8-2 Electrical characteristics
MCA: Minimum Circuit Ampacity (A) MOP: Maximum Overcurrent Protective Device (A)
kW: Fan Motor Rated Output (kW) FLA: Full Load Ampacity (A)
8-3 Specifications for field supplied fuses and wire
Allowable length of transmission wirings and remote controller wiring are as follows.
(1) Outdoor unit - Indoor unit:
Max. 3280ft. (Total wiring length: 6560ft.)
(2) Indoor unit - Remote controller
Max. 1640ft.
NOTE
1. Vinyl cord with sheath or cable (Insulated thickness : 0.04in. or more)
9. WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER
9-1 How to connect wires
Connection of wiring between units, ground wire and the remote controller wire (Refer to Fig. 25)
Wiring the units and ground wire
Remove the control box cover and connect wires of matching number to the terminal block for wiring the
units (3 P) inside. And connect the ground wire to the ground terminal. In doing this, pull the wires inside
through the hole and fix the wires securely with the included clamp (4) (2 points).
Remote controller wires (not necessary for slave unit of simultaneous operation system)
Remove the control box cover and pull the wires inside through the hole and connect to the terminal block
for remote controller (6 P). (no polarity) Securely fix the remote controller wire with the included clamp (4)
(2 points).
After connection, attach sealing pad (13).
Be sure to attach it to prevent the infiltration of water from the outside.
Units Power supply Fan motor
Model Hz Volts Voltage range MCA MOP kW FLA
FCQ18PAVJU
60 208/230
Max. 253
Min. 187
0.4 15 0.056 0.3
FCQ24PAVJU 0.5 15 0.056 0.4
FCQ30PAVJU 0.6 15 0.056 0.5
FCQ36PAVJU 1.4 15 0.120 1.1
FCQ42PAVJU 1.5 15 0.120 1.2
Power supply wiring
Remote controller wiring
Transmission wiring
Field fuses Size Wire Size
15A
Wire size must comply with
local codes.
Sheathed wire
(2 wire)
AWG18 - 16