COMMISSIONING
42
Turn the adjusting knob on
the temperature limiting valve
counter-clockwise (down
away from the water heater),
using a 6 mm Allen key.
Turning the adjusting knob
counter clockwise (down
away from the water heater)
increases the outlet water
temperature, turning it
clockwise (up towards the
water heater) decreases the
outlet water temperature.
Repeat the water temperature measurement from the same hot tap.
Further adjust the temperature limiting valve as required, turning the
adjusting knob either counter clockwise (down away from the water heater)
or clockwise (up towards the water heater) to increase or decrease the
outlet water temperature, until an acceptable water temperature not
exceeding 50°C is measured at the same hot tap.
Note: The valve has a stop point for both maximum and minimum outlet
water temperature adjustment. The outlet water temperature cannot be
increased or decreased beyond these points. It is possible that, depending
upon valve tolerances and the pipe work design, 50°C water temperature
may not be attainable at the hot tap.
Turn off the hot tap.
Replace the insulation and plastic casing to cover the temperature limiting
valve and pipe work on the side of the water heater and secure using the
three (3) retaining screws.
RHEEMPLUS TEMPERATURE ADJUSTMENT