46 | PERFORMANCE DATA
Single-Zone LGRED° Four-Way Ceiling-Cassette System Engineering Manual
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©
/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
Cooling Capacity
PERFORMANCE DATA
Outdoor Air
Temp.
(°F DB)
Indoor Air Temp. °F DB / °F WB
68 / 57 73 / 61 77 / 64 80 / 67 86 / 72 90 / 75
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
-4 41.29 31.54 1.94 43.86 33.32 2.01 46.42 32.26 2.08 48.27 32.94 2.11 51.55 33.22 2.15 54.11 33.85 2.19
-0.4 41.27 31.73 1.96 43.83 33.52 2.03 46.40 32.45 2.11 48.25 33.14 2.13 51.52 33.42 2.17 54.08 34.05 2.22
5 41.24 32.00 1.99 43.80 33.81 2.07 46.36 32.74 2.14 48.21 33.42 2.17 51.48 33.71 2.21 54.04 34.34 2.25
10 41.20 32.26 2.02 43.76 34.08 2.10 46.32 33.00 2.17 48.17 33.69 2.20 51.44 33.98 2.24 54.00 34.62 2.28
15 41.17 32.51 2.05 43.73 34.35 2.13 46.29 33.26 2.21 48.13 33.96 2.23 51.40 34.24 2.27 53.96 34.89 2.32
20 41.14 32.77 2.08 43.70 34.62 2.16 46.25 33.52 2.24 48.10 34.22 2.26 51.36 34.51 2.31 53.92 35.16 2.35
25 41.11 33.02 2.11 43.66 34.88 2.19 46.22 33.78 2.27 48.06 34.49 2.29 51.32 34.78 2.34 53.88 35.44 2.38
30 41.08 33.28 2.14 43.63 35.15 2.22 46.18 34.04 2.30 48.02 34.75 2.33 51.28 35.04 2.37 53.83 35.71 2.42
35 41.05 33.53 2.17 43.60 35.42 2.25 46.15 34.29 2.33 47.99 35.02 2.36 51.24 35.31 2.40 53.79 35.98 2.45
40 41.02 33.78 2.20 43.56 35.68 2.28 46.11 34.55 2.36 47.95 35.28 2.39 51.20 35.58 2.44 53.75 36.25 2.48
45 40.98 34.03 2.23 43.53 35.95 2.31 46.07 34.81 2.40 47.91 35.54 2.42 51.17 35.84 2.47 53.71 36.52 2.52
50 40.95 34.28 2.26 43.50 36.22 2.34 46.04 35.07 2.43 47.88 35.81 2.45 51.13 36.11 2.50 53.67 36.79 2.55
55 40.92 34.54 2.29 43.46 36.48 2.37 46.00 35.32 2.46 47.84 36.07 2.49 51.09 36.37 2.53 53.63 37.06 2.58
60 40.89 34.79 2.32 43.43 36.75 2.40 45.97 35.58 2.49 47.80 36.33 2.52 51.05 36.64 2.57 53.59 37.33 2.62
65 40.86 35.04 2.35 43.40 37.01 2.43 45.93 35.84 2.52 47.77 36.59 2.55 51.01 36.90 2.60 53.55 37.60 2.65
70 40.83 35.29 2.38 43.36 37.28 2.46 45.90 36.09 2.55 47.73 36.85 2.58 50.97 37.16 2.63 53.50 37.87 2.68
75 39.84 34.71 2.51 42.37 36.71 2.60 44.90 35.59 2.69 46.73 36.36 2.72 49.96 36.71 2.77 52.49 37.44 2.83
80 38.86 34.11 2.63 41.39 36.13 2.73 43.91 35.07 2.83 45.73 35.86 2.86 48.95 36.25 2.92 51.48 37.00 2.97
85 37.89 33.49 2.76 40.41 35.52 2.86 42.92 34.52 2.97 44.74 35.33 3.00 47.96 35.76 3.06 50.47 36.53 3.12
90 36.91 32.86 2.89 39.43 34.90 3.00 41.94 33.96 3.10
43.75 34.79 3.14 46.96 35.26 3.20 49.47 36.05 3.26
95 35.86 32.51 3.02 38.36 34.59 3.13 40.85 33.70 3.24 42.00 34.02 3.28 45.85 35.07 3.34 48.35 35.90 3.41
100 34.98 31.64 3.15 37.48 33.72 3.26 39.98 32.90 3.38 41.46 33.49 3.42 44.98 34.32 3.48 47.47 35.16 3.55
105 34.11 30.77 3.27 36.61 32.85 3.39 39.11 32.10 3.52 40.91 32.97 3.56 44.10 33.56 3.63 46.60 34.42 3.70
110 33.24 29.72 3.40 35.74 31.78 3.53 38.23 31.10 3.66 40.04 31.98 3.70 43.23 32.61 3.77 45.73 33.48 3.84
115 32.37 28.83 3.53 34.86 30.89 3.66 37.36 30.28 3.79 39.17 31.17 3.84 42.36 31.83 3.91 44.86 32.72 3.99
118 31.84 28.62 3.61 34.34 30.70 3.74 36.84 30.13 3.88 38.64 31.03 3.92 41.83 31.72 3.99 44.33 32.63 4.07
122 31.67 28.55 3.71 34.16 30.64 3.85 36.66 30.07 3.99 38.47 30.98 4.03 41.66 31.68 4.11 44.16 32.60 4.19
Table 28: LCN429HV / LUU420HHV Cooling Capacities.
Cooling Capacity Table for LC429HHV (LCN429HV + LUU420HHV)
LC429HHV
DB: Dry Bulb Temperature (°F) WB: Wet Bulb Temperature (°F) TC: Total Capacity (kBtu/h)
SHC: Sensible Capacity (kBtu/h) PI: Power Input (kW) (includes compressor, indoor fan motor and
outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Cooling range can be extended from 5°F down to -4°F using the Low Ambient Wind Baffle Kit (sold
separately).
3. Grey shading indicates reference data. When operating at this temperature, these values can be
different if the system is not running consistently.
4. Direct interpolation is permissible.
Do not extrapolate.
Capacity as rated: 0 ft. above sea level with 24.6 ft. of refrigerant piping. 0 ft. level difference between
outdoor and indoor units.
Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet
bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).