Tripp Lite PDUMNH20HV 3.7kW Single-Phase 208/230V Monitored PDU - LX Platform, 8 C13 Outlets, C20 Input

Owner's Manual - Page 7

For PDUMNH20HV.

PDF File Manual, 48 pages, Read Online | Download pdf file

PDUMNH20HV photo
Loading ...
Loading ...
Loading ...
A
B
C
3.2-2
C
88
C
A
B
3.2-4
3.2-3
7
3. Installation
3.2-3
NEMA Power Cord Connection:
Insert the IEC C19 connector
A
of
the input power cord into the IEC
C20 inlet
B
of the PDU. Connect
the other end of the input power
cord
C
to a compatible source of
AC power, such as a UPS system,
PDU or utility outlet. The PDU
should be provided with over-
current protection. The PDU should
be provided with a maximum 20A
branch-rated over-current
protection device.
Note: The AC power source should not
share a circuit with a heavy electrical
load (such as an air conditioner or
refrigerator).
3.2-2
NEMA Adapter Connection: The
PDU includes a plug adapter that
adds a NEMA L6-20P plug to the
input power cord. Use this adapter
only if you will be connecting the
PDU to a NEMA L6-20R outlet.
Insert the IEC C19 connector
A
of
the adapter into the IEC C20
connector
B
of the input power
cord. Secure the connection with
the retention bracket
C
by using
the included bolts to fasten the two
halves of the bracket around the
connection as shown.
Caution: To avoid the risk of
electric shock, ensure that the
Neutral (L2) conductor has been
identiļ¬ed before connecting the
PDU.
3.2-4
Connect Equipment to PDU: Do
not exceed the load rating of the
PDU. The total electrical current
used by the PDU will be displayed
on the digital meter in amperes.
Refer to the Digital Load Meter
(Ammeter) in the Features section
for more information.
21-03-420-933682.indb 721-03-420-933682.indb 7 4/5/2021 1:10:24 PM4/5/2021 1:10:24 PM