TERMINAL CONNECTIONS
The wall thermostat terminal block is located behind the front panel and is easily accessible on
control panel.
,\
\
\\
\\
\\
STATUS LED
J Wall Thermostat
Energy Management Terminal Connections
Terminal Connections
Fig.20- Terminal Connector and Status LED Location
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation,
front of
©
©
©
©
©
TYPICAL WALL THERMOSTAT ©
©
©
©
NOTES: TERMINALBLOCK
1. Use terminal "O" for heat pump connection only.
2. Terminal "C" (common) is typically only required
for digital thermostats.
Energy
-- management
(24VAC in)
--Common
R
W
Y
O See Note 1
GH
GL
C See Note 2
TERMZNAL DESZGNATION
R 24 VAC
W Electric Heat
Y Compressor
O Reversing Valve
GH High Fan
GL Low Fan
C Common
NOTE: Any incorrect input combinations will be captured as
Improper wiring may damage unit electronics. Common
thermostat wiring failures and will light the STATUS LED
busing is not permitted. Damage or erratic operation may indicator on main board(see Intelligent Self- Checking
result. Control section)
fig,21-Wiring Connections
ENERGY MANAGEMENT INPUT (FRONT DESK CONTROL)
The controller can handle a switch signal from remote energy management input, called EM signal or front
desk control. Input must be 24VAC. If system receives a 24VAC signal, it will turn unit off; otherwise, the
unit runs in normal control. This function will be disabled under Freeze Guard protection. See Fig. 20 and
Fig. 21 for terminal connections.
INTELLIGENT SELF=CHECKING CONTROL
Your Frigidaire PTAC has a computer on-board that continuously checks key components of the unit to ensure
they are operating properly. Under normal operation, unit status indicator (STATUS, on main PCB), light is
steadily ON. If there is a major problem, the unit will shut down and display a diagnostic failure code on
the unit's display. If it is a minor error and the unit can correct it by itself, the diagnostic code
will be flashed on the status LED that can easily be seen when the front panel is removed (see Fig.23).
Failure STATUS codes are defined in the table below
1 Indoor air temp sensor open/short
2 Indoor coil sensor open or short
3 Outdoor coil sensor open/short NOTE" When status
4 Freeze Guard protection ight is flashing, it will
5 Indoor coil freeze protection 3e ON for 1 seconds
6 Outdoor coil high temp protection and OFF for another
7 Defrost (heat pump type)
8 Indoor coil high temp protection 1 seconds.
9 Thermostat wiring error
Table 5--STATUS LED Indicator Definitions
8-segment display 'FI', with STATUS light flash 1 times and off 3 sec, repeat
8-segment display 'F2', with STATUS light flash 2 times and off 3 sec, repeat
8-segment display 'F4', with STATUS light flash 3 times and off 3 sec, repeat
8-segment display 'FP'
STATUS light flash 5 times and off 3 sec, repeat
STATUS light flash 6 times and off 3 sec, repeat
STATUS light flash 7 times and off 3 sec, repeat
STATUS light flash 8 times and off 3 sec, repeat
STATUS light flash 9 times and off 3 sec, repeat
12