When the cylinder below the counter is enclosed in a space equal to
or greater than 6,712 cubic inches (0.11 cubic meters) , additional
ventilation is not required.
When the cylinder below the counter is enclosed in a space less than
6,712 cubic inches (0.11 cubic meters), ventilation is required.
A
4.0 Ventilation
Spaces surrounding the cylinder that are equal to or greater than 6,712 cubic inches
(0.11 cubic meters) do not require additional ventilation.
This example would not require additional ventilation: 30” x 30” x 8” = 7,200 cubic inches
4.1 Ventilation - Example A
4.2 Ventilation - Example B
This example would require additional ventilation:
12” x 12” x 30” = 4,320 cubic inches
30”
12”
12”
Spaces surrounding the cylinder that are less than 6,712 cubic inches (0.11 cubic meters)
require additional ventilation. A small vent into a larger partition or into ambient air should be
specied in the back partition of the space. This will allow for proper airow.
The vent should have an area of at least 14 square inches.
(back partition)
For Optimum Performance
Ensure appliances that generate heat are not
near the product
Ensure the base and sides are not obstructed
Ensure the base and sides are not located in
an area where they are vulnerable to damage
or obstruction
vent example size:
1-1/2” x 9-1/2” = 14.25 square inches
(back partition)
30”
30”
8”
If multiple U-Chill
TM
units are installed into the same space, the non-vented allowance is 6,712
cubic inches per installed U-Chill
TM
.