CONVERSIONS
8) UNIVERSAL-LP GAS TO NATURAL
GAS CONVERSION PROCEDURE
Appliance models: Gas stainless steel hotplate
models:
EMJGC900SX
6 Burners
EMJGC60SX 4 Burners
EMJG30WSX 1 Burners
1. Remove each burner cap and burner skirt.
2. Remove the U-LPG main injector with a
7 mm/VF tube spanner and replace with the
appropriate size Natural Gas main injector for each
burner. The following injector sizes are required for
Natural Gas:
Burner Main injector
Double crown, Item 1 on page 3 1.75 B mm
Rapid 1.55 B mm
Semi Rapid 1.16 B mm
Auxiliary 0.90 Bmm
Double crown, Item 24 on page 3 2 x123B+80 B mm
3. Shut off gas supply to the appliance.
4. Disconnect gas inlet pipe from the U-LPG test
point inlet fitting.
5. Remove the U-LPG test point inlet fitting from
the appliance.
6. Fit the Natural Gas Regulator supplied in the
conversion kit.
7. Connect the gas supply to the Regulator.
8. Check for gas leaks. Do not use a naked flame
to check for gas leaks.
9. Adjust the gas pressure to 1.00 kPa.
10. Remove the control knob, with a thin shaft blade
screwdriver down the centre of each gas valve
shaft, screw the by-pass injector anti-clockwise.
Test the appliance on both high and low flame for
each burner. If the burner fails to remain alight or
the flame is not stable on the simmer setting, adjust
the by-pass screw, until flame is stable.
11. If not already removed, remove the Only for
use with U-LPG label adhered to the bottom panel
near the gas connection.
12. Fit the new data label included in the gas
conversion kit.
9) NATURAL GAS TO U-LPG
CONVERSION PROCEDURE
Appliance models: Gas stainless steel hotplate
models:
EMJGC900SX
6 Burners
EMJGC60SX 4 Burners
EMJG30WSX 1 Burners
1. Remove each burner cap and burner skirt.
2. Remove the Natural Gas main injector with a
7 mm/VF tube spanner and replace with the
appropriate size U-LPG Gas main injector for each
burner. The following injector sizes are required for
U-LPG Gas:
Burner Main injector
Double crown, Item 1 on page 3 1.00 B mm
Rapid 0.95 B mm
Semi Rapid 0.72 B mm
Auxiliary 0.56 B mm
Double crown, Item 24 on page 3 2 x123B+80 B mm
3. Remove the control knob, with a thin shaft blade
screwdriver down the centre of each gas valve
shaft, screw the by-pass injector fully clockwise.
4. Shut off gas supply to the appliance.
5. Disconnect gas inlet pipe from the Natural Gas
Regulator.
6. Remove the Natural Gas Regulator from the
appliance.
7. Fit the U-LPG Gas test point inlet fitting supplied
in the conversion kit.
8. Connect the gas supply to the inlet fitting.
9. Check for gas leaks. Do not use a naked flame
to check for gas leaks.
10. Adjust the gas pressure to 2.75 kPa.
11. Test the appliance on both high and low flame
for each burner and check the gas pressure. If the
burner fails to remain alight or the flame is not
stable on the simmer setting, adjust the by-pass
screw until flame is stable.
12. If not already removed, remove the Only for
use with Natural Gas” label adhered to the bottom
panel near the gas connection.
13. Fit the new data label included in the gas
conversion kit.