubing to the ¼” OD barbed condensate water outlet on the back of your KwiKool
and connect the discharge end of the tube to the ¼” barbed connector on the conden-
sate tank. The condensate float jack must be inserted into the female condensate jack
to operate your KwiKool. CF displays if the jack is not connected or the bypass plug is
not inserted properly.
Cord Compartment