Loading ...
Loading ...
Loading ...
33
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
7528%/(6+227,1*
7(03(5$785(,13876
'LVSOD\VKRZV6HQVRU23(1
Check the sensor is connected and the wires are continuous to the BCP-8W. Finally follow the procedure for Incorrect
Temperature Display.
'LVSOD\VKRZV6HQVRU6+257
The BCP-8W sees a short across the input terminals. Remove the wires from the the sensor terminals. The display should change
to read OPEN. If it doesn’t, the BCP-8W may be damaged.
'LVSOD\VKRZVDQ,QFRUUHFW7HPSHUDWXUH'LVSOD\
Remove the wires from the sensor terminals. The display should change to read OPEN. If it doesn’t, the BCP-8W may be
damaged. Take an ohm reading across the detached sensor wires. Take an ohm reading across the detached sensor wires. The
ohm reading should correspond to the Temperature sensor Table. If it does not, the sensor may be damaged.
5HWXUQ6HQVRUGRHVQRW'LVSOD\7HPSHUDWXUH
Check the sensor is connected and the wires are continuous to the BCP-8W. Finally follow the
procedure for Incorrect temperature display.
&21752/23(5$7,21
7RR0XFK+HDW
&KHFNLIWKHFRQWUROKDVDQ\RIWKHIROORZLQJFRQGLWLRQV
'RPHVWLF+RW:DWHUFDOO- The BCP-8W will raise the temperature of the system to either
Û)RU0D[LPXP7DUJHWRQD'+:FDOO
5HVHW5DWLRDQG2IIVHW- If excessive heat occurs only in certain weather conditions, adjust
the Reset Ratio and Offset (See Understanding Operating Concept on page 5). If excessive
heat occurs year round, reduce the Offset.
%RLOHU0RGH6HWWLQJV- The BCP-8W will only sequence boilers with a Mode set to Auto or
Standby. Check to if any boiler stage is set to On.
&RQWURO6HWWLQJV7KH/DVW6WDJH+ROGZLOODOORZRQO\WKH/HDGERLOHUWRH[FHHGWKHVHWSRLQW
,IWKHVHWWLQJLVWRRKLJKDQGRQO\WKH/HDGERLOHULVRQWKHV\VWHPFDQRYHUKHDW5HGXFHWKH
/DVW6WDJH+ROGVHWWLQJ7KLVZLOOPRVWO\RFFXULQPLOGZHDWKHU
7RR/LWWOH+HDW
&KHFNLIWKHFRQWUROKDVDQ\RIWKHIROORZLQJFRQGLWLRQV
5HVHW5DWLRDQG2IIVHW- If reduced heat occurs only in certain weather conditions, adjust the
Reset Ratio and Offset (See Understanding Operating Concept on page 5). If reduced heat
occurs year round, increase the Offset.
6HWEDFNDQG'D\1LJKW6FKHGXOH,IUHGXFHGKHDWRFFXUVRQO\GXULQJVSHFL¿FKRXUVFKHFN
the Day/Night Schedule and the Setback, Boost, and Boost Period values. Either reduce the
Setback or Boost settings or change the Day and Night Schedules.
%RLOHU0RGH6HWWLQJV- The BCP-8W will only modulate boilers their mode is set to Auto or
Standby. Check if any boiler stage is set to Manual, Off, or Standby.
%RLOHUVDUH6KRUW&\FOLQJ
0LQLPXP5XQWLPH- Increase the Minimum Runtime only if all boilers tend to short-cycle.
/DVW6WDJH+ROG,QFUHDVHWKH/DVW6WDJH+ROGRQO\LIWKHOHDGERLOHUWHQGVWRVKRUWF\FOH
6\VWHPLV2YHUVKRRWLQJRU8QGHUVKRRWLQJ
5HDFWLRQ7LPHDQG0LQLPXP5XQWLPH- If the system is overshooting or undershooting,
adjust Minimum Runtime or the Reaction Time. That depends on if the stages are brought on
fast and were not allowed to turn off until the Minimum Runtime elapsed. Or, the stages were
brought on slowly, however, were allowed to turn off quickly.
3,'YV266- If the application the system is used on requires fast response that the normal
PID mode cannot provide, try using the OSS mode and adjust the Throttle Range according to
the system requirements.
7HPSHUDWXUH6HQVRU&KDUW
7(03(5$785(
LQ'HJUHHV°)
9DOXH
LQ2KPV
-30 117720
-20 82823
-10 59076
0 42683
10 31215
20 23089
25 19939
30 17264
35 14985
40 13040
45 11374
50 9944
55 8714
60 7653
70 5941
80 4649
90 3667
100 2914
110 2332
120 1879
130 1524
140 1243
150 1021
160 842
170 699
180 583
190 489
200 412
210 349
220 297
230 253
240 217
250 187
Loading ...
Loading ...
Loading ...