15. Set up the control box dip switches as
indicated in the illustration and table
below (Fig. 14):
ON
1
2
3
4
5
6
Fig. 14
Zone
Selection*
DIP 1
:DIP2
DIP 1 DIP 2 ZONE
OFF OFF ZONE1
OFF ON ZONE2
ON OFF ZONE3
ON ON ZONE4
Heat Pump
(selected
models)
DIP 3 Reserved
Furnace DIP 4
OFF
Furnace
Off
ON
Furnace
On
Electric
Heat
(selected
models)
DIP 5
OFF
Heat Stripe
Off
ON
Heat Stripe
On
Analog /
Digital
DIP 6
OFF Digital
ON Analog
*NOTE: DIP1 and DIP2 are for Multi Zone
only.
16. Connect the wall thermostat cable
and 12VDC power cable to the control
box.(Fig. 15)
Wall Ther-
mostat Cable
12V DC Power Cable
LED Cable
Fig. 15
17. Install the control box into the
mounting frame and fix with 2 self-
tapping screws (one piece each side).
(Fig. 16)
Fig. 16
18. Connect the LED cable (if applicable)
from the ADB shroud to the control
box. (Fig. 17)
LED Cable
LED Cable
Fig. 17