26
9. Control Panel
SmartOnline SV-Series UPS Operating Mode
Standby Bypass Line Battery Battery Test Fault Converter ECO
Output Voltage Y Y
Bypass Voltage Range Y Y Y Y Y Y Y Y
Bypass Frequency Range Y Y
Converter Mode Y
ECO Mode Y Y Y
Bypass Mode Y Y
Auto Restart Y Y Y Y Y Y Y Y
Cold Start Y Y Y Y Y Y Y Y
Battery Mode Delay Time Y Y Y Y Y Y
System Shutdown Time Y Y Y Y Y Y Y Y
System Restore Time Y Y Y Y Y Y Y Y
Redundancy Y Y Y Y Y Y Y Y
Charger Test Y Y Y Y Y Y Y Y
Table 9.4
9.3.6.3 Battery
The SETUP – BATTERY screen may be accessed in any UPS operating mode. Some settings may only be amended in certain modes; refer to table
9.5 for details.
BATTERY
BATTERY LOW /
SHUTDOWN SETTING
MAXIMUM CHARGING
CURRENT
BATTERY CAPACITY IN Ah
BATTERY TEST
BATTERY AGE ALERT
TEMPERATURE
COMPENSATION
Battery Capacity in Ah
Maximum Charging Current
Battery Low Voltage
Battery Low Capacity
Battery Shutdown Voltage
Periodic Battery Test
Battery Test Interval
Stop by Time
Stop by Battery Voltage
Stop by Battery Capacity
Battery Age Alert
Temperature
Compensation
Set battery capacity (0-999) (Default: 009)
Set maximum battery charging current (1-64A)
(Default: 2 for UPS system)
Set battery low voltage: (10.5-11.5V) x (number of
batteries) (Default: 110V)
Set battery low capacity (20-50%) (Default: 20%)
Set voltage point for system shutdown
(10-11V) x (number of batteries) (Default: 100)
Set ‘Disable’ or ‘Enable’ (Default: Disabled)
Set battery test interval (7-99 days) (Default: 30)
Set testing time for battery test (10-1000 sec)
(Default: 10)
Set battery voltage cut-off to end battery test
(11-12V) x (number of batteries) (Default: 110V)
Set battery capacity cut-off for battery test (20-50%)
(Default: 20)
Set battery age for replacement alert
(Disable, 12-60 months) (Default: Disable)
Set battery compensation (-5 ~ 0)
(Default: 0)