Weil-McLain BCP-8 Boiler Control Panels (BCP)

Product's Documents

Below are documents related to this product, you can read online or download:
User Manual Other Documents

Installation and Operation Instructions Manual

This is the main product document for model BCP-8. Additionally, the document applies to other Weil-McLain models: BCP-8W, BCP-8X

The file format is pdf, 40 pages, you can download this manual here .

background
BCP-8W
HYDRONIC SEQUENCING CONTROL
SYSTEM
DHW PUMP
PWR
LN
12
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11 13
Stage E
15
Stage F
17
Stage D
6 8 10 12 14
16 18
RS485
SYS=144F OD=35F
<AB
>DEGHJK
HI LO -- OFF
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27 29 31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20 22 28 30 32 34 36
STAGE MENU
Stage E
Stage F
Stage G
Stage H
Stage A
Stage B
Stage C
Stage D
25 26
37 38
PROVE
TEMP
PROGRAM RUN
23 24
COMB.
AIR
COMB. AIR
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
CUS
AUX 1
INPUT RATINGS: 120VAC 60Hz, 12VA MAX
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
OUTPUT RATING: 2A, 120VAC.
MAXIMUM 15A TOTAL FOR ALL CIRCUITS
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
 ,167$//$7,21$1'23(5$7,21,16758&7,2160$18$/
 86(523(5$7,21,16758&7,2160$18$/
BCP-8W
AND
BCP-8X
+<'521,&6(48(1&,1*%2,/(5&21752/$1'(;7(16,21
7KLV:HLO0F/DLQFRQWUROLVVWULFWO\DQRSHUDWLQJFRQWUROLWVKRXOGQHYHUEHXVHGDVD
SULPDU\OLPLWRUVDIHW\FRQWURO$OOHTXLSPHQWPXVWKDYHLWVRZQFHUWLILHGOLPLWDQGVDIHW\
FRQWUROVUHTXLUHGE\ORFDOFRGHV7KHLQVWDOOHUPXVWYHULI\SURSHURSHUDWLRQDQGFRUUHFWDQ\
VDIHW\SUREOHPVSULRUWRWKHLQVWDOODWLRQRIWKLV:HLO0F/DLQFRQWURO
:$51,1*
Part Number 550-100-071/0408
background
2
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
%&3:/$<287                   3
%&3:29(59,(:                  4
81'(567$1',1*23(5$7,21&21&(37     5
Reset Ratio/Outdoor Reset ................5
PID Operation .......................6
OSS Operation ......................6
0DNH6XUH<RX+DYHWKH5LJKW&RQWURO          7
,1,7,$/6(783                     7
6HOHFWLQJWKH6\VWHP)HDWXUHV              7
,167$//$7,21                    
0RXQWLQJWKH(QFORVXUH                
,QVWDOOWKH6HQVRUV                    9
System Sensor Installation ................9
Outdoor Sensor Installation ................9
:LULQJ                          10
Wiring the Power (Terminals 1, 2) . ...........10
Wiring the Sensors ...................10
Wiring the Domestic Hot Water (DHW) Sensor (Terminals 33,
34)............................11
Wiring the Shutdown (Terminals 35, 36) ........11
Wiring the T-STAT (Terminals 35, 36) ..........11
Wiring the Setback (Terminals 35, 36) .........11
Connecting to the BCP-8X Panels and 420MOD Interface13
Selecting the BCP-8X Panel Letter ...........13
,167$//(50(186(48(1&(           14
6WDUWXS6HWWLQJV                      17
Program Change Settings. ...............17
Startup Sequence ....................17
Control Mode ......................17
Display Unit .......................17
Setting the 4mA and 20mA Set Points (Available in 4-20mA
EMS only) ........................17
DHW Piping .......................18
DHW Pump Output ...................18
Combustion Air Damper Output . ............18
External Input Mode . ..................18
Burner Type .......................19
Boiler Output ......................19
Total Boilers .......................19
Staging .........................19
Sequence ........................19
Control Logic ......................19
Sensor Fault. ......................20
6HWWLQJWKH&RQWUROWR)DFWRU\'HIDXOWV         20
2SHUDWLQJ6HWWLQJV                    20
Program Change Settings. ...............20
Season .........................21
Reset Ratio .......................21
Customized Reset Ratio. ................21
Set Point (Not Adjustable in EMS Mode) ........22
Outdoor Cutoff Temperature. ..............22
Target Offset. ......................22
Minimum Target .....................23
Maximum Target. ....................23
%RLOHU0LQLPXP5HWXUQ                  23
Minimum Return. ....................23
Return Lag. .......................24
6\VWHP6HWWLQJV                      24
Program Change Settings. ...............24
6WDJH6HWWLQJV                       24
Reaction Time . .....................24
Purge Delay .......................24
Minimum Runtime . ...................24
Standby Delay. .....................25
Last Stage Hold .....................25
Throttle Range. .....................25
/HDG6HWWLQJV                       25
Lead Boiler .......................26
Rotate Mode. ......................26
6HWEDFN6FKHGXOH                     26
Setback .........................26
Boost ..........................26
Boost Period. ......................27
Day/Night Schedules ..................27
Set Present Time ....................27
'+:6HWWLQJV                       2
DHW Priority Timer (Available with Parallel DHW Piping)28
DHW Set Point (Requires an Optional DHW Temperature
Sensor) .........................28
3XPS9DOYHDQG&RPEXVWLRQ$LU'DPSHU2SHUDWLRQ 29
Run-On .........................29
Pump Exercise .....................29
0DLQWHQDQFH                        30
System & Outdoor Sensor Trim .............30
+LVWRU\                           30
&RQ¿JXUDWLRQ ......................30
Display and Buttons . ..................30
%RLOHU6HWWLQJV                       32
Mode ..........................32
RunTime. ........................32
7528%/(6+227,1*                 33
08/7,3/(%2,/(56:,7+380363,3,1*:,5,1*
',$*5$06                      34
86(50(186(48(1&(               35
Program Change Settings. ...............35
Season .........................35
Set Point (Not Adjustable in EMS Mode) ........36
Reset Ratio .......................36
Customized Reset Ratio. ................36
Outdoor Cutoff Temperature. ..............37
Setback .........................37
Day/Night Schedules ..................37
63(&,),&$7,216                  40
%&3:6SHFL¿FDWLRQV                  40
%&3;6SHFL¿FDWLRQV                  40
&RQWHQWV
background
3
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
HYDRONIC SEQUENCING CONTROL
SYSTEM
DHW PUMP
PWR
LN
12
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11 13
Stage E
15
Stage F
17
Stage D
6 8 10 12 14
16 18
RS485
SYS=144F OD=35F
<AB
>DEGHJK
HI LO -- OFF
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27 29 31
DHW
33 35
RETURN
TEMP
20 22 28 30 32 34 36
STAGE MENU
Stage E
Stage F
Stage G
Stage H
Stage A
Stage B
Stage C
Stage D
25 26
PRESS
+ -
37 38
PROVE
TEMP
PROGRAM RUN
23 24
COMB.
AIR
COMB. AIR
Connect to Extension panels to
add additional stages or connect
to 420MOD Interface for
external set point.
When connecting Temperature Sensors, no
Polarity is observed. Prove terminals
must be connected for BCP-8 to
operate stages.
Button function is presented on
bottom row of the display.
LEDs indicate
associated relay’s status
Program Switch to restrict access
to function changes. This Switch is
covered with Enclosure Wiring Cover.
System Output controls pumps,
valves, or other system components.
DHW Pump and Comb. Air relays are
controlled when configured.
Output Relays to manage the stages.
BCP-8W
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
CUS
SHUTDOWN
/TSTAT
/SETBACK
INPUT RATINGS: 120VAC 60Hz, 12VA MAX
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
OUTPUT RATING: 2A, 120VAC.
MAXIMUM 15A TOTAL FOR ALL CIRCUITS
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
%&3:/$<287
background
4
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
%&3:29(59,(:
6(48(1&(6837267$*(6:,7+38036259$/9(6
The BCP-8W is the perfect control whenever multiple boiler stages are required for Hydronic heating applications. The BCP-8W controls
the stages and their pumps or valves to maintain a precise system set point.
3,'2529(56,=('6<67(0266/2*,&
The BCP-8W’s control algorithm allows it to look at the rate of change in the system. If the load is changing quickly, the BCP-8W can
be set to OSS sequencing where it will react based on load changes. If the system oscillation is minimal as in heating applications, the
%&3:ZLOOPDNHVORZDQGJUDGXDORXWSXWDGMXVWPHQWV7KHUHIRUHWKH%&3:DGDSWVWRVSHFL¿FV\VWHPUHTXLUHPHQWVDQGPLQLPL]HV
oscillation around the set point.
',*,7$/',63/$<2)$//6<67(06(77,1*6
The BCP-8W’s alphanumeric digital display names each system parameter in simple English and shows its precise value. The easy to
IROORZPHQXV\VWHPDOORZVXVHUVWRTXLFNO\PDNHFKDQJHVWRDQ\V\VWHPVHWWLQJZLWKRXWKDYLQJWROHDUQDQ\VSHFLDOL]HGFRGHVRUNH\
commands.
$8720$7,&527$7,21$021*67$*(6
5RWDWLQJWKH¿UVWVWDJHWREHDFWLYDWHGRQDFDOOIRURXWSXWSURPRWHVHYHQZHDURQHDFKERLOHU7KH%&3:KDVWKUHHPRGHVRIURWDWLRQ
Manual, First-On/First-Off (FOFO), or Time. The Time rotates the lead stage every selected period from every hour to every 41 days.
287'2255(6(7:,7+&86720,=$%/(&859(
With its Outdoor reset feature, the BCP-8W is capable of changing its temperature target based on the outdoor temperature. It offers
VHYHUDOSDUDPHWHUVWKDWFDQEHXVHGWR¿QHWXQHWKHUHVHWFXUYHOffset, Minimum, and Maximum Targets, and Night Setback Schedule
or Setback using an External Signal. )XUWKHUPRUHDFXVWRPL]DEOHRXWGRRUUHVHWFXUYHKDVEHHQLQFRUSRUDWHGIRUXQLTXHDSSOLFDWLRQV
ZKHUHVWDQGDUGUHVHWUDWLRVZLOOQRWVXI¿FH
67$1'%<%2,/(5237,21
$Q\RIWKH%&3:KHDWLQJERLOHUVFDQEHFRQ¿JXUHGDVD6WDQGE\ZLWKDQDGMXVWDEOH6WDQGE\GHOD\$VVLJQLQJDVSHFL¿FERLOHUWR
work in standby mode will remove it from the rotation. In this mode, the boiler will be used for backup in large demand periods where
WKHSULPDU\ERLOHUVZLOOQRWVXI¿FH
6<67(0$1'&20%867,21$,5'$03(52873876:,7+3529(,1387
These outputs work with the control logic to operate a primary system pump and a combustion air damper. In addition, a System Prove
LQSXWFDQEHZLUHGLQWRFKHFNWKHVWDWXVRIHLWKHURIWKHFRPSRQHQWVHQHUJL]HGE\WKHRXWSXWVEHIRUHWKHVWDJHVFDQEHDFWLYDWHG
1250$//2+,/2+,253$5$//(//2/2+,+,6(48(1&,1*
The BCP-8W can sequence boilers as needed)RUKHDWLQJV\VWHPVZKHUHKLJKHUHI¿FLHQF\LVDFKLHYHGXVLQJORZHU¿ULQJVWDJHVWKH
%&3:RIIHUVWKH3DUDOOHO6HTXHQFLQJRSWLRQ,WVHTXHQFHVDOOWKHORZ¿ULQJVWDJHV¿UVWEHIRUHEULQJLQJWKHUHVWRIWKHVWDJHVRQ)RU
other types of boilers, using the Normal Sequencing option brings the lower operating stage followed by the higher one of the lead boiler.
That will be repeated for each of the lag boilers.
08/7,3/(256,1*/(67$*,1*
8QOLNHPDQ\ERLOHUVZKHUHWR¿UHDPXOWLVWDJHERLOHUERWKORZDQGKLJKVWDJHUHOD\VPXVWEHHQHUJL]HGVRPHRIWKHDYDLODEOHHTXLSPHQW
require that the operation of the higher stages turn off the lower operating stages. This can be achieved by selecting Single from the
Startup Staging menu.
$''837267$*(6
As a stand-alone, the BCP-8W-8 is designed to control eight stages. However, it has the capability of expanding its control to two
extension panels (BCP-8X) each with eight stages. Thus, the BCP-8W can control a total of up to 24 stages.
021,7256<67(05(78517(03(5$785(
Using a smart algorithm, the BCP-8W can monitor the boiler return temperature using an optional return sensor mounted on the return
line. Then, sequence the boilers to raise the return temperature above an adjustable Minimum Return.
'+:3803&21752/:,7+08/7,3/(35,25,7<237,216
Having a DHW input either as a dry contact to be used with an external aquastat or as a temperature sensor that can be ordered separately,
the BCP-8W can control a DHW pump using its built-in DHW Pump output relay. The user will have different priority options that
varies based on the DHW piping design.
background
5
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
81'(567$1',1*23(5$7,21&21&(37
The BCP-8W has multiple operating modes that satisfy most hydronic systems. When the
Outdoor Reset is selected, it can change the System Set Point based on outdoor temperature.
Or, it can be set to Set Point and sequence stages to achieve a manually adjusted Set Point.
In Outdoor Reset, the BCP-8W controls a hot water heating system to provide a building with
comfortable and even heat levels. The BCP-8W varies the Target temperature of the circulating
heating water in response to changes in the outdoor temperature.
The BCP-8W also controls the system circulating pump with an adjustable Outdoor Cutoff.
When the outdoor temperature is above the Outdoor Cutoff, the System Pump will be off
and no heating water is circulated through the system. When the outdoor temperature drops
EHORZWKH2XWGRRU&XWRIIWKHV\VWHPSXPSUHOD\LVHQHUJL]HGDQGWKHKHDWLQJZDWHUVWDUWVWR
circulate through the system. The temperature of the heating water is controlled by the Reset
Ratio parameters or the Set Point.
5(6(75$7,2287'2255(6(7
When a building is being heated, heat escapes through the walls, doors, and windows to
the colder outside air. The colder the outside temperature, the more heat escapes. If you
can input heat into the building at the same rate that it is lost out of the building, then the
building temperatures will remain constant. The Reset Ratio is an adjustment that lets
you achieve this equilibrium between heat input and heat loss.
7KHVWDUWLQJSRLQWIRUPRVWV\VWHPVLVWKH2'6<62XWGRRU7HPSHUDWXUH
+HDWLQJ:DWHU7HPSHUDWXUHUDWLR7KLVPHDQVWKDWIRUHYHU\GHJUHHWKHRXWGRRU
temperature drops, the temperature of the heating water will increase one degree. The
starting point of the curves is adjustable, but comes factory selected at 70°F Outdoor
Temp. and 100°):DWHU7HPS)RUH[DPSOHZLWKD2'6<6UDWLRLIWKH
outdoor temperature is 50°F, this means the temperature has fallen 20° from the starting
point of 70°F. Therefore, the heating water temperature will increase 20° to 120°F.
Each building has different heat loss characteristics. A very well insulated building will
QRWORVHPXFKKHDWWRWKHRXWVLGHDLUDQGPD\QHHGD5HVHW5DWLRRI2'
6<62XWGRRU:DWHU7KLVPHDQVWKHRXWGRRUWHPSHUDWXUHZRXOGKDYHWRGURS
degrees to increase the water temperature 1 degree. On the other hand, a poorly insulated
EXLOGLQJZLWKLQVXI¿FLHQWUDGLDWLRQPD\QHHGD5HVHW5DWLRRI2'6<6
This means that for each degree the outdoor temperature dropped the water temperature
will increase 2 degrees. The BCP-8W has a full range of Reset Ratios to match any
buildings heat loss characteristics.
A heating curve that relies not only on Outdoor temperature but also on the type of
radiation will improve heat comfort. The following are suggested initial settings for
different types of radiation based on average building insulation and heat loss. The
FRQWUDFWRUFDQ¿QHWXQHWKHVHDGMXVWPHQWVEDVHGRQWKHVSHFL¿FEXLOGLQJQHHG
7\SHRI5DGLDWLRQLQ%XLOGLQJ 5HVHW5DWLR 2IIVHW
Radiators (Steel & Cast Iron) 1.00 (OD) : 1.00 (SYS) Û)
Baseboard (Finned copper tube& Cast Iron) 1.00 (OD) : 1.00 (SYS) Û)
Radiant (High Mass/Concrete) 4.00 (OD) : 1.00 (SYS) Û)
Radiant (Low Mass/Joists) 2.00 (OD) : 1.00 (SYS) Û)
Fan Coils & Air Handlers 1.00 (OD) : 1.00 (SYS) Û)
Outdoor Temperature
Water Temperatur e
70 405060
130
120
110
100
Outdoor Temperature
Water Tem perature
70 405060
110
100
90
80
Outdoor Temperature
Water Tem perature
70 405060
150
140
130
120
1:4
With a Offset, the
ratio curves begin at
100° Water Temperature.
With a -20° Offset, the
ratio curves begin at
80° Water Temperature.
With a +20° Offset, the
ratio curves begin at
120° Water Temperature.
1:4
1:4 1:1
1:1
1:1
4:1
4:1
4:1
90
100
+20 Offset
-20 Offset
(O) Outdoor Temperature (in °F)
70 60
50
40 20
30 0 -10
10 -20
100
120
110
130
140
150
160
180
170
190
200
210
220
1:3 1:2 1:1.5
1:1.25
1:1
1.25:1
1.5:1
2:1
3:1
4:1
(S) Water Temperature (in °F)
Reset Ratio Curves
Reset Ratio is Presented as
Outdoor Temp.(O) : Water Temp.(S) Ratio
1:4
8:1
:$51,1*
:KHQFRQWUROOLQJDQRQFRQGHQVLQJ
ERLOHUWKH0LQLPXP7DUJHW
WHPSHUDWXUHPXVWEHVHWWRWKHERLOHU
PDQXIDFWXUHUVSHFL¿FDWLRQV,QWKDW
FDVHV\VWHPWHPSHUDWXUHPXVWQRW
JREHORZVXFKWHPSHUDWXUH
background
6
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
The BCP-8W has multiple operating modes that satisfy most hydronic systems. It can sequence stages to achieve an adjustable Set Point
or an Outdoor Reset Ratio. Moreover, when used with the 420MOD Interface it can accept a 4-20mA signal as a set point. The 420MOD
Interface must be purchased separately. This gives the BCP-8W the capability of being controlled remotely.
3,'23(5$7,21
3,'FRQWUROORJLFLVSULPDULO\XVHGIRUEXLOGLQJKHDWLQJ7KHORJLFZLOOXWLOL]HWZRSULPDU\VHWWLQJVWRDGGRUVXEWUDFWVWDJHV7KH5HDFWLRQ
7LPHLVXVHGWRWXUQRQHQHUJL]HVWDJHV2QWKHRWKHUKDQGWKH0LQLPXP5XQWLPHLVXVHGWRWXUQRIIGHHQHUJL]HVWDJHV$FDOOIRUKHDW
by either closing the TSTAT input or opening the SHUTDOWN input, and when the outdoor temperature is below the Outdoor Cutoff, the
%&3:ZLOOWXUQRQHQHUJL]HWKHORZHVW¿ULQJVWDJHRIWKH/HDG%RLOHUWRVWDUWWKH3XUJH'HOD\$IWHUWKHHODSVHRIWKHSXUJHSHULRGWKH
BCP-8W will start calculating the Reaction Period. If after a full Reaction Time the control logic foresee additional stages are needed,
WKH%&3:ZLOOHQHUJL]HWKHIROORZLQJVWDJH,IWKDWVWDJHZDVDQRWKHUERLOHUWKDWERLOHUKDVWRJRWKURXJKDIXOO3XUJH'HOD\EHIRUH
VWDUWLQJWRFDOFXODWHWKH5HDFWLRQ7LPHIRUWKDWVWDJH2WKHUZLVHLIWKHQH[WVWDJHZDVWKHKLJKHU¿ULQJVWDJHRQWKHVDPHERLOHUWKH
5HDFWLRQ7LPHZLOOVWDUWIURPWKHPRPHQWWKHKLJKHU¿ULQJVWDJHUHOD\LVHQHUJL]HG
When the BCP-8W PID logic foresees that the system will overshoot, regardless of the current system and target values, it will make sure
WKDWWKHODVWVWDJHWXUQHGRQHQHUJL]HGHODSVHGDIXOO0LQLPXP5XQWLPHEHIRUHLWLVWXUQHGRIIGHHQHUJL]HG([FHSWIRUWKHOHDGVWDJH
QRDGGLWLRQDOVWDJHVZLOOEHWXUQHGRIIGHHQHUJL]HGXQWLODQRWKHUIXOO0LQLPXP5XQWLPHLVHODSVHG2QWKHRWKHUKDQGLIWKHODVWVWDJH
LVDOHDGVWDJHLWZLOOUHPDLQHQHUJL]HGXQWLOWKHV\VWHPUHDGLQJH[FHHGVWKHWDUJHWVHWSRLQWE\WKH/DVW6WDJH+ROGYDOXHLQDGGLWLRQWR
satisfying the Minimum Runtime condition. That is, if the Set Point was 150°)DQGWKH/DVW6WDJH+ROGZDVVHWWR°F, the lead stage
ZLOOUHPDLQHQHUJL]HGXQWLOWKHV\VWHPUHDFKHV°F and a full Minimum Runtime elapses. This is useful in protecting the lead stages
from short cycling.
26623(5$7,21
266LVXVHGLQIDVWUHDFWLQJDSSOLFDWLRQDVLQSURFHVVDSSOLFDWLRQVZKHUHPDLQWDLQLQJDVHWSRLQWLVFULWLFDO7KH266XWLOL]HVWKH7KURWWOH
setting, as a mean to calculate the number of stages the BCP-8W shall have on at any point. For every Throttle Range below the set
SRLQWDQDGGLWLRQDOVWDJHVKDOOEHWXUQHGRQHQHUJL]HG7KDWLVLIWKHVHWSRLQWZDV°F and the Throttle setting was 5°F, if the System
dropped below 175°F (180°F - 5°)WKHOHDGVWDJHZLOOHQHUJL]H:LWKIXUWKHUGHFUHDVHLQWKHV\VWHPYDOXHWR°F (180°F - 5°F - 5°F),
WKHVHFRQGVWDJHZLOOHQHUJL]H
As the system temperature rises towards the set point, stages will turn off. Using the previous example, when the system rise to 175°F
ERLOHU%ZLOOGHHQHUJL]HOHDYLQJRQO\ERLOHU$RQ%RLOHU$ZLOOUHPDLQRQXQWLOWKHV\VWHPULVHVDRQHIXOO7KURWWOHUDQJHDERYHWKHVHW
point. This will leave the lead boiler A on until the temperature rises to 185°)WKHQWXUQRIIGHHQHUJL]H
7KURWWOLQJ([DPSOH
6HW3RLQW °) 7KURWWOLQJ °) %RLOHU6WDJHV$%&DQG'
)DOOLQJ7HPSHUDWXUH 5LVLQJ7HPSHUDWXUH
7HPSHUDWXUH &DOFXODWLRQ 6WDJH7XUQHG2Q 6WDJHV2Q 6WDJH7XUQHG2II 6WDJHV2Q
185°F
180 + (1)THR
--- None A None
180°F 180 - (0)THR --- None --- A
175°F 180 - (1)THR A A B A
171 to 174°F --- --- A --- A,B
170°F 180 - (2)THR B A,B C A,B
166 to 169°F --- --- A,B --- A,B,C
165°F 180 - (3)THR C A,B,C D A,B,C
161 to 165°F --- --- A,B,C --- A,B,C,D
160°F 180 - (4)THR D A,B,C,D --- A,B,C,D
background
7
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
0$.(685(<28+$9(7+(5,*+7&21752/
,I\RXQHHGWKH%&3:WRGRDGGLWLRQDOWDVNVWKDWHLWKHUDUHQRWOLVWHGRUGRQRWNQRZKRZWRVHWWKHPFRQWDFW:HLO0F/DLQ
,1,7,$/6(783
+DYLQJDQ,QLWLDO6HWXS3URJUDPZLOOHDVHWKHFRQ¿JXUDWLRQRIWKH%&3:DQGZLOOSURYLGHWKHRSSRUWXQLW\WRXWLOL]HPDQ\RIWKHHQHUJ\
saving features and give more comfortable heat when needed.
7KHSURJUDPVKRXOGFRQVLVWRIWKHIROORZLQJ
 6HOHFWLQJWKHIHDWXUHVWKDW\RXUV\VWHPFDQXWLOL]H
 ,QVWDOODWLRQ,QVWDOOWKH&RQWUROVZLWFKHVDQGVHQVRUV
 6HWWLQJWKH6\VWHP6WDUWXS
 6HWWLQJWKH6\VWHP6HWWLQJV
 6HWWLQJWKH6WDJHV
 $GMXVWLQJ5HVHW5DWLRDQG:DWHU2IIVHW,Q5HVHW0RGH2QO\
6(/(&7,1*7+(6<67(0)($785(6
The BCP-8W has been designed with Hydronic heating as the primary purpose. With this in mind, many of the BCP-8W features can
EHXWLOL]HGWRHDVHHQKDQFHDQGLPSURYH\RXUV\VWHPSHUIRUPDQFH6RPHRIWKHVHIHDWXUHVDUHOLVWHGLQWKLVVHFWLRQ
+($7,1*:,7+08/7,3/(256,1*/(287387$7$7,0(
 7KH%&3:LVHTXLSSHGWRFRQWUROPXOWLSOHPXOWLVWDJHERLOHUVZLWKRUZLWKRXWSXPSVRUYDOYHVIRUKHDWLQJDSSOLFDWLRQV
 7KDWFRPELQHGZLWKWKHFDSDELOLW\RIHQHUJL]LQJRQO\DVLQJOHVWDJHRIDPXOWLVWDJHERLOHUZKHQLQKLJKGHPDQGPDNHVWKH%&3
8W versatile for many industries.
287'2255(6(76(732,1725(;7(51$/0$6(732,17
 7KH%&3:FDQFRQWUROWKH6\VWHP7HPSHUDWXUHHLWKHUE\DGMXVWLQJWKHWDUJHWDFFRUGLQJWRWKH2XWGRRU7HPSHUDWXUH2XWGRRU
Reset) or by maintaining an adjustable Set Point. The Outdoor Reset option uses an Outdoor Sensor (supplied with the control) and
achieves better fuel savings in addition to better comfort.
 8VLQJWKHRSWLRQDO02',QWHUIDFHWKH%&3:FDQUHFHLYHDQH[WHUQDOVHWSRLQWWKURXJKDQ(06V\VWHP
3,'25266&21752//2*,&
 7KH%&3:3,'FDQEHXVHGIRUDSSOLFDWLRQVZKHUHV\VWHPUHDFWLRQis slow and requires a long period to achieve or measure the
results. However, OSS, can be used for applications where the load changes frequently and the sequencing must match the load and
its immediate change.
180%(52)67$*(6
 7KH%&3:FDQEHFRQ¿JXUHGWRFRQWUROXSWRHLJKWVWDJHV,WFDQFRQWUROXSWRVWDJHVXVLQJDPD[LPXPRIWZR%&3;
Extension Panels, each with eight stages.
67$*(38036259$/9(6
 7KH%&3:FDQFRQWUROPXOWLSOHVWDJHVLQDGGLWLRQWR boiler pumps or valves.
&21752/'+:3803$1'&20%867,21$,5'$03(5
 The control of the DHW is based on either a temperature sensor, can be purchased separately, on the DHW source or using a dry
contact from an aquastat. The BCP-8W provides multiple DHW Priority options based on the DHW piping. The Combustion Air
Damper output can be used in conjunction with the PROVE input to check the status of the Combustion Air Damper's End Switch,
6\VWHP3XPSV)ORZ6ZLWFKRUDQ\RWKHURSHUDWLQJGHYLFHEHIRUHDQ\VWDJHLVHQHUJL]HG
021,725%2,/(55(7851
 The optional return line sensor, is purchased separately, can be connected to monitor and help protect the boilers from thermal
shock and condensation caused by cool returns.
background
8
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
$8720$7,&527$7,21$021*%2,/(56
 5RWDWLQJWKHOHDGERLOHUWREHDFWLYDWHGRQDFDOOIRURXWSXWSURPRWHVHYHQZHDURQDOOERLOHUV7KH%&3:KDVWKUHHPRGHVRI
URWDWLRQ0DQXDO)LUVW2Q)LUVW2IIRU7LPHG5RWDWLRQ7KLVRSWLRQDXWRPDWLFDOO\URWDWHVWKHERLOHUVHYHU\VHOHFWHGSHULRGIURP
one hour to every 41 days (999 hours).
6(7%$&.%226725'$<1,*+76&+('8/,1*
7ZR6HWEDFNPRGHVDUHDYDLODEOHIRUWKH%&3:
 The Day/Night Scheduling provides an adjustable time-based schedule for the Setback. It will be available when Shutdown or Tstat
is selected from the External Input Startup menu options.
 :hen Setback is selected from the External Input Startup menu options, an external signal can be used to switch the operation of
the BCP-8W in and out of setback mode
 7KH%RRVWFDQEHXVHGWREULQJWKHEXLOGLQJWRFRPIRUWDEOHWHPSHUDWXUHVHWWLQJVDIWHUD1LJKWRU6HWEDFNSHULRG,WGRHVWKDWE\
increasing the target temperature for an adjustable period that follows the setback.
,167$//$7,21
Each of the BCP-8W and BCP-8X consists of three primary enclosure
components.
 7KH(QFORVXUH'LVSOD\0RGXOHFRQWDLQVWKHGLVSOD\EXWWRQV/('V
and electric wiring terminals. It has two screws to hold it to the base. A
SURJUDPFRQ¿JXUDWLRQVZLWFKXVHGWRDGMXVW%&3:VHWWLQJVLVSODFHG
above the terminals. This switch is enclosed with the Enclosure Wiring
Cover for security. The wiring terminals are of the plug-in type to ease
installation and removal.
 7KH(QFORVXUH%DVH contains the holes to mount and hold the control
DJDLQVWWKHZDOORUDQ\ÀDWVXUIDFH$OORWKHUHQFORVXUHFRPSRQHQWVPRXQW
on the base. The bottom section of the Enclosure Base contains the wiring
chamber with knockouts on the bottom to ease installation.
 7KH(QFORVXUH:LULQJ&RYHU seals the wires from the external
environment. It has two screws to hold it to the base and a hole to secure
a lock on the wiring enclosure. A plastic web that separates the wiring
chamber into high and low volt sections has been provided.
02817,1*7+((1&/2685(
 6HOHFWDORFDWLRQQHDUWKHHTXLSPHQWWREHFRQWUROOHG
 7KHVXUIDFHVKRXOGEHÀDWDQGVXI¿FLHQWO\ZLGHDQGVWURQJWRKROGWKH%&3
8W or BCP-8X.
 .HHSWKHFRQWURODZD\IURPH[WUHPHKHDWFROGRUKXPLGLW\$PELHQW
operating temperature is from 20 to 120°F.
 5HPRYHWKH(QFORVXUH:LULQJ&RYHUIURPWKHFRQWUROHQFORVXUHE\
removing the two bottom screws.
 5HPRYHWKH(QFORVXUH'LVSOD\0RGXOHE\UHPRYLQJWKHPLGGOHVFUHZV
 6FUHZWKH(QFORVXUH%DVHWRWKHVXUIDFHWKURXJKWKHXSSHUDQGORZHU
mounting holes on the back of the enclosure.
 5HSODFHWKH(QFORVXUH'LVSOD\0RGXOHDQGUHSODFHWKHPLGGOHVFUHZV
 'RQRWUHSODFHWKHHQFORVXUHZLULQJFRYHUXQWLODOOZLULQJLVGRQH
 :KHQSXUFKDVLQJDSDGORFNIRUWKHHQFORVXUHWKHPD[LPXPVKDQNGLDPHWHU
should not exceed ¼"
Mounting Base
Display Mounting Scr ews Wiring Cover Mounting Scr ews
Enclosure Display Module
Enclosure Wiring Cover Enclosure Base
Hole for optional
Padlock (not supplied)
background
9
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
S
,
1
6
7$//7+(
(1
62
5
6
6<
6
7(0
6
(1
62
5
,
1
6
7$//$7,
21
/
2&
$7,
1
*
7+(
6
<
6
7(0
6
(1
62
5
3XWW
K
H6\VWHPVHQVRUDSSUR[
L
PDWH
O
\IHHWSDVWW
K
H
O
DVW
K
HDW
L
QJ
E
R
LO
HURQW
K
H
common suppl
y
header but before an
y
takeoffs
.
7
KHVHQVRUPXVWEHORFDWHGZKHUHLWVHHVWKHRXWSXWRIDOOWKHVWDJHV,ID
b
o
il
er
i
s p
i
pe
d
so t
h
at t
h
e sensor
d
oes not see
i
ts output, t
h
e BCP-8W w
ill
no
t
s
equence the boilers correctl
y
.
2QO\XVHD6WDQGDUG%UDVV7XEHVHQVRU
7K
HVHQVRUZ
L
UHVFDQ
E
HH[WHQ
G
H
G
XSWRXV
L
QJDV
KL
H
OG
H
G
FRQ
G
XFWRU
FDEOH%HOGHQRUH
T
XLYDOHQ
W
(#18/2
)
)
. Do not
g
round the shield at the
s
ensor but at the panel using one of the terminals marked with an “O”
.
'RQRWUXQVHQVRUZ
L
UHV
L
QFRQ
G
X
L
WZ
L
W
K
OL
QHYR
O
WDJHZ
L
U
L
QJ
,00(5
6
,
2
1+
(
$7,1
*
6<
6
7(0
6
(1
62
5
+
66
,
1
6
7$//$7,
2
1
,QVWD
OO
D
,'
L
PPHUV
L
RQZH
OO


,QVHUWWKHVHQVRU
S
UREHRIWKHVX
SS
OLHGVHQVRULQWRWKHZHOO
6
75$3
2
1
+
(
$7,1
*
6
<
6
7(0
6
(1
62
5
+
66
,
1
6
7$//$7,
2
1
6WUDSWKHVHQVRUWRWKHSLSHXVLQ
J
PHWDOFODPSV'RQRWRYHUWL
J
KWHQWKH
clamp. The sensors's concave surface must be facing the pipe for bette
r
t
emperature rea
di
ng
.
6WUD
S
S
L
S
HLQVXODWLRQDURXQGWKHVHQVRUDQG
S
L
S
H
Immersion Well
3/8" ID 1/2" NPT
Heating System
Sensor
Common Supply Pipe
Sensor Probe
Immersion Heating System Sensor
Shield
Common Supply Pipe
Sensor Probe
Strap-On Heating System Sensor
Shield
Pipe Insulation
$
/(57
I
f
the
S
ystem
S
ensor can not sense the
correct s
y
stem water temperature bein
g
supplied to the buildin
g
, the BCP-8W will
not
p
rovide com
f
ortable heat level
s
.
B
e
sure that it is located on the main suppl
y
p
i
pe w
hi
c
h
can not eas
ily
b
e
i
so
l
ate
d
f
rom the syste
m
.
2
8
7'
22
5
6
(1
62
5
,
1
6
7$//$7,
21
2QO
\
XVHWKH:HLO0F/DLQVHQVRULQFOXGHGZLWKWKHXQLW
/
RFDWHW
K
HVHQVRU
L
QW
K
HV
K
D
G
HRQW
K
HQRUW
K
V
LG
HRIW
K
H
E
X
LOGL
QJ
7KH
VH
Q
VRU
s
h
ou
ld
never
b
e
i
n
di
rect sun
ligh
t
.
%HVXUHWKHORFDWLRQLVDZD
\
IURPGRRUVZLQGRZVH[KDXVWIDQVYHQWVR
U
ot
h
er poss
ibl
e
h
eat sources
.
7K
HVHQVRUV
K
RX
OG
E
HPRXQWH
G
DSSUR[
L
PDWH
O\
IHHWD
E
RYH
J
URXQ
G
O
HYH
O
$GKHUHWKH2XWGRRU/DEHO
S
URYLGHGWRWKHEDFNRIWKHVHQVRUEDVH
8
VHW
K
H(QF
O
RVXUH%DVH
E
RWWRP
N
QRF
N
RXWIRUW
K
HFRQ
G
X
L
W
8
VHW
K
H
O
RF
N
QXWWR
h
o
ld
t
h
e con
d
u
i
t an
d
enc
l
osure
b
ase to
g
et
h
er. Screw t
h
e cover to t
h
e
b
ase
.
,IVFUHZVDUHXVHGWRDI¿[WKHHQFORVXUHWRWKHZDOOPDNHVXUHWRVHDODURXQG
th
e sensor an
d
wa
ll
except from t
h
e
b
ottom
.
7K
HVHQVRUZ
L
UHVFDQ
E
HH[WHQ
G
H
G
XSWRXV
L
Q
J
V
KL
H
OG
H
G
FRQ
G
XFWRUFD
EO
H
(
#18/2
)
. Do not
g
round the shield at the sensor but at the control usin
g
the
t
erm
i
na
l
mar
k
e
d
w
i
t
h
an “
O
.
'RQRWUXQVHQVRUZ
L
UHV
L
QFRQ
G
X
L
WZ
L
W
K
OL
QHYR
O
WD
J
HZ
L
U
L
Q
J
:
$51,1
:
:
*
7KH
%&3
:
LV
D
Q
R
SHUDW
L
Q
J
FR
Q
W
U
RO
RQ
O\
$OO
H
TX
L
SPHQ
W
PXVW
KD
Y
H
DOO
V
DIHW
\
D
Q
G
OL
P
LW
FRQWUR
O
VUH
T
X
L
UH
G
E\
F
R
G
H
,W
LV
WK
H UHVSRQV
LELOL
W
\
RI
W
K
H
L
Q
VWD
OO
HU
WR
YHUL
I\
W
K
DW
D
O
O
W
K
H
VD
I
HW
\
OLPL
WV
DUH
Z
RUNLQ
J
S
URSHUO
\
EH
I
R
U
H
WKH
%
&3
:
LV
L
Q
VWDOOHG
Outdoor
Sensor
snap-in
location
Shield
not connected
Conduit
Outdoor Label
on back of Sensor
Outdoor Sensor
Mounting
screws
location
Seal around
sensor and wall
Outdoor
drip-hole
$
/(57
'
HWHUP
L
Q
L
QJ W
KH
SURSHU
O
RFDW
L
R
Q
IR
U
W
KH
2XWGRR
U
6HQVRU
LV
Y
HU\
L
P
S
RUWDQW
7KH
%&3
:
ZLOO
E
DV
H
L
WV
RSHUDWLR
Q
RQ
W
K
H
RXWGRR
U
W
HPSHUD
W
XU
H
LQ
IR
UP
DW
L
R
QL
W
U
HFH
LY
HV
I
U
RP
W
KL
V
ORFDW
L
R
Q
,
I
W
K
H
VHQVRU
L
V
L
Q
W
K
H
V
X
Q
RU
FRYHUH
G
ZL
W
K
L
FH
L
W
V
U
HD
GL
Q
J
ZLOO
E
H
G
LIIHUHQ
W
I
UR
P
WK
H
D
FWXD
O
2
XWGRR
U
W
HP
S
HUDWXUH
background
10
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
:,5,1*
:,5,1*7+(32:(57(50,1$/6
 %ULQJWKH9$&+]SRZHUZLUHVWKURXJKWKHERWWRP.QRFNRXWRIWKHHQFORVXUH
 &ODVVYROWDJHZLULQJPXVWHQWHUWKHHQFORVXUHWKURXJKDGLIIHUHQWRSHQLQJIURPDQ\&ODVVYROWDJHZLULQJ
 &RQQHFWWKHKRWOLQHWRWKHWHUPLQDOPDUNHG/
 &RQQHFWWKHQHXWUDOOLQHWRWKHWHUPLQDOPDUNHG1
:$51,1*
&ODVVYROWDJHZLULQJPXVWHQWHUWKHHQFORVXUHWKURXJKDGLIIHUHQWRSHQLQJIURPDQ\&ODVVYROWDJH
ZLULQJ:HLO0F/DLQUHFRPPHQGVLQVWDOOLQJDVXUJHVXSSUHVVRURQWKHSRZHUVRXUFHWRWKH%&3:
Line
Neutral
120VAC
Power Source
PWR
LN
12
:$51,1*
&RQQHFWWKH7HPSHUDWXUHVHQVRUVKLHOGDWWKHFRQWUROWRWKHVHQVRUWHUPLQDOPDUNHG2
'RQRWFRQQHFWWKH6KLHOGDWWKHVHQVRUHQG
27 2928 3
02
5 26
TEMP
Sensor Shiled
System Sensor
OUTDOO
R
TEMP
:,5,1*7+(6(16256
6<67(07(03(5$785(6(1625:,5,1*7(50,1$/6
 7KH%&3:LVGHVLJQHGWREHFRQQHFWHGWRDWHPSHUDWXUHVHQVRUIRULPPHUVLRQLQD,'ZHOO
located on the common header. Contact the factory for additional temperature sensor options.
 7HPSHUDWXUHVHQVRUZLUHVFDQEHH[WHQGHGXSWR¶E\VSOLFLQJVKLHOGHGFRQGXFWRUFDEOH%HOGHQRU
equivalent (#18/2)).
 7HPSHUDWXUHVHQVRUVKDYHQRSRODULW\&RQQHFWWKHWZRZLUHVIURPWKHVHQVRUWRWKH%&3:WHUPLQDOVPDUNHG
SYSTEM TEMP 27, 28.
 &RQQHFWWKHVKLHOGWRWKHFLUFOHGWHUPLQDOZLWKRQHRIWKHVHQVRUZLUHV'RQRWFRQQHFWWKHVKLHOGDWWKH
sensor end.
287'2256(1625:,5,1*7(50,1$/6
 :KHQ2XWGRRU5HVHWLVVHOHFWHGWKH%&3:ZLOOYDU\WKHV\VWHPWDUJHWEDVHGRQWKHRXWGRRUWHPSHUDWXUH
 :KHWKHULQ6HW3RLQWRU2XWGRRU5HVHWPRGHVWKHRXWGRRUVHQVRUFDQEHXVHGDVDQ2XWGRRU&XWRII7KH%&3
8W will disable all Boilers when the outdoor temperature is above the adjustable Outdoor Cutoff temperature.
This feature will automatically be activated when an outdoor sensor is connected.
 )RUDQRXWGRRUVHQVRUXVHWKHSURYLGHG:HLO0F/DLQRXWGRRUVHQVRU
 7KHVHQVRUZLUHVFDQEHH[WHQGHGXSWR¶XVLQJVKLHOGHGFRQGXFWRUFDEOH%HOGHQRUHTXLYDOHQW
(#18/2)).
 7HPSHUDWXUHVHQVRUVKDYHQRSRODULW\&RQQHFWWKHZLUHVIURPWKHRXWGRRUVHQVRUWRWKH%&3:WHUPLQDOV
marked OUTDOOR TEMP - 29, 30. Connect the shield to the circled terminal 30 with one of the sensor wires.
Do not connect the shield at the sensor end.
Sensor Shiled
Outdoor Sensor
29 31
D
328 30 32
MP
OUTDOOR
TEMP
RETURN
TEMP
5(78516(1625:,5,1*7(50,1$/6237,21$/$9$,/$%/(,1+($7,1*21/<
 ,IWKH5HWXUQ6HQVRULVFRQQHFWHGPXVWEHSXUFKDVHGVHSDUDWHO\WKH%&3:ZLOOUHFRJQL]HLWDQGDOWHUQDWHLWV
temperature on the display with the Target temperature. If the Return is below the Minimum Return, the BCP-
8W will sequence stages based on the Return Sensor, Minimum Return, Calculated Target, and the actual System
Temperature.
 7KH5HWXUQRQWKH%&3:LVGHVLJQHGWREHFRQQHFWHGWRDWHPSHUDWXUHVHQVRUWKDWFDQEHSXUFKDVHGVHSDUDWHO\
IRULPPHUVLRQLQD,'ZHOO
 7KHVHQVRUZLUHVFDQEHH[WHQGHGXSWR¶XVLQJVKLHOGHGFRQGXFWRUFDEOH%HOGHQRUHTXLYDOHQW
(#18/2)).
 7HPSHUDWXUHVHQVRUVKDYHQRSRODULW\&RQQHFWWKHZLUHVIURPWKHRXWGRRUVHQVRUWRWKH%&3:WHUPLQDOV
marked OUTDOOR TEMP - 31, 32.
 &RQQHFWWKHVKLHOGWRWKHFLUFOHGWHUPLQDO32 with one of the sensor wires. Do not connect it to the sensor.
31
DHW
3330 32 34
Sensor Shiled
Return Sensor
D
OOR
MP
RETURN
TEMP
background
11
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
:,5,1*7+('20(67,&+27:$7(5'+:6(16257(50,1$/6
 7KH'+:LQSXWFDQEHXVHGWRUDLVHV\VWHP6HW3RLQWWR)RU0D[LPXP7DUJHWZKLFKHYHULVORZHU7KH
DHW Piping on page 18 must be selected from the Startup Menu to determine the DHW Priority options.
 DHW Call terminals can be connected to either a dry-contact or a temperature sensor that can be purchased
VHSDUDWHO\IRULPPHUVLRQLQD,'ZHOO
 ,IXVLQJDGU\FRQWDFWZLUHDQDTXDVWDWRURWKHUFRQWUROVWRSURYLGHGU\FRQWDFWFORVXUHRQWKHDHW terminals.
 ,IXVLQJDVHQVRUWKHVHQVRUZLUHVFDQEHH[WHQGHGXSWR¶XVLQJVKLHOGHGFRQGXFWRUFDEOH%HOGHQRU
equivalent (#18/2)).
 7HPSHUDWXUHVHQVRUVKDYHQRSRODULW\&RQQHFWWKHZLUHVIURPWKH'+:VHQVRUWRWKH%&3:WHUPLQDOV
marked DHW - 33, 34. Connect the sensor shield to the circled terminal 34 with one of the sensor wires. Do not
connect the shield to the sensor.
 ,I6KXWGRZQZDVVHOHFWHGDVWKH([WHUQDO,QSXWDQ\'+:FDOOZLOOEHLJQRUHGZKHQWKH6KXWGRZQLVDFWLYH
Sensor Shiled
DHW Sensor
DHW
33 35
3
23436
3
P
SHUTDOWN
/TSTAT
/SETBACK
R
N
P
:,5,1*7+(6+87'2:17(50,1$/6
 7KLVIHDWXUHZLOORQO\EHDYDLODEOHZKHQ6KXWGRZQLVVHOHFWHGDVWKH([WHUQDO,QSXW0RGHRQSDJH18.
 7KLVIHDWXUHFDQEHXVHGZKHQHYHULWLVGHVLUDEOHWRWXUQRIIWKH%&3:VWDJHRXWSXWVIURPDUHPRWHORFDWLRQRU
another controller (i.e. EMS input).
 :KHQWKH6KXWGRZQLVHQDEOHGDOODFWLYHVWDJHVZLOOLPPHGLDWHO\WXUQRII7KH6\VWHP3XPS&RPEXVWLRQ$LU
DQGERLOHUSXPSVRUYDOYHVUHOD\VZLOOUHPDLQHQHUJL]HGIRUWKH5XQ2QGHOD\SHULRGDQGWKHQWXUQRII
 7KH6KXWGRZQVLJQDOPXVWEHDGU\FRQWDFWLQSXW1RYROWDJHFDQEHSODFHGDFURVVWKHSHUTDOWN terminals.
 %ULQJWKHWZRZLUHVIURPWKHGU\FRQWDFWWRWKHSHUTDOWN- 35,36 terminals.
 :KHQ6KXWGRZQLVVHOHFWHG6HWEDFNZLOOEHDYDLODEOHXVLQJWKHSURJUDPPHG'D\1LJKWVFKHGXOH
D
HW
3
3534 36
37 38
PROVE
Shutdown
Dry Contact
SHUTDOWN
/TSTAT
/SETBACK
:,5,1*7+(767$77(50,1$/6
 7KLVIHDWXUHFDQEHXVHGZKHQHYHULWLVGHVLUDEOHWRVZLWFKWKH%&3:WRRSHUDWHIURPDUHPRWHORFDWLRQLH
EMS input or thermostat). It will only be available when Tstat is selected as the External Input Mode option
from the Startup menu on page 18.
 :KHQWKH7VWDWLVHQDEOHGE\FORVLQJDGU\FRQWDFWWKH%&3:ZLOODFWLYDWHWKHKHDWLQJORJLF
 7KH7VWDWVLJQDOPXVWEHDGU\FRQWDFWRQO\1RYROWDJHFDQEHSODFHGDFURVVWKHTSTAT terminals.
 %ULQJWKHWZRZLUHVIURPWKHGU\FRQWDFWWRWKHTSTAT- 35,36 terminals.
 $IDFWRU\LQVWDOOHGMXPSHUSURYLGHVWKH7VWDWVLJQDO'RQRWUHPRYHWKHMXPSHUXQOHVVLWZLOOEHUHSODFHGE\D
Tstat signal.
 :KHQ7VWDWLVVHOHFWHGIURPWKH6WDUWXS([WHUQDO,QSXWPRGH6HWEDFNZLOOEHDYDLODEOHXVLQJWKHSURJUDPPHG
Day/Night schedule.
33 3534 36
37 38
PROVE
SHUTDOWN
/TSTAT
/SETBACK
Auxiliary
Input3
T-Stat
Dry Contact
:,5,1*7+(6(7%$&.7(50,1$/6
 7KLVIHDWXUHFDQEHXVHGZKHQHYHULWLVGHVLUDEOHWRVZLWFKWKH%&3:WRRSHUDWHLQ6HWEDFNIURPDUHPRWH
location (i.e. EMS input or external time clock). It will only be available when Setback is selected as the
External Input Mode option from the Startup menu. See page 18.
 :KHQWKH6HWEDFNLVHQDEOHGE\FORVLQJDGU\FRQWDFWWKH7DUJHWZLOOFKDQJHE\WKH6HWEDFNYDOXH7KDWLVWKH
Target will be reduced by the Setback value.
 7KH6HWEDFNVLJQDOPXVWEHDGU\FRQWDFWRQO\1RYROWDJHFDQEHSODFHGDFURVVWKHSETBACK terminals.
 %ULQJWKHWZRZLUHVIURPWKHGU\FRQWDFWWRWKHSETBACK- 35,36 terminals.
 :KHQ6HWEDFNLVVHOHFWHG1R'D\1LJKW6FKHGXOLQJZLOOEHDYDLODEOH
D
HW
3
SHUTDOWN
/TSTAT
/SETBACK
3534 36
37 38
PROVE
Setback
Dry Contact
:,5,1*7+(3529(7(50,1$/6
 7KH3URYHIHDWXUHLVSURYLGHGWRFKHFNV\VWHPFRPSRQHQWRSHUDWLRQEHIRUHHQHUJL]LQJWKHVWDJHV,WFDQEH
used to check on the Combustion Air Damper by connecting it to the end switch of the damper. In this case,
the Comb. Air Output option must be activated from the Startup Menu on page 18.
 ,IWKH&RPE$LU'DPSHU2XWSXWRSWLRQZDVQRWDFWLYDWHGWKHPROVE input can be used to check on the
6\VWHP2XWSXW$W\SLFDOXVHRIWKLVIHDWXUHLVWRFKHFNIRUV\VWHPSXPSÀRZEHIRUHHQHUJL]LQJDQ\VWDJH
 ,IWKHPROVE input is open on a call, the BCP-8W will enable only the System Output. All stage outputs will
be off when the PROVE input is open.
 $IDFWRU\LQVWDOOHGMXPSHUSURYLGHVWKH6\VWHP3URYHVLJQDO'RQRWUHPRYHWKHMXPSHUXQOHVVLWZLOOEH
replaced by a System Prove signal.
 %ULQJWKHWZRZLUHVIURPWKHGU\FRQWDFWWRWKHPROVE - 37, 38 terminals. No voltage can be placed across the
PROVE terminals
Prove
Dry Contact
RS485
36
37 38
PROVE
D
OWN
T
AT
B
ACK
background
12
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
:$51,1*
7KH3529(LQSXWFDQQRWEHXVHGDVDVDIHW\OLPLW$OOHTXLSPHQWPXVWKDYHLWVRZQFHUWL¿HGOLPLWDQGVDIHW\
controls as required by local codes. No boiler stage will start unless the Prove terminals are shorted. DO NOT
remove the PROVE jumper supplied unless replacing it with a Prove signal.
:,5,1*7+(6<67(02873877(50,1$/6
 7KH6\VWHPRXWSXWKDVD1RUPDOO\2SHQ12UHOD\WKDWDFWVDVDGU\FRQWDFW,WGRHVQRWVRXUFHDQ\SRZHU
 &ODVVYROWDJHVPXVWHQWHUWKHHQFORVXUHWKURXJKDGLIIHUHQWRSHQLQJIURPDQ\&ODVVYROWDJHZLULQJ
6\VWHP2XWSXW2SHUDWLRQLQ6HW3RLQW0RGH
 7KH6\VWHPRXWSXWUHOD\ZLOOHQHUJL]HZKHQHYHUWKHRXWGRRUWHPSHUDWXUHGURSVEHORZWKH2XWGRRU&XWRIIRU
ZKHQHYHUDVWDJHRXWSXWLVDFWLYH,IQRRXWGRRUVHQVRULVFRQQHFWHGDQGWKHODVWERLOHUUHOD\KDVGHHQHUJL]HG
WKH6\VWHPUHOD\ZLOOUHPDLQHQHUJL]HGIRUDSHULRGVHWE\WKH5XQ2QDQGWKHQGHHQHUJL]H
 ,IWKHPROVELQSXWLV2SHQWKH6\VWHPUHOD\ZLOOUHPDLQHQHUJL]HGKRZHYHUDOOVWDJHVZLOOEHGHHQHUJL]HG
If a Prove is not required, the factory-installed jumper must remain connected for proper operation.
System
Pump
SYSTEM
DHW
PUMP
17
16 18
ge G
19
Stage H
2120 22
L
N
 $W\SLFDOXVHRIWKH6\VWHPRXWSXWLVWRDFWLYDWHDV\VWHPSXPSRULWVVWDUWHU7KHSXPSFDQUXQZKHQHYHUWKHUHLVDFDOOIRU
KHDW:KHQVWDJHVDUHQRORQJHUUHTXLUHGWKHSXPSZLOOVWD\DFWLYHIRUDQDGMXVWDEOH5XQ2QGHOD\DQGWKHQGHHQHUJL]H
6\VWHP2XWSXW2SHUDWLRQLQ5HVHW0RGH
 7KH6\VWHPRXWSXWUHOD\ZLOOHQHUJL]HZKHQHYHUWKHRXWGRRUWHPSHUDWXUHLVEHORZWKH2XWGRRU&XWRII
 :KHQWKHRXWGRRUWHPSHUDWXUHULVHV)DERYHWKH2XWGRRU&XWRIIWKH6\VWHPRXWSXWZLOOUHPDLQHQHUJL]HGIRUWKHSHULRGVHW
by the System Run-OnDQGWKHQGHHQHUJL]H.
:,5,1*7+('+:38037(50,1$/6
The BCP-8W can control the DHW Pump when the DHW Pump Output option is activated from the Startup Menu.
See page 18.
 7KH%&3:ZLOOHQHUJL]HWKH'+:3XPSZKHQHYHUWKHUHLVDFDOOIRU'+:XVLQJDGU\FRQWDFWRUZKHQWKH
DHW temperature falls below the DHW Set Point and DHW Differential when using a DHW sensor.
 7KH'+:3XPSRXWSXW relay is a Normally Open (N.O.) dry contact. It does not source any power.
 &ODVVYROWDJHVPXVWHQWHUWKHHQFORVXUHWKURXJKDGLIIHUHQWRSHQLQJIURPDQ\&ODVVYROWDJHZLULQJ
 ,I6KXWGRZQZDVVHOHFWHGDVWKH([WHUQDO,QSXWSDJH18), The BCP-8W will ignore a DHW call when the
Shutdown is active.
DHW
Pump
DHW
PUMP
7
18
19
a
ge H
2120 22
23
CO
M
A
I
SYSTEM
L
N
:,5,1*7+(&20%867,21$,5'$03(57(50,1$/6
The BCP-8W can control the Combustion Air Damper when the Comb. Air Output option is activated in the Startup
Menu (Page 18). In addition, the PROVE input will function as the Combustion Air Damper status checker.
 7KH%&3:ZLOOHQHUJL]HWKH&RPEXVWLRQ$LU'DPSHUUHOD\ZKHQHYHUWKHUHLVDFDOOWRHQHUJL]HDQ\RIWKH
boiler stages.
 7KH&RPEXVWLRQ$LURXWSXW relay is a Normally Open (N.O.) dry contact. It does not source any power.
 &ODVVYROWDJHVPXVWHQWHUWKHHQFORVXUHWKURXJKDGLIIHUHQWRSHQLQJIURPDQ\&ODVVYROWDJHZLULQJ
DHW
PUMP
21
0
22
23 24
COMB.
AIR
E
M
Comb.
Air
Damper
L
N
:,5,1*7+(67$*(67(50,1$/672
7KH%&3:FDQEHFRQ¿JXUHGWRRSHUDWHWKHVWDJHVRIWKHERLOHUV0RUHRYHULWFDQEHFRQ¿JXUHGWR
operate the boiler pumps or valves in addition to the boiler stages.
 7KHUHOD\VDUHN.O. dry contacts only. They do not source any voltage.
 :LUHWKH12UHOD\FRQWDFWVLQVHULHVZLWKWKHERLOHUVOLPLWFLUFXLW
 &ODVVYROWDJHVPXVWHQWHUWKHHQFORVXUHWKURXJKDGLIIHUHQWNQRFNRXWIURPDQ\&ODVVYROWDJH
wiring.
:,5,1*7+(67$*(2873876
 (DFK6WDJHRXWSXW$WKURXJK+KDVRQH12UHOD\
 :KHQZLULQJVHYHUDOPXOWLVWDJHERLOHUVVWDUWZLWKWKHORZHUVWDJHRIWKH¿UVWERLOHUDQGZLUHLWWR
Output A, followed by the higher stage of the same boiler and wire it to Stage B.
35
Stage A
7
Stage B
9
Stage C
11
Stage
Stage D
6 8 10 14
Lo Hi
Unit1
Stages
Lo Hi
Unit2
Stages
background
13
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
:,5,1*7+(3803259$/9(2873876
 ,IWKH%&3:LVFRQ¿JXUHGWRRSHUDWH6WDJH3XPSVRU9DOYHV7KH\PXVWEHZLUHGWRWKHVWDJH
RXWSXWDIWHUWKHKLJKHVWVWDJHIRUWKDWERLOHU7KDWLVWKHORZVWDJHIRUWKH¿UVWERLOHUPXVWEH
connected to A and the higher stage of the same boiler must be connected to Stage B. The boiler
valve or pump for the same boiler must be connected to Stage C.
N
2
35
Stage A
7
Stage B
9
Stage C
11 13
Stage E Stage F
Stage D
6 8 10 12 144
Lo Hi
Unit1
Stages
Unit1
Pump
Lo Hi
Unit2
Stages
Unit2
Pump
L
N
&211(&7,1*727+(%&3;3$1(/6$1'02',17(5)$&(
 7KH%&3:LVHTXLSSHGZLWKDSKRQHVRFNHW56WRFRQQHFWWRWKH%&3;([WHQVLRQSDQHOVRUWKH02',QWHUIDFH
XVLQJWKHSURYLGHGSLQSKRQHFDEOH
 (DFK%&3;([WHQVLRQKDVWZR56FRPPXQLFDWLRQSRUWV8VHRQHWRFRQQHFWWRWKH%&3:8VHWKHRWKHUSRUWWR
connect to the second extension or the 420MOD Interface.
 $GGLWLRQDOFRPSDWLEOHGHYLFHVFDQXWLOL]HWKHVHFRQG56FRQQHFWLRQRQWKHVHFRQG%&3;([WHQVLRQ$QH[DPSOHZRXOG
EHWRXVHWKH02',QWHUIDFHWRSURYLGHDP$VHWSRLQWVLJQDOWRWKH%&3:
6(/(&7,1*7+(%&3;3$1(//(77(5
 7KH%&3:LVFDSDEOHRIFRPPXQLFDWLQJWRWZR%&3;([WHQVLRQV+RZHYHUHDFK
H[WHQVLRQPXVWEHLGHQWL¿HGDVHLWKHU$RU%XVLQJWKHVZLWFKRQHDFKH[WHQVLRQWRDYRLGKDYLQJ
communication problem.
 ([WHQVLRQ$6ZLWFKLVVHWWR$ZLOORSHUDWHVWDJHV,WKURXJK3:KLOH([WHQVLRQ%
(Switch is set to "B") will operate stages "Q" through "X".
Ext A
Ext B
Connecting BCP-8 to Two Extension Panels
and 420MOD Interface using RS485
BCP-8
HYDRONIC SEQUENCING CONTROL
SYSTEM
DHW PUMP
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
LN
12
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11 13
Stage E
15
Stage F
17
Stage D
6 8 10 12 14
16 18
RS485
SYS=144F OD=35F
<AB
>DE GH JK
HI LO -- OFF
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27 29 31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20 22 28 30 32 34 36
STAGE MENU
Stage E
Stage F
Stage G
Stage H
Stage A
Stage B
Stage C
Stage D
25 26
PRESS
+ -
37 38
PROVE
TEMP
PROGRAM RUN
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
COMB. AIR
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
CUS
O
P
Power
CAUTION:
Risk of Electric Shock.
PWR
LN
12
I
34
J
56
K
78
L
910
M
11 12
EXTENSION
MODULE
RS-485
Ext A
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
Ext B
L
M
N
Comm
T
U
V
W
X
N
13 14
Q S UR T V
BCP-8X A
Use Copper Conductors Only.
I
J
K
Q
R
S
O
15 16
P
17 18
W X
O
P
Power
CAUTION:
Risk of Electric Shock.
PWR
LN
12
I
34
J
56
K
78
L
910
M
11 12
EXTENSION
MODULE
RS-485
Ext A
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS
Ext B
L
M
N
Comm
T
U
V
W
X
N
13 14
Q S UR T V
BCP-8X B
Use Copper Conductors Only.
I
J
K
Q
R
S
O
15 16
P
17 18
W X
4-20 mA EMS
4-20mA INPUT
+
Signal GND
1
2
3
RS485
EXTENSION
CONNECTORS
420MOD EMS Interface
4-20mA
EMS Signal
(+)
(-)
6 Pin Phone Cable (provided with Extension)
6 Pin Phone Cable (provided with 420MOD EMS Interface)
SEQUENCING CONTROL EXTENSION
BCP-8X
SEQUENCING CONTROL EXTENSION
BCP-8X
BCP-8W
background
14
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
S
-
-----
SETTINGS
------
S
eason
Wi
n
t
er
<
Outdoor Rst>
1
35 F
Set Point
135
F
EMS Set Point
135
F
Mi
n
R
e
t
urn
110
F
<
System Settings>
<
Maintenance>
<System Startup>
BACK SELECT
,
167$//(5
0
(18
6
(
4
8(1&(
SYS
=
168
FOD
=
45
F
TGT
=
172
F
ABC <EFG >
---- LO
BOILER MENU
-
--- CONTROL MODE --
-
Outdoor Reset
Set Point
EMS 4-20m
A
BACK SAVE
-
--- DISPLAY UNIT --
-
F
C
BACK SAVE
EMS 4mA SET POINT
100
F
[
]
BACK SAVE
E
MS 20mA SET POIN
T
170
F
[
]
BACK SAVE
-
---
DHW PIPING
---
Parallel
Primary/Secondar
y
BACK SAVE
-
-DHW PUMP OUTPUT--
No
Yes
BACK SAVE
-
-COMB. AIR OUTPUT--
No
Yes
BACK SAVE
-
-- BURNER TYPE ----
On/Off
2
-
Stage
3
-Stage
4
-Stage
BACK SAVE
-
-
BOILER OUTPUT
-
-
None
Pump
V
alve
BACK SAVE
-
-
TOTAL BOILERS
-
-
8
[
]
BACK SAVE
-
-----
STAGING
------
M
ultiple Outputs
S
ingle Outpu
t
BACK SAVE
-
-----
SEQUENCE
-------
Lo/Hi/Lo/Hi
Lo/Lo/Hi/Hi
BACK SAVE
-
-- CONTROL LOGIC---
PID
OSS
BACK SAVE
-
-- SENSOR FAULT ---
Stages On
Stages Off
BACK SAVE
ARE YOU SURE
?
No
Yes
BACK SAVE
(
06 6(
7
32,17
-
---
MAINTENANCE
----
U
n
it
F
Present Time
12
:
30P
<
Sensor Trim>
<Hi
s
t
or
i
es
>
<Configuration>
BACK SELECT
--- SENSOR TRIM ---
-
System Trim
+0
F
Outdoor Trim
+0
F
Return Trim
+0
F
D
HW Trim +0 F
BACK SELECT
Sys=12
0
F
1
0:00AM
BACK NEXT
BCP
-
8W V1.00
Outdoor reset
D
ay/Night Schedul
e
D
HW Parallel
BACK SELECT
$
/
(57
7RDFFHVV,QVWDOOHU0HQXKROG
do
wn th
e
M
e
n
u
bu
tt
o
n f
o
r
o
v
er
t
h
ree secon
ds
.
7REHDEOHWRFKDQ
J
HWKH%
&
3:
s
ettings the Program/Run Switch
m
ust
b
e set to
P
rogra
m
.
6
6
7$5783
&
0
$,17(1$1
&
(
-
-
EXTERNAL INPUT -
Shutdown
Tstat
Setback
BACK SAVE
background
15
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
S
-
----
SETTINGS
-----
-
Season
Winter
<O
u
td
oor
R
s
t>
135
F
S
et Poin
t
1
35
F
EMS Set Point
135
F
Min Return
110
F
<System Settings>
<
Maintenance>
<
System Startup>
BACK SELECT
----
SEASON
--
-
Winter
Summe
r
BACK SAVE
--
OUTDOOR RESET
-
Reset Ratio
7
Target Offset +0 F
Outdoor Cutoff 65 F
Min.Target
120
F
Max.Target
120
F
BACK SELECT
-
--- RESET RATIO ---
C
us
t
om
1(8.00
OD
:
1.00
SYS)
2(4.00
OD
:
1.00
SYS)
3
(3.00
O
D:1.00
S
YS)
4(2
.
00
OD
:
1
.
00
SYS)
5(1.50
OD
:
1.00
SYS)
6(1.25
OD
:
1.00
SYS)
7(1.00
O
D:1.00
S
YS)
8(1.00
O
D:1.25
S
YS)
9(1.00
O
D:1.50
S
YS)
10(1.00
OD
:
2.00
SYS)
11(1.00
OD
:
3.00
SYS)
12(1.00 OD:4.00
S
YS)
BACK SAVE
-
- SET SYS TEMP.1
-
100
F
[
]
]
BACK SAVE
--
AT OD TEMP.1
---
7
0
F
[
]
]
BACK SAVE
--
SET SYS TEMP.2
-
170
F
[
]
BACK SAVE
-- AT OD TEMP.2 ---
0
F
[
]
BACK SAVE
-- TARGET OFFSET --
-
+
0
F
[
]
BACK SAVE
-- OUTDOOR CUTOFF -
-
60
F
[
]
BACK SAVE
---- MIN TARGET ---
-
140
F
[
]
BACK SAVE
----
MAX TARGET
---
-
20
0
F
[
]
BACK SAVE
-
----
SET POINT
----
-
140
F
[
]
BACK SAVE
-
-
EMS SET POINT
-
-
140 F
BACK SAVE
- SYSTEM SETTINGS -
<Stage Settings>
<Setback Schedule>
<DHW Settings
>
Setback
0
F
Run
-
On
2min
Pump Exercise
Off
BACK SELECT
-
---
MIN RETURN
----
120
F
[
]
BACK SAVE
-
---
RETURN LAG
----
2min
[
]
BACK SAVE
---
PUMP EXERCISE
-
-
Off
On
BACK SAVE
-
------
RUN
-
ON
------
-
2min
[
]
BACK SAVE
-
-----
SETBACK
------
-
0 F
[ ]
BACK SAVE
-- DHW SETTINGS ---
D
HW Temp
.
120 F
DHW
Prior
Tmr
60min
DHW Set Point
120
F
D
HW Diff
.
5 F
BACK SELECT
DHW PRIORITY TIMER
2min
[
]
BACK SAVE
-
-
DHW SET POINT
--
140
F
[
]
BACK SAVE
DHW DIFFERENTIAL
10
F
[
]
]
BACK SAVE
SYS=168 F OD=45
F
TGT
=
172
F
ABC
<EFG
>
---- L
O
BOILER MENU
'+:
6
6
(77,1
*
*
6
6
6
5(
6
(
7
2
5$7,
2
6
6
(
7
2
3
2
,1
7
background
16
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
S
-----
SETTINGS
------
Season
W
inter
<Outdoor Rst>
1
35
F
Set Point
135
F
EMS Set Point
135
F
Mi
n
R
e
t
urn
110
F
<System Settings>
<Maintenance>
<System Startup>
BACK SELECT
- SYSTEM SETTINGS
-
<Stage Settings
>
<Setback Schedule>
<DHW Settings>
Setback
0
F
Run-O
n
2
min
Pump Exercise
O
ff
BACK SELECT
--
STAGE SETTINGS
-
-
Reaction Time
1min
Purge Delay
0.0min
Min Runtim
e
2min
Standby Dela
y
10min
Last
Stage
Hold
5
F
Throttle
2
F
<Lead Settings
>
BACK SELECT
--
LEAD SETTINGS
--
Lead Boiler
AB
R
otate Mode Time
BACK SELECT
--
REACTION TIME
--
1mi
n
[
]
]
BACK SAVE
---
PURGE DELAY
---
-
1.0min
[ ]
BACK SAVE
- MINIMUM RUNTIME
-
2mi
n
[
]
]
BACK SAVE
-- STANDBY DELAY --
10mi
n
[
]
]
BACK SAVE
LAST STAGE HOLD
0
F
[]
BACK SAVE
SYS=
168
F OD=
45
F
TGT
=
172
F
ABC <EF
G
>
---- LO
BOILER MENU
-
---- BOILER AB ----
-
Mode
Auto
Runtime
58Hrs
<Prev Boiler>
<Next Boiler>
BACK SAVE
-
- BOILER AB MODE -
A
uto
S
tandby
Off
On
BACK SAVE
B
OILER AB RUNTIM
E
58hrs
BACK CLEAR OK
S
ETBACK SCHEDUL
E
Setbac
k
0
F
Present Time
**:**
Day Schdul
7
:
00Am
Night Schdu
l
7
:00P
m
BACK SELECT
------
SETBACK
------
-
0
F
[
]
BACK SAVE
-- NIGHT SCHEDULE -
-
07
:**
Pm
BACK SAVE
--
DAY SCHEDULE
---
-
07:**Am
BACK SAVE
- SET PRESENT TIME
**:*
*
BACK SAVE
--
LEAD BOILER
--
A
B
CD
BACK SELECT
-- LEAD ROTATION --
T
ime
Manual
FOFO
BACK SELECT
AUTO ROTATE PERIOD
24hr
s
[
]
BACK SAVE
-
-------
BOOST
---------
0
F
[
]
BACK SAVE
-
-----
BOOST PERIOD
--
-
30min
[
]
]
BACK SAVE
-- THROTTLE RANGE -
-
2
F
[]
BACK SAVE
6
6
7
$
*
*
(
6
6
(77,
1
*
*
6
6
6& 6
6&
+('
8
/(
6
1
R
W
$
YD
LO
D
EOH
Z
K
H
Q
6
HWEDF
N
LV
6
HOHFWH
G
I
UR
P
S
6
WDUWX
S
0
HQX
6
6
7
$
*
*
(
0(18
background
17
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
67$57836(77,1*6
Can be accessed by holding down the Menu
button for over three seconds.
352*5$0&+$1*(6(77,1*6
To be able to change the BCP-8W settings the Program/Run Switch must be set to Program.
The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring
Cover can be securely closed using a padlock.
PROGRAM RUN
67$57836(48(1&(
Hold Button: MENU/<System Startup>
 :KHQSRZHUHGWKH%&3:SHUIRUPVDVHOIWHVWRQLWVFRPSRQHQWV$IWHUWKHVHOIWHVW
GLDJQRVWLFVKDYHEHHQVXFFHVVIXOO\FRPSOHWHGWKH%&3:ZLOOLQLWLDOL]HWKHSDQHO
 2QWKH¿UVWSRZHUXSWKH6\VWHP6WDUWXSVFUHHQZLOODSSHDUDIWHUWKHLQLWLDOL]DWLRQLV
FRPSOHWH,ILWGRHVQ¶WWKH%&3:KDVDOUHDG\EHHQFRQ¿JXUHG
ARE YOU SURE?
No
Yes
BACK SAVE
 7KH6\VWHP6WDUWXSPHQXVHWVWKHPDLQSDUDPHWHUVDVWKHW\SHRIVHQVRUWKHVHTXHQFLQJPRGHDQGPDQ\RWKHUSDUDPHWHUV
described in this section.
 %HIRUHHQWHULQJWKH6WDUWXSPHQXVHYHUDOZDUQLQJVZLOODOHUW\RXWRWKHFRQVHTXHQFHVRIPDNLQJ6WDUWXSFKDQJHV
&21752/02'(
2XWGRRU5HVHW6HW3RLQW(06P$ 'HIDXOW2XWGRRU5HVHW
Hold Button: MENU/<System Startup>/..../Control Mode
 2XWGRRU5HVHWSURYLGHVDYDULDEOHVHWSRLQWEDVHGRQRXWGRRUWHPSHUDWXUH
 2XWGRRU5HVHWPRGHUHTXLUHVWKHXVHRIDQRXWGRRUVHQVRU'2127VHOHFW2XWGRRU
Reset without an outdoor sensor.
---- CONTROL MODE ---
Outdoor Reset
Set Point
EMS 4-20mA
BACK SAVE
 6HW3RLQWPRGHGRHVQRWUHTXLUHDQRXWGRRUVHQVRU,IDQRXWGRRUVHQVRULVFRQQHFWHGLQ6HW3RLQWPRGHLWZLOOEHXVHGRQO\DV
an Outdoor Cutoff point. That is, to turn the stages, system, and Comb. Air relays off.
 7KH(06P$DOORZVWKH%&3:WRUHFHLYHDQH[WHUQDOVHWSRLQWIURPDQ(06%06V\VWHP7KLVRSWLRQUHTXLUHVWKHXVH
RIWKH02',QWHUIDFH
 <RXPXVWVHOHFWWKHP$PLQDQGP$PD[6HW3RLQWYDOXHVLQWKHIROORZLQJVFUHHQV
 &RQQHFWWKH02',QWHUIDFHWRWKH%&3:56FRQQHFWLRQXVLQJWKHSKRQHFDEOHSURYLGHGZLWKWKH02'LQWHUIDFH
',63/$<81,7
º)º& 'HIDXOWºF
Hold Button: MENU/<System Startup>/..../Display Unit
 7KH%&3:FDQFRQWUROERLOHUVLQK\GURQLFHQYLURQPHQWZKHUHWKHWHPSHUDWXUHLV
the critical factor. It allows the user to display temperature information and settings in
either ºF (Fahrenheit) or ºC (Celsius). Select the display unit that is best suited for your
application.
---- DISPLAY UNIT ---
F
C
BACK SAVE
6(77,1*7+(0$$1'0$6(732,176$9$,/$%/(,10$(0621/<
P$IURP)&WR)& 'HIDXOW)&
P$IURP)&WR)& 'HIDXOW)&
Hold Button: MENU/<System Startup>/..../EMS 4mA Set Point/EMS 20mA Set Point
 ,I(06P$LVVHOHFWHGIURPWKH&RQWURO0RGHPHQXDVWKHWHPSHUDWXUHVHWSRLQW
VRXUFHWKHXVHUPXVWSXUFKDVHD:HLO0F/DLQ02',QWHUIDFHWR
accept the 4-20mA signal and transmit it to the BCP-8W.
EMS 4mA SET POINT
100 F
[ ]
BACK SAVE
 ,QDGGLWLRQWKHXVHUZLOOQHHGWRVHWWKHWHPSHUDWXUHUDQJHSDUDPHWHUV)LUVWVHWWKHP$
temperature set point, then the 20mA temperature set point.
 7RVKXWGRZQWKHFRQWUROXVLQJWKH(06VLJQDOVHQGDVLJQDOWKDWLVDERYHRUEHORZWKH
2-22mA range. The display will show the message "Shutdown by EMS" and all
VWDJHVZLOOGHHQHUJL]H+RZHYHUWKH6\VWHP&RPE$LUDQGERLOHU3XPSVDQG9DOYHV
ZLOOFRQWLQXHIRUWKH5XQ2QGHOD\SHULRGDQGWKHQGHHQHUJL]H
EMS 20mA SET POINT
170 F
[ ]
BACK SAVE
$/(57
$JRRGSUDFWLFHDIWHUSHUIRUPLQJDQ\6WDUWXSPHQXPRGL¿FDWLRQVLVWR
check all operating settings and adjustments to match the new settings.
background
18
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
'+:3,3,1*
3DUDOOHO3ULPDU\6HFRQGDU\ 'HIDXOW3DUDOOHO
Hold Button: MENU/<System Startup>/..../DHW Piping
 :KHQ3DUDOOHOLVVHOHFWHGWKH%&3:ZLOORIIHUD'+:3ULRULW\7LPHU7KH'+:
priority will only take place during heating periods. See the DHW Priority Timer on
page 28.
---- DHW PIPING ---
Parallel
Primary/Secondary
BACK SAVE
 7KHSULRULW\ZLOODOORZWKH'+:3XPSUHOD\WRHQHUJL]HZKLOHGHHQHUJL]LQJWKH6\VWHPUHOD\ZKHQWKHUHLVD'+:FDOOGXULQJ
KHDWLQJ+RZHYHUGXULQJ6XPPHURQO\WKH'+:3XPSUHOD\ZLOOHQHUJL]HRQD'+:FDOO
 6HOHFWLQJWKH3ULPDU\6HFRQGDU\RSWLRQZLOOHQHUJL]HWKH6\VWHPUHOD\ZLWKWKH'+:3XPSUHOD\ZKHQHYHUWKHUHLVDFDOOIRU
DHW even during the Summer or when outdoor temperature is above the Outdoor Cutoff. No priority will be available.
$/(57
A DHW call can be initiated by either a dry contact or using a Weil McLain Sensor (389-900-230)
for immersion in a 3/8ID well (592-300-023). The use of a sensor will allow the adjustment of the
DHW Set Point and DHW Differential.
'+:3803287387
1R<HV 'HIDXOW<HV
Hold Button: MENU/<System Startup>/..../DHW Pump Output
 7KH%&3:FDQFRQWUROWKHRSHUDWLRQRIWKH'+:3XPS7KLVRSWLRQDOORZVWKHXVHU
to select if the BCP-8W should be controlling the DHW Pump or not.
--DHW PUMP OUTPUT--
No
Yes
BACK SAVE
&20%867,21$,5'$03(5287387
1R<HV 'HIDXOW<HV
Hold Button: MENU/<System Startup>/..../Comb. Air Output
 7KH%&3:FDQFRQWUROWKHRSHUDWLRQRIWKH&RPEXVWLRQ$LU'DPSHU7KLVRSWLRQ
allows the user to select if the BCP-8W should be controlling the Combustion Air
Damper or not.
- COMB. AIR OUTPUT-
No
Yes
BACK SAVE
 ,I<HVLVVHOHFWHGWKH%&3:ZLOOHQHUJL]HWKH&RPE$LUUHOD\ZKHQHYHUWKHUHLVDFDOOIRUDERLOHUDQGZLOOXVHWKHPROVE
LQSXWWRFKHFNRQWKHVWDWXVRIWKH&RPEXVWLRQ$LU'DPSHU:KHQWKHODVWVWDJHLVGHHQHUJL]HGWKH&RPE$LUUHOD\ZLOO
UHPDLQHQHUJL]HGIRUWKH5XQ2QSHULRGDQGWKHQGHHQHUJL]H
 On a prove failure situation, the message "Wait for Comb. Prove". No boiler stages will be active until the Prove
input is Shorted.
 ,I3URYHIDLOVDIWHUWKHERLOHUVWDJHVZKHUHHQHUJL]HGWKHVWDJHVZLOOGHHQHUJL]HDQGWKHPHVVDJHComb. Prove
FailureZLOOGLVSOD\XQWLOWKHVLWXDWLRQLVUHFWL¿HG
 ,I1RLVVHOHFWHGWKHPROVE input will be used to check System status instead of the Combustion Air Damper.
(;7(51$/,138702'(
6KXWGRZQ7VWDW6HWEDFN 'HIDXOW7VWDW
Hold Button: MENU/<System Startup>/..../External Input
 7KH6KXWGRZQIXQFWLRQDOORZVWKH%&3:WRUHFHLYHDUHPRWH6KXWGRZQVLJQDOWR
WHUPLQDOVDQGWRWXUQRIIDOOUHOD\VLQFOXGLQJDOOERLOHUVVWDJHV
 :KHQ6KXWGRZQLVVHOHFWHG'+:FDOOVZLOOEHLJQRUHGXQOHVVWKHFRQWUROLVRXWRI
Shutdown.
-- EXTERNAL INPUT -
Shutdown
Tstat
Setback
BACK SAVE
 7KH7VWDWRSWLRQJLYHVWHUPLQDOV35 and 36 the capability of functioning as a heat-call. That is, when terminals 35 and 36 are
shorted, the BCP-8W will sequence the stages. However, when they are opened, all stages will turn off. Thus, do not remove
the factory installed jumper unless it was replaced with a Tstat signal.
 6HWEDFNLVXVHGWRORZHUWKHVHWSRLQWZKHQOHVVORDGLVUHTXLUHGGXULQJQLJKWVDQGZHHNHQGV
 )RUVHWEDFNRSHUDWLRQWKH%&3:FDQHLWKHUXWLOL]HLWVEXLOWLQQLJKWVFKHGXOHDYDLODEOHZKHQ6KXWGRZQRU7VWDWLVVHOHFWHGDV
the External Input, or an external dry contact signal to switch to setback by selecting Setback from this menu.
background
19
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
%851(57<3(
2Q2II6WDJH6WDJH6WDJH 'HIDXOW2Q2II
Hold Button: MENU/<System Startup>/..../Burner Type
 7KH%&3:FDQVHTXHQFHIURPDVLQJOHVWDJHDQGXSWRIRXUVWDJHVSHUERLOHU6HOHFW
the option based on your boiler number of stages.
--- BURNER TYPE ----
On/Off
2-Stage
3-Stage
4-Stage
BACK SAVE
%2,/(5287387
1RQH3XPS9DOYH 'HIDXOW1RQH
Hold Button: MENU/<System Startup>/..../Boiler Output
 :KHQ1RQHLVVHOHFWHGWKH%&3:ZLOOVHTXHQFHPXOWLSOHERLOHUVZLWKRXWDQ\
additional boiler pumps or valves.
 7KH3XPSRSWLRQDOORZVWKH%&3:WRFRQWUROWKHERLOHUVWDJHVLQDGGLWLRQWRWKHERLOHU
pumps. The pump stage will run for the Run-On delay after the lower stage of that boiler
KDVGHHQHUJL]HG
-- BOILER OUTPUT --
None
Pump
Valve
BACK SAVE
 7KH9DOYHRSWLRQIXQFWLRQVVLPLODUWRWKHSXPSRSWLRQH[FHSWWKDWZKHQDOOVWDJHVDUHRIIDQGDIWHUWKH5XQ2QGHOD\KDV
HODSVHGWKH/HDGERLOHUVYDOYHUHOD\ZLOOUHPDLQHQHUJL]HGWRDOORZIRUÀRZDFURVVWKHV\VWHP7KHOHDGERLOHUVYDOYHZLOO
UHPDLQHQHUJL]HGXQWLOWKHRXWGRRUWHPSHUDWXUHULVHVDERYHWKH2XWGRRU&XWRIIRUZKHQWKH6KXWGRZQRU6XPPHULVDFWLYDWHG
727$/%2,/(56
IURPWR 'HIDXOWYDULHVEDVHGRQ%XUQHU7\SHDQG%RLOHU2XWSXW
Hold Button: MENU/<System Startup>/..../Boiler Output
 7KLVRSWLRQLQFRPELQDWLRQZLWK%XUQHU7\SHDQG%RLOHU2XWSXW6WDUWXSRSWLRQVZLOO
determine the total number of outputs the BCP-8W will need to control.
 ,IWKHWRWDOQXPEHURIVWDJHVVHOHFWHGLQFOXGLQJERLOHUSXPSVRUYDOYHVLVPRUHWKDQWKH
control and extension stages, the additional boilers containing these stages will have CE
DVWKHLUVWDWXVDQGZLOOVHL]HWRRSHUDWH
-- TOTAL BOILERS --
8
[ ]
BACK SAVE
67$*,1*
0XOWLSOH2XWSXWV6LQJOH2XWSXW 'HIDXOW0XOWLSOH2XWSXWV
Hold Button: MENU/<System Startup>/..../Staging
 0RVWERLOHUVZLOOUHTXLUHWKDWWKHKLJKHURXWSXWVWDJHVEHHQHUJL]HGDIWHUWKHORZHURXWSXW
stages. These boilers will need to select the Multiple Output option. That means, both
/RZDQG+LJK2XWSXWVWDJHVPXVWEHHQHUJL]HGWRDFKLHYHWKHERLOHUVPD[LPXPRXWSXW
 6RPHHTXLSPHQWUHTXLUHWKDWZKHQWKHKLJKHURXWSXWVWDJHVDUHUHTXLUHGWKHORZHUVWDJHV
PXVWGHHQHUJL]H7RRSHUDWHWKHVHHTXLSPHQWWKHXVHUPXVWVHOHFWWKH6LQJOH2XWSXW
option.
------ STAGING ------
Multiple Outputs
Single Output
BACK SAVE
6(48(1&(
/R+L/R+L/R/R+L+L 'HIDXOW/R+L/R+L
Hold Button: MENU/<System Startup>/..../Sequencing
 6RPHERLOHUVUXQPRUHHI¿FLHQWZKHQWKHORZHUVWDJHVDUHHQHUJL]HGDORQHWKDQZLWKWKH
KLJKHUVWDJHV7KHVHW\SHVRIERLOHUVVKRXOGVHOHFW/R/R+L+L7KHQWKH%&3:ZLOO
sequence the lower stages of all Automatic boilers before sequencing the higher stages.
------ SEQUENCE -------
Lo/Hi/Lo/Hi
Lo/Lo/Hi/Hi
BACK SAVE
 )RUWKHUHVWRIWKHERLOHUW\SHVWKH/R+L/R+LVKRXOGDOORZWKHVWDJLQJRIWKHORZHUVWDJHRIWKHOHDGERLOHUIROORZHGE\WKH
KLJKHUVWDJHRIWKHVDPHERLOHU7KHQZKHQPRUHVWDJHVDUHQHHGHGLWZLOO¿UHWKHORZHUVWDJHRIWKHODJERLOHUIROORZHGE\WKH
higher stage of the lag boiler.
&21752//2*,&
3,'2662YHU6L]HG6\VWHP 'HIDXOW3,'
Hold Button: MENU/<System Startup>/..../Sequencing
 7KH3,'RSWLRQDOORZVWKH%&3:WRVHTXHQFHVWDJHVEDVHGRQWKH5HDFWLRQ7LPH
and the Boiler Minimum Run Time. The PID relies on the rate of change in the System
Temperature. The PID logarithmic calculations foresee changes and sequence stages
EDVHGRQWKRVHFKDQJHV,WLVWKHPRVWHI¿FLHQWRSHUDWLRQIRUPRVWKHDWLQJDSSOLFDWLRQV
--- CONTROL LOGIC---
PID
OSS
BACK SAVE
background
20
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
 7KH2YHUVL]HRSWLRQVHTXHQFHVWDJHVEDVHGRQKRZPDQ\7KURWWOLQJUDQJHVGLIIHUHQWLDOVLVWKHV\VWHPWHPSHUDWXUHDZD\IURP
the Target Temperature. At one Throttling range below the Set Point, only one stage will be on. For each additional Throttling
range below the Set Point, an additional stage will be activated. The last stage on will be allowed to exceed the Set Point by one
Throttling range before turning off that stage. This helps to prevent the last stage from short cycling.
:KHQ3,'LV6HOHFWHGWKHIROORZLQJDUHWKHVHWWLQJVWKDWGLUHFWO\DIIHFWVWKLVPRGHVRSHUDWLRQ
 5HDFWLRQ7LPHSJ24 6(/(&7Settings/System Settings/Stage Settings/Reaction Time
 3XUJH'HOD\(pg 24) 6(/(&7Settings/System Settings/Stage Settings/Purge Delay
 0LQLPXP5XQ7LPH(pg 24) 6(/(&7Settings/System Settings/Stage Settings/Min Runtime
 6WDQGE\'HOD\(pg 25) 6(/(&7Settings/System Settings/Stage Settings/Standby Delay
 /DVW6WDJH+ROG(pg 25) 6(/(&7Settings/System Settings/Stage Settings/Last Stage Hold
:KHQ2YHUVL]H266LV6HOHFWHGWKHIROORZLQJDUHWKHVHWWLQJVWKDWGLUHFWO\DIIHFWVWKLVPRGHVRSHUDWLRQ
 7KURWWOH(pg 25)6(/(&7Settings/System Settings/Stage Settings/Throttle
6(1625)$8/7
6WDJHV2Q6WDJHV2II 'HIDXOW6WDJHV2Q
Hold Button: MENU/<System Startup>/..../Sensor Fault
 The Sensor Fault will determine the operating status of all output stages set to Auto or
Standby when a sensor reads Short or Open.
--- SENSOR FAULT ---
Stages On
Stages Off
BACK SAVE
 7KH6KXWGRZQRU7VWDWDFWLYDWLRQZLOOWDNHSUHFHGHQFHRYHUWKH6HQVRU)DXOWVWDWXV7KDWPHDQVLI6WDJHV2QLVVHOHFWHGDQG
the Shutdown was active, all stages will be Off on a sensor fault.
5(6(702'(
 :KHQ6WDJHV2QLVVHOHFWHGWKH%&3:ZLOOWXUQDOOERLOHUVWDJHV2QZKHQWKH6\VWHPUHDGVShort or Open and the
outdoor is below the Outdoor Cutoff. When the Outdoor reads Short or Open, the BCP-8W will change the Target to the
Maximum Target.
 :KHQ6WDJHV2IILVVHOHFWHGWKH%&3:ZLOOWXUQDOOVWDJHV2IIZKHQWKH6\VWHPUHDGVShort or Open. However, when
the Outdoor reads Short or Open, the BCP-8W will change the Target to the Minimum Target.
6(732,1702'(
 :KHQ6WDJHV2QLVVHOHFWHGWKH%&3:ZLOOWXUQDOOVWDJHV2QZKHQWKH6\VWHPVHQVRUUHDGVShort or Open.
 :KHQ6WDJHV2IILVVHOHFWHGWKH%&3:ZLOOWXUQDOOVWDJHV2IIZKHQWKH6\VWHPVHQVRUUHDGV Short or Open.
 7KH2XWGRRU6HQVRU6KRUWRU2SHQVWDWXVZLOOQRWDIIHFWWKHFRQWURORSHUDWLRQLQ6HW3RLQWPRGH
6(77,1*7+(&21752/72)$&725<'()$8/76
To Reset the BCP-8W control to its original factory defaults, power down the control. Hold
down the two right most buttons while powering the control back up until the Total
Clear Started screen appears. The Display will direct you to the Startup menu to
program the control after the defaults are loaded.
TOTAL CLEAR STARTED
Release buttons
and
Please Wait
127(:KHQUHVHWWLQJWKHFRQWUROWRRULJLQDOIDFWRU\GHIDXOWVDOOFRQWUROVHWWLQJVZLOOEHRYHUZULWWHQDQGZLOOQRORQJHUH[LVW
$/(57
Do not turn off power to control until all Startup settings have been made. Otherwise, the next
SRZHUXSZLOOEHVHWWRPDQ\6WDUWXSIDFWRU\VHWWLQJVWKDWPLJKWQRW¿W\RXUDSSOLFDWLRQ
23(5$7,1*6(77,1*6
352*5$0&+$1*(6(77,1*6
To be able to change the BCP-8W settings the Program/Run Switch must be set to Program.
The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring
Cover can be securely closed using a padlock.
PROGRAM RUN
background
21
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
$/(57
DO NOT turn power off to the
BCP-8W when in off-season.
If you do so, the battery will
run down and have to be
replaced. Instead, switch
Season to Summer.
---- SEASON ---
Winter
Summer
BACK SAVE
6($621
:LQWHU6XPPHU 'HIDXOW:LQWHU
Button: MENU/Season
 7KH%&3:ZLOOWXUQDOOERLOHUUHOD\VRIIZKHQLWLVLQ6XPPHUVHWWLQJThe Message
'LVSOD\/LQHZLOOUHDGSummer to show status. However, a DHW call will bring the
boilers back on if needed. When in Winter, the BCP-8W will activate the System relay
whenever the Outdoor temperature falls to or below the Outdoor Cutoff setting. In
addition, it will begin heating whenever the System temperature falls below the Set Point
7HPSHUDWXUH7KH0HVVDJH'LVSOD\/LQHZLOOQRWGLVSOD\DQ\VHDVRQLQIRUPDWLRQ
 :KHQWKHVHDVRQLVRYHULWLVDJRRGSUDFWLFHWRVZLWFKWKH%&3:6HDVRQVHWWLQJ7KLV
will allow DHW calls to operate the boilers when needed.
5(6(75$7,2
&XVWRP2'6\VWR2'6\V'HIDXOW2'6\V
Hold Button: MENU/<Outdoor Reset>/Reset Ratio ,Q2XWGRRU5HVHW2QO\
 7KH5HVHW5DWLRGHWHUPLQHVKRZWKHV\VWHP7DUJHWWHPSHUDWXUHZLOOYDU\EDVHGRQWKH
outdoor temperature. With any of the ratios, the colder it becomes outside, the hotter the
temperature of the system water. (See Understanding Operation Concept on page 5)
 :LWKD2'6<6UDWLRWKH6\VWHPZDWHUWHPSHUDWXUH6<6ZLOOLQFUHDVH
UDSLGO\DVWKHRXWVLGHWHPSHUDWXUHIDOOVKLWWLQJWKH0D[LPXPRI)DW)RXWVLGH
WHPSHUDWXUH:LWKD2'6<6UDWLRWKH6\VWHPWHPSHUDWXUH6<6ZLOO
LQFUHDVHVORZO\DVWKHRXWVLGHWHPSHUDWXUHIDOOV(YHQDW)WKHV\VWHPZDWHUZLOO
only be 125°F, and at 22°F outside, the system water will be 112°F. Such a low Reset
5DWLRPLJKWEHXVHGZLWKUDGLDQWÀRRUKHDWLQJDSSOLFDWLRQV
 :LWKPRVWEDVHERDUGKHDWLQJDSSOLFDWLRQVD2'6<6) setting is a good
SODFHWRVWDUW:LWKD2'6<6) ratio, for every degree the outside
temperature falls, the system water temperature is increased one degree.
---- RESET RATIO ---
Custom
1(8.00
OD:1.00 SYS)
2(4.00
OD:1.00 SYS)
3(3.00
OD:1.00 SYS)
4(2.00
OD:1.00 SYS)
5(1.50
OD:1.00 SYS)
6(1.25
OD:1.00 SYS)
7(1.00 OD:1.00 SYS)
8(1.00
OD:1.25 SYS)
9(1.00
OD:1.50 SYS)
10(1.00
OD:2.00 SYS)
11(1.00
OD:3.00 SYS)
12(1.00
OD:4.00 SYS)
BACK SAVE
 ,IUHTXLUHG$GMXVWWKH5(6(75$7,2LQFROGZHDWKHU If the ambient building
temperature are cold in cold weather, move the ratio to a higher selection. That is, if
2'6<6ZDVLQLWLDOO\VHOHFWHGFKDQJHWKHVHOHFWLRQWR2'
(6<6). If the building temperature are too warm in cold weather, move the ratio to a
ORZHUVHOHFWLRQ7KDWLVLI2'6<6) was initially selected, change it to 1.25
2'6<6).
 $IWHUVHOHFWLQJWKH5HVHW5DWLRSUHVVLQJWKHSAVE button will switch to the Outdoor
Cutoff setting option.
Outdoor Temperature
Water Temperatur e
70 405060
130
120
110
100
1:4 1:1
4:1
Colder
Warmer
&86720,=('5(6(75$7,2
Hold Button: MENU/<Outdoor Reset>/Reset Ratio/Custom
 )RUVLWXDWLRQVZKHUHWKHDYDLODEOHUHVHWUDWLRVGRQRWSURYLGHWKHSHUIHFWEXLOGLQJKHDWORVVHTXLOLEULXPWKHFXVWRPL]HGRSWLRQ
can be used by selecting Custom from the Reset Ratio menu option.
 ,WSURYLGHVWKHXVHUZLWKWKHFDSDELOLW\RIDVVLJQLQJWZRSRLQWVRQWKHUHVHWUDWLRGLDJUDPDQGXVHWKHOLQHWKDWFRQQHFWVWKRVH
WZRSRLQWVDVWKHFXVWRPL]HGUHVHWUDWLRFXUYH(DFKRIWKHWZRSRLQWVZLOOQHHGDVSHFL¿F6\VWHPDQG2XWGRRU7HPSHUDWXUHWR
identify it on the diagram.
 7R6HWWKH¿UVWSRLQWVSHFLI\6\V7HPSDQG2'7HPS7KHQVSHFLI\6\V7HPSDQG2'7HPSWRVHWWKHVHFRQGSRLQW
on the curve. The two points can be anywhere on the line, not necessarily at the ends.
 7KHFKDUWVKRZVDQH[DPSOHRIDFXVWRPL]HGFXUYH2'6<6WKDWGRHVQRWH[LVWLQWKHVWDQGDUGFXUYHRSWLRQV,IWKH
RXWGRRUWHPSHUDWXUHUHDFKHV)WKHV\VWHPWDUJHWZLOOEH)
 5HPHPEHUWKDWWKH2IIVHW0LQ7DUJHWDQG0D[7DUJHWDSSO\WRDOOUHVHWUDWLRVLQFOXGLQJWKHFXVWRPL]HGUHVHWUDWLRRQHV
background
22
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
-- SET SYS TEMP.1 -
120 F
[ ]
BACK SAVE
-- SET SYS TEMP.2 -
170 F
[ ]
BACK SAVE
-- AT OD TEMP.1 ---
60 F
[ ]
BACK SAVE
-- AT OD TEMP.2 ---
0 F
[ ]
BACK SAVE
Outdoor Temperature (in °F)
70 60 50 40 2030 0 -1010 -2
0
120
140
130
150
160
170
180
100
110
Water Temperature (in °F)
Custom Reset Ratio
Point1: System=120°F
Oudoor=60°F
Point2: System=170°F
Oudoor=0°F
Point1
Point2
Customized Reset Ratio
Max Target
Min Target
6(732,17127$'-867$%/(,1(0602'(
$GMXVWDEOHIURPº)º&WRº)ºC 'HIDXOWº)º&
Button: MENU/Set Point ,Q6HW3RLQWRU(06P$
 7KH6HWSRLQWLVWKHWHPSHUDWXUHYDOXHWKH%&3:ZLOOXVHWRFRQWUROWKHV\VWHP
 7KH%&3:ZLOODGGVXEWUDFWRUKROGWKHVWDJHVRIWKHKHDWLQJERLOHUVWRPDLQWDLQWKH
system temperature around the Set point.
----- SET POINT -----
70
F
[ ]
BACK SAVE
 7KHV\VWHPFDQEHH[SHFWHGWRÀXFWXDWHDURXQGWKHVHWSRLQW7KHDPRXQWRIÀXFWXDWLRQGHSHQGVRQWKH6\VWHP6HWWLQJVDQG
Stage Settings.
 ,IDQ2XWGRRU6HQVRUZDVFRQQHFWHGSUHVVLQJWKHSAVE button will continue to the Outdoor Cutoff setting option.
 ,IWKH(060RGHZDV(QDEOHGWKH6HW3RLQWZLOOEHVHWE\WKH(06%06V\VWHPDQGZLOOEHDYDLODEOHDVDUHDGRQO\
 7KHUDQJHRI6HW3RLQWLQWKH(06LVVHWLQWKH6WDUWXSPHQXDWP$DQGP$
 $Q\UHDGLQJEHORZWKHP$RUDERYHP$ZLOOLQGLFDWHDShutdown by EMSPHVVDJHRQWKH0HVVDJH/LQH
287'225&872))7(03(5$785(
$GMXVWDEOH2IIIURPº)º&WRº)º&2Q 'HIDXOW)&
Hold Button: MENU/Set Point/Outdoor Cutoff LQ6HW3RLQW
Hold Button: MENU/<Outdoor Reset>/Outdoor Cutoff LQ5HVHW
 ,Q2XWGRRU5HVHWPRGH2XWGRRU&XWRIIZLOODOZD\VH[LVW+RZHYHULQ6HW3RLQWPRGH
if the outdoor sensor is installed, the Outdoor Cutoff screen will automatically appear
after the temperature Set Point has been selected.
-- OUTDOOR CUTOFF --
70 F
[ ]
BACK SAVE
 :KHQWKHRXWGRRUWHPSHUDWXUHIDOOVWRWKHDGMXVWDEOH2XWGRRU&XWRIIWHPSHUDWXUHWKH%&3:ZLOOFRQWURODQGVHTXHQFHWKH
boiler stages to hold the calculated temperature.
 :KHQWKHRXWGRRUWHPSHUDWXUHULVHVWRWKH2XWGRRU&XWRIISOXVD)GLIIHUHQWLDOWKH%&3:ZLOOWXUQDOOERLOHUVRII7KH
6\VWHP&RPEXVWLRQ$LU'DPSHUDQGDQ\RWKHU3XPSRUYDOYHUHOD\VWKDWZHUHHQHUJL]HGZLOOUHPDLQHQHUJL]HGIRUWKH5XQ2Q
delayDQGWKHQGHHQHUJL]H.
 ,QDGGLWLRQWKH2XWGRRU&XWRIIFDQEHVHWWR21RU2)),QWKH21RSWLRQWKH6\VWHP5HOD\ZLOOUXQUHJDUGOHVVRIWKH2XWGRRU
temperature and the burner stages will be active to hold the target water temperature.
 ,QWKH2))SRVLWLRQWKHV\VWHPSXPSZLOODOZD\VEHRIIDQGDOOVWDJHVZLOOEHRIIDVZHOO
7$5*(72))6(7
$GMXVWDEOHIURPº)º&WRº)º& 'HIDXOWº)º&
Hold Button: MENU/<Outdoor Reset>/Offset LQ2XWGRRU5HVHWRQO\
 7KH2IIVHWVHWWLQJPRYHVWKH5HVHW5DWLRFXUYHYHUWLFDOO\7KLVPHDQVWKDWUHJDUGOHVV
of the Outdoor temperature, or the Reset Ratio that has been selected, when the Offset
setting is changed, that change is directly added to or subtracted from the calculated
WHPSHUDWXUH)RUH[DPSOHLIWKH6HW3RLQWWHPSHUDWXUHZDV)DQGWKH2IIVHWZDV
changed from 0° to 10° (an increase of 10°), the Set Point would increase to 140°F.
-- TARGET OFFSET ---
+0 F
[ ]
BACK SAVE
background
23
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
 7KH2IIVHWVHWWLQJGRHVQRWFKDQJHWKHUDWLRVHOHFWLRQ)RULQVWDQFHZLWK2'
6<65HVHW5DWLRWKH6\VWHPZDWHUWHPSHUDWXUHZLOODOZD\VLQFUHDVHRQHGHJUHHIRU
every 1.5 degree change in the Outdoor temperature. What the Offset does is add or
subtract a constant temperature value. (See Understanding Operation Concept on page 5)
 7KH0LQLPXPDQG0D[LPXP7DUJHWZLOOWDNHSUHFHGHQFHRYHUWKH2IIVHW7KDWLVLIWKH
0D[7DUJHWZDVVHWWR)DQGWKH2IIVHWZDVVHWWR),IWKHVHWSRLQWZDV)
the new calculated set point based with the Offset should be 175°F. However, it will not
exceed 170°F due to the Maximum Target setting.
 ,IUHTXLUHG$GMXVWWKH:DWHU2IIVHWLQPLOGZHDWKHU. If the ambient building
temperatures are too warm in the mild weather, decrease the Target Offset. If the
ambient building temperatures are too cold in the mild weather, increase the Target
Offset. The rule of thumb for baseboard radiation is to change the Offset 4°F for every
1°F you wish to change the building temperatures. In radiant heat applications, change
the Offset 1°F or 2°F for every 1°F you wish to change the building temperature.
Outdoor Temperature (in °F)
70 60 50 40 2030 0 -1010 -2
0
120
140
130
150
160
170
180
100
110
Water Temperature (in °F)
Tar
g
et Offset
Offset=10°F
Reset Ratio=1.5 : 1.0
Reset Ratio
Max Target
Min Target
Reset Ratio + 10F Offset
Min Target=120°F
Max Target=170°F
0,1,0807$5*(7
$GMXVWDEOHIURPº)º&WRº)º& 'HIDXOWº)º&
Hold Button: MENU/<Outdoor Reset>/Min. Target LQ2XWGRRU5HVHWRQO\
 7KH0LQLPXP7DUJHWPXVWEHVHWWRWKHERLOHUPDQXIDFWXUHUVVSHFL¿FDWLRQ7KH%&3
8W will calculate the Set Point based on the Outdoor temperature, the Reset Ratio, and
the Offset value. The BCP-8W will control all boilers to hold either the Set Point
---- MIN TARGET ----
140 F
[ ]
BACK SAVE
temperature, or the Minimum Target, whichever is higher.
 7KH0LQLPXP7DUJHWPXVWEHDWOHDVW)ORZHUWKDQWKH0D[LPXP7DUJHW6HHQH[WVHWWLQJ
0$;,0807$5*(7
$GMXVWDEOHIURPº)º&WRº)º& 'HIDXOWº)º&
Hold Button: MENU/<Outdoor Reset>/Max. Target LQ2XWGRRU5HVHWRQO\
 7KLVLVWKHKLJKHVW7DUJHWWHPSHUDWXUHWKH%&3:ZLOOFDOFXODWHIRUWKHKHDWLQJV\VWHP
 :KHQXVLQJLQÀRRUUDGLDQWV\VWHPLWVKRXOGEHVHWDFFRUGLQJWRWKHWXELQJRUÀRRU
PDQXIDFWXUHUVVSHFL¿FDWLRQ
 7KH0D[LPXP7DUJHWPXVWEHDWOHDVW)KLJKHUWKDQWKH0LQLPXP7DUJHW6HH
previous setting)..
---- MAX TARGET ----
200 F
[ ]
BACK SAVE
%2,/(50,1,0805(7851
When a return sensor is connected to the BCP-8W, it will monitor and control the boiler return. It does that by monitoring the Target
WHPSHUDWXUH7*76\VWHPWHPSHUDWXUH6<60LQLPXP5HWXUQDQGDFWXDOUHWXUQ571:KHQWKH%&3:IRUHVHHVWKDWDORZ
return will occur, it will increase the Target automatically as an effort to increase the return temperature. See Return Sensor Wiring on
page 10.
0,1,0805(7851
$GMXVWDEOH2IIIURPº)º&WRº)º& 'HIDXOW2II
Hold Button: MENU/Min. Return
 7KH0LQLPXP5HWXUQLVWKHFULWLFDOWHPSHUDWXUHDWZKLFKWKHUHWXUQVKRXOGEHDERYH
Normally, this setting is provided by the boiler manufacturer or the system engineer.
---- MIN RETURN ----
OFF
[ ]
BACK SAVE
 7KH%&3:ZLOOXVHWKDWYDOXHDVDJXLGH,WZLOOVWDUWWRDGGDGGLWLRQDOVWDJHVLILWIRUHVHHVWKDWWKH571WHPSHUDWXUHZLOO
drop below the Min. Return. During that period, it will display "Hold Return at 120 F" in the Display Message
/LQHWRLQGLFDWHWKDWWKH%&3:LVVHTXHQFLQJERLOHUVWRSURWHFWWKHUHWXUQIURPGURSSLQJEHORZWKH0LQLPXP5HWXUQ
 0RVWFRQGHQVLQJERLOHUVZLOOUXQPRUHHI¿FLHQWZLWK&RROHUUHWXUQWHPSHUDWXUHV,QWKLVFDVHVHOHFWWKH2IIRSWLRQRQWKH
Minimum Return to allow the monitoring of the return on the display without sequencing the boiler stages.
background
24
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
5(7851/$*
$GMXVWDEOHIURPWRPLQXWHV 'HIDXOWPLQXWHV
Hold Button: MENU/Min. Return/Return Lag
 ,WLVWKHWLPHLWWDNHVIRUWKHV\VWHPUHWXUQWRFKDQJHDIWHUVHTXHQFLQJWKHVWDJHV
 ,QLWLDOO\DGMXVWWKLVYDOXHWRHTXDOWKH5HDFWLRQ7LPH7KHQLQH[WUHPHFROGZHDWKHU
monitor the return making sure it is about 10°F above the Minimum Return setting and
adjust it if needed.
---- RETURN LAG ----
2min
[ ]
BACK SAVE
6<67(06(77,1*6
Hold Button: MENU/<System Settings>
7KH6\VWHP6HWWLQJVPHQXSURYLGHVDFFHVVWRDGMXVWLQJDQG¿QHWXQLQJWKHV\VWHPIRUHQKDQFHG
comfort and better fuel savings. The BCP-8W behaves differently based on the selected Control
Modes (see Startup Settings 17).
- SYSTEM SETTINGS -
<Stage Settings>
<Setback Schedule>
<DHW Settings>
Setback 0
F
Run-On 2min
Pump Exercise Off
BACK SELECT
PROGRAM RUN
352*5$0&+$1*(6(77,1*6
To be able to change the BCP-8W settings the Program/Run Switch must be set to Program.
The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring
Cover can be securely closed using a padlock.
67$*(6(77,1*6
Button: MENU/<System Settings>/<Stage Settings>
-- STAGE SETTINGS --
Reaction Time 1min
Purge Delay 0.0min
Min Runtime 2min
Standby Delay 10min
Last Stage Hold5 F
Throttle 2 F
<Lead Settings>
BACK SELECT
-- REACTION TIME --
2min
[ ]
BACK SAVE
5($&7,217,0(
$GMXVWDEOHIURPWRPLQXWHV 'HIDXOWPLQXWHV
Hold Button: MENU/<System Settings>/<Stage Settings>/Reaction TimeLQ3,'/RJLFRQO\
 ,WLVWKHDPRXQWRIWLPHLWWDNHVDVLQJOHVWDJHWRDIIHFWWKHV\VWHP
 $IWHUWKH%&3:WXUQVRQDVWDJHWU\LQJWRPHHWDVHWSRLQWLWZLOOQRWWXUQRQDQRWKHU
stage until the Reaction Time has elapsed.
 7RGHWHUPLQHWKHRSWLPXPWLPHLQDKHDWLQJV\VWHPVWDUWZLWKDKRWV\VWHP7XUQRQ
a single stage and calculate how long it takes until the system begins to respond to that
stage. That period should be set as the Reaction Time (See PID operation ).
385*('(/$<
$GMXVWDEOHIURPWRPLQXWHV 'HIDXOWPLQXWHV
Hold Button: MENU/<System Settings>/<Stage Settings>/Purge DelayLQ3,'/RJLFRQO\
 0RVWODUJHERLOHUVPXVWJRWKURXJKDSXUJHF\FOHEHIRUHWKH\DUHEURXJKWRQOLQH
 :KHQWKH%&3:DFWLYDWHVDERLOHUWKHORZHVWVWDJHRQDERLOHULWGRHVQRWVWDUWWR
calculate its output until the Purge Delay is over. This allows the boiler to fully come on
line and to begin producing output.
--- PURGE DELAY ----
1.0min
[ ]
BACK SAVE
 7KH3XUJH'HOD\KHOSVSUHYHQWVKRUWF\FOLQJRIDQHZO\DFWLYDWHGERLOHU2QFHWKHORZHVWERLOHUVWDJHLVDFWLYDWHGLW0867UXQ
through the entire Purge Delay period (See PID operation on page ).
 7KHPLQLPXP3XUJH'HOD\VHWWLQJ0867EHVHWWRWKHWLPHUHTXLUHGE\WKHERLOHUVPDQXIDFWXUHUVSHFL¿FDWLRQ
0,1,0805817,0(
$GMXVWDEOHIURPWRPLQXWHV 'HIDXOWPLQXWHV
Hold Button: MENU/<System Settings>/<Stage Settings>/Min RuntimeLQ3,'/RJLFRQO\
 7KLVLVWKHPLQLPXPDPRXQWRIWLPHDQ\VWDJHZLOOUXQ (See PID operation on page ).
 )RUWKHORZHVWVWDJHRIDERLOHUWKH0LQLPXP5XQWLPHVWDUWVDIWHUWKHSXUJHF\FOH
- MINIMUM RUNTIME -
1min
[ ]
BACK SAVE
 7KLVWLPHUGRHVQRWDSSO\WRWKHODVWVWDJHRQOLQH7KH/DVW6WDJH+ROGDSSOLHVLQWKDWFDVH
 ,QLWLDOO\VHWWKHMinimum Runtime to half the Reaction Time.
 ,I6\VWHPWHQGVWRRYHUVKRRWUHGXFHWKHMinimum Runtime. If boilers tend to short cycle, increase Minimum Runtime.
background
25
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
67$1'%<'(/$<
$GMXVWDEOHIURPWRPLQXWHV 'HIDXOWPLQXWHV
Hold Button: MENU/<System Settings>/<Stage Settings>/Standby DelayLQ3,'/RJLFRQO\
 7KH6WDQGE\'HOD\RQO\DSSOLHVWRERLOHUVLQ6WDQGE\0RGH6HH0RGHRQSDJH2.
 $6WDQGE\ERLOHUFDQRQO\EHDFWLYDWHGDIWHUDOOWKHERLOHUVLQ$XWR0RGHKDYHKDGDOO
their stages on running for the full Standby Time.
-- STANDBY DELAY --
10min
[
]
BACK SAVE
 6WDQGE\ERLOHUVDUHXVHGDVDEDFNXSLQH[WUHPHORDGFRQGLWLRQV$6WDQGE\ERLOHUFDQQHYHUEHD/HDGERLOHU
 7KHIXOO6WDQGE\'HOD\PXVWDOZD\VHODSVHUHJDUGOHVVRIZKDWKDSSHQVWRWKHV\VWHPWHPSHUDWXUH7KHUHIRUHVKRUWHU6WDQGE\
WLPHVZLOOUHVXOWLQVPRRWKHUVHWSRLQWRSHUDWLRQLQH[WUHPHFRQGLWLRQV/RQJHU6WDQGE\WLPHVPD\SUHYHQWD6WDQGE\ERLOHU
from starting if the other boilers can eventually meet the load or if the load decreases.
 :KHQVHWWLQJWKH6WDQGE\'HOD\UHPHPEHUWKDWLWZLOOEHDGGHGWRWKH5HDFWLRQ7LPHIRUWKH¿UVWVWDJHRQWKH¿UVWVWDQGE\
boiler. The following stages start time will rely on Pre-Purge and Reaction Time only.
/$6767$*(+2/'
$GMXVWDEOHIURP)º&ºWR)º&º 'HIDXOW)º&º
Hold Button: MENU/<System Settings>/<Stage Settings>/Lst Stg Hld LQ3,'/RJLFRQO\
 7KH/DVW6WDJH+ROGSUHYHQWVVKRUWF\FOLQJRIWKH/HDG6WDJHGXULQJORZORDGFRQGLWLRQV
ZKHUHWKHV\VWHPPLJKWKDYHDORDGWKDWLVVLJQL¿FDQWO\OHVVWKDQWKHRXWSXWRIRQHVWDJH
LAST STAGE HOLD
5 F
[ ]
BACK SAVE
:KHQWKH%&3:EULQJVRQWKH/HDG6WDJHWKH6HW3RLQWLVTXLFNO\H[FHHGHGDQGWKH/HDG6WDJHLVWXUQHGRII7RSURORQJ
WKHUXQWLPHGXULQJWKLVW\SHRIFRQGLWLRQXVHWKH/DVW6WDJH+ROGVHWWLQJ
 7KH%&3:ZLOODOORZWKHV\VWHPWHPSHUDWXUHWRH[FHHGWKH6HW3RLQWE\WKHQXPEHURIGHJUHHVVHOHFWHGEHIRUHWKH/HDG
Stage is turned off. (See PID operation ).
 )RUH[DPSOHZLWKD6HW3RLQWRI)DQGD/DVW6WDJH+ROGVHWWLQJRI)WKH/HDG6WDJHERLOHUZLOOUHPDLQRQXQWLOWKH6HW
Point reaches 170°F. During that period, the display will show "Hold Until 170F" then, the lead stage will turn off
7+5277/(5$1*(
$GMXVWDEOHIURP)º&ºWR)º&º 'HIDXOW)º&º
Hold Button: MENU/<System Settings>/<Stage Settings>/Throttle LQ266/RJLFRQO\
 7KH7KURWWOLQJ5DQJHVHWVDWHPSHUDWXUHEDQGDURXQGWKH6HW3RLQWWKDWFRQWUROVZKHQ
stages will be turned on or off.
-- THROTTLE RANGE --
2 F
[ ]
BACK SAVE
 )RUH[DPSOHLQWKH266&RQWURO0RGHQRVWDJHVZLOOEHDFWLYDWHGXQWLOWKHWHPSHUDWXUHIDOOVRQHIXOO7KURWWOLQJ5DQJHEHORZWKH
Set Point. A second stage will be activated when the temperature falls to two full Throttling Ranges below the Set Point, and so
on, with one extra stage being turned on for every throttling range below the Set Point the System temperature reaches.
 6WDJHVZLOOEHWXUQHGRIIDVWKHWHPSHUDWXUHULVHVWRZDUGWKH6HW3RLQWXVLQJRQHIXOOWKURWWOLQJUDQJHDVDGLIIHUHQWLDOEHWZHHQ
stages.
 7KHODVWVWDJHWREHWXUQHGRIIZLOOEHDOORZHGWRH[FHHGWKH6HW3RLQWE\DIXOOWKURWWOLQJUDQJHEHIRUHLWLVWXUQHGRII7KLVKHOSV
WRSUHYHQWWKHODVWVWDJHIURPVKRUWF\FOLQJZKHQWKHORDGLVORZRUZKHQWKHVWDJHLVRYHUVL]HG (See OSS operation ).
7KURWWOLQJ([DPSOH
6HW3RLQW °) 7KURWWOLQJ )° %RLOHU6WDJHV$%&DQG'
)DOOLQJ7HPSHUDWXUH 5LVLQJ7HPSHUDWXUH
7HPSHUDWXUH &DOFXODWLRQ 6WDJH7XUQHG2Q 6WDJHV2Q 6WDJH7XUQHG2II 6WDJHV2Q
185°F
180 + (1)THR
--- None A None
180°F 180 - (0)THR --- None --- A
175°F 180 - (1)THR A A B A
171 to 174°F --- --- A --- A,B
170°F 180 - (2)THR B A,B C A,B
166 to 169°F --- --- A,B --- A,B,C
165°F 180 - (3)THR C A,B,C D A,B,C
161 to 165°F --- --- A,B,C --- A,B,C,D
160°F 180 - (4)THR D A,B,C,D --- A,B,C,D
/($'6(77,1*6
Hold Button: MENU/<System Settings>/<Stage Settings>/<Lead Settings>
7KHOHDGPHQXLVWRKHOSLQVHOHFWLQJWKH/HDGERLOHUDQGWKHW\SHRIURWDWLRQDSSURSULDWHIRU
the system.
-- LEAD SETTINGS --
Lead Boiler AB
Rotate Mode Time
BACK SELECT
background
26
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
/($'%2,/(5
'HSHQGLQJRQWKHQXPEHURIVWDJHV 'HIDXOW7KH¿UVWVHWRIVWDJHV
Hold Button: MENU/<System Settings>/<Stage Settings>/<Lead Setting>/Rotate Mode
 7KH/HDG%RLOHUVORZHVWVWDJHZLOODOZD\VEHWKHILUVWVWDJHEURXJKWRQZKHQWKHUHLVD
call for output. As more output is needed, additional stages are added.
 7KH/HDG%RLOHULVDOZD\VVKRZQRQWKHPDLQGLVSOD\LQEUDFNHWV
 ,QD6WDJHV\VWHPVHH%XUQHU7\SHLQWKH6WDUWXSVHFWLRQRQSDJH19), the display will
show the WZR/HDG%RLOHUVWDJHVEUDFNHWHG$%!,QD6WDJHV\VWHPWKHGLVSOD\ZLOO
No Pump or Valve stages
-- LEAD BOILER --
AB
CD
EF
BACK SELECT
VKRZWKHWKUHH/HDG%RLOHUVWDJHVEUDFNHWHG$%&!DQGVRRQ
 ,IDSXPSRUDYDOYHLVVHOHFWHGDVWKH%RLOHU2XWSXWLQWKH6WDUWXSPHQXVHHSDJH19),
the pump or valve letter will be skipped from the number os stages. See example to the
ULJKW7KHPLVVLQJVWDJH&DQG)UHSUHVHQWWKH%RLOHU9DOYHRU3XPS
 7KH/HDG%RLOHUFDQEHURWDWHGEDVHGRQWKH5RWDWLRQ0RGHVHOHFWHG6HHQH[WVHWWLQJ
With Pump or Valve stages
-- LEAD BOILER --
AB
DE
BACK SELECT
527$7(02'(
$GMXVWDEOH7LPHIURPKUWRKUV0DQXDO)2)2 'HIDXOW7LPH+RXUV
Hold Button: MENU/<System Settings>/<Stage Settings>/<Lead Setting>/Rotate Mode
 7KH/HDG%RLOHULVWKH¿UVWERLOHUEURXJKWRQZKHQRXWSXWLVUHTXLUHG
 7KH/HDG%RLOHUFDQEHURWDWHGDXWRPDWLFDOO\PDQXDOO\RUEDVHGRQ)LUVW2Q)LUVW2II
(FOFO). The automatic rotation is recommended for most applications.
 7KHFXUUHQW/HDG%RLOHULVVKRZQLQEUDFNHWVRQWKHPDLQGLVSOD\
 2QO\ERLOHUVWKDWDUHVHWWR$XWR0RGHFDQEH/HDG7KHUHIRUHQRWDOOWKHERLOHUVPD\
EHDYDLODEOHZKHQPDQXDOO\VHOHFWLQJDQHZ/HDG%RLOHU
 ,I7LPHLVVHOHFWHGDVHFRQGVFUHHQZLOODOORZWKHDGMXVWPHQWRIWKH$XWR5RWDWH3HULRG
,I+RXUVGHIDXOWVHWWLQJZDVVHOHFWHGWKH¿UVWURWDWLRQZLOOWDNHHIIHFWDIWHUKRXUV
if the Time was not set. However, if the Time was set, the rotation will always take
SODFHDW$07KHIROORZLQJURWDWLRQVZLOOWDNHSODFHHYHU\KRXUVWKHUHDIWHU
 ,I7LPH5RWDWLRQZDVVHWWRRWKHUWKDQKRXUVWKHURWDWLRQWLPHUZLOOVWDUWIURPWKH
moment the setting is changed.
 ,I)LUVW2Q)LUVW2II)2)2LVVHOHFWHGWKHFRQFHSWZLOOIROORZWKLVH[DPSOHLI$LVWKH
OHDGWKHVWDUWLQJVHTXHQFHRIWKHERLOHUVZLOOEH$%WKHQ&:KHQWKHGHHQHUJL]LQJ
of the stages starts, it will turn off A, B, Then C. Then, stage D will be the new lead for
the next load.
6(7%$&.6&+('8/(
Hold Button: MENU/<System Settings>/<Stage Settings>/<Setback Schedule>
This menu provides the Setback and Boost based on Day/Night Schedule. It will only be
available when Shutdown or Tstat are selected as the Startup External Input option.
-- LEAD ROTATION --
Time
Manual
FOFO
BACK
SELECT
If Time Rotation is selected
AUTO ROTATE PERIOD
24hrs
[ ]
BACK SAVE
SETBACK SCHEDULE
Setback 0 F
Present Time **:**
Day Schdule 7:00Am
Night Schdul 7:00Pm
BACK SELECT
6(7%$&.
$GMXVWDEOHIURP°)°&WR)& 'HIDXOW°)°&
Hold Button: MENU/<System Settings>/<Stbck Schdle>/Setback LQ'D\1LJKW6FKHGXOH
Hold Button: MENU/<System Settings>/Setback LQ([WHUQDO6LJQDO
 7KH6HWEDFNIHDWXUHFDQEHXVHGWRSURYLGHWKH%&3:ZLWKDORZHUWHPSHUDWXUH6HW
Point when less load is required during the night or on the weekends when the building
is not occupied, but heat is still required.
------ SETBACK -------
0 F
[ ]
BACK SAVE
 7KHQHZ6HW3RLQWZLOODSSHDURQWKHPDLQGLVSOD\LQGLFDWLQJWKLVFRQGLWLRQSetback to 160 F".
 )RUH[DPSOHLIWKHFDOFXODWHGWHPSHUDWXUHLV)DQGWKH6HWEDFNLV)WKHQZKHQLQ6HWEDFNWKH%&3:ZLOOKROGD6HW
3RLQWRI)180°F - 20°F).
 $IWHUVHOHFWLQJDYDOXHLQ6HWEDFN\RXZLOOEHGLUHFWHGWRWKH%RRVWPHQX
%2267
$GMXVWDEOHIURP)&WR)& 'HIDXOW°)°&
Hold Button: MENU/<System Settings>/Setback/Boost
 7KLVIHDWXUHVDOORZVDEXLOGLQJWRZDUPXSGRZQTXLFNO\DIWHUD6HWEDFNSHULRGWREULQJ
the building to the desired temperature faster.
-------- BOOST ---------
0 F
[ ]
BACK SAVE
background
27
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
 7KH%RRVWWHPSHUDWXUHZLOOEHWKHQXPEHURIGHJUHHVWREHDGGHGWRWKH7DUJHW
 7KHQHZ6HW3RLQWZLOODSSHDURQWKHPDLQGLVSOD\LQGLFDWLQJWKLVFRQGLWLRQBoost to 190 F".
 8VLQJWKHSUHYLRXVH[DPSOHLIWKH7DUJHWZDV)DQGWKH6HWEDFNZDV)DQGWKH%RRVWZDV)IRUPLQXWHVDIWHUWKH
VHWEDFNSHULRGWKH%RRVWZLOOFKDQJHWKHWDUJHWWR)IRUDSHULRGRIPLQXWHV
%22673(5,2'
$GMXVWDEOHIURPWRPLQXWHV 'HIDXOWPLQXWHV
Hold Button: MENU/<System Settings>/Setback/Boost/Boost Period
 7KLVZLOOGHWHUPLQHWKHOHQJWKRIWLPHWKHV\VWHPZLOOUHFHLYH%RRVW
 ,I([WHUQDO6LJQDOZDVVHOHFWHGDVWKH6HWEDFN0RGHWKH%RRVWZLOOVWDUWZKHQWKH
------ BOOST PERIOD---
30min
[ ]
BACK SAVE
switch from Setback to normal operation takes place and will continue for the full Boost Period. An example would be if
WKH%RRVW3HULRGZDVVHWWRPLQXWHVDQGWKHVKRUWLQJRIWKH6HWEDFNWHUPLQDOVKDVHQGHGDW$PWKH%RRVWZLOOVWDUWDW
$PDQGZLOOWHUPLQDWHDW$PZKHUHWKHFRQWUROZLOOUHVXPHQRUPDORSHUDWLRQ
 ,I'D\1LJKW6FKHGXOHVZHUHDYDLODEOHWKH%RRVWZLOOVWDUWDIXOO%RRVW3HULRGSULRUWRWKHVZLWFKIURP1LJKWVHWEDFNWR'D\
QRUPDORSHUDWLRQ,IWKH'D\ZDVVHWWRVWDUWDW$PWKH%RRVW3HULRGZDVVHWWRPLQXWHVWKH%RRVWZLOOVWDUWDW$P
DQGWHUPLQDWHDW$P
$YRLGLQJ&RQÀLFWLQJ%RLOHU/LPLWV
 7KHWHPSHUDWXUHOLPLWVVHWRQWKHERLOHUV0867EHVHWFRQVLGHUDEO\KLJKHUWKDQWKH
BCP-8W’s Set Point for the reasons detailed below.
 7KH%&3:VHQVRULVORFDWHGLQDFRPPRQKHDGHUVRPHGLVWDQFHIURPWKHERLOHUV$V
the temperature rises in the header and before reaching the sensor location, energy is
dissipated. Therefore, the temperature in the header could be lower than that registered
by boiler sensors.
 ,QDGGLWLRQWRWKHQRUPDOGURSH[SHULHQFHGEHWZHHQWKHERLOHUVWHPSHUDWXUHDQGWKDW
:$51,1*
The temperature limits set on
the boilers must be higher than
the BCP-8W Set Point. Read
the section at left for details
that will prevent erratic system
operation.
UHDGE\WKH%&3:VHQVRUWKH/DVW6WDJH+ROGVHWWLQJPXVWEHDFFRXQWHGIRU7KHERLOHUOLPLWPXVWEHVHWDERYHWKH6HW3RLQW
3/86WKH/DVW6WDJH+ROG3/86WKHQRUPDOGURSH[SHULHQFHGLQWKHSLSLQJ
 8VLQJWKHSUHYLRXVH[DPSOHRID)/DVW6WDJH+ROGZLWKD)6HW3RLQWWKHERLOHUV¶OLPLWVPXVWEHVHWHQRXJKRYHU)
to prevent the boilers’ internal limits being reached. In this situation, the boiler high limit should be set at approximately 180°F
to prevent the difference in boiler temperature vs. header temperature from causing erratic operation.
'$<1,*+76&+('8/(6
Hold Button: MENU/<System Settings>/<Setback Schedule>/Day Schedules
 7KH%&3:KDVWZROHYHOVRIKHDW7KH'D\OHYHOLVXVHGZKHQDEXLOGLQJLVRFFXSLHG
and people are active.
 7KH1LJKW6HWEDFNOHYHOLVXVHGZKHQDEXLOGLQJLVQRWRFFXSLHGRUZKHQSHRSOHDUH
sleeping. This setting reduces the calculated temperature by the Setback setting based
RQWKHSURYLGHGVFKHGXOH,IWKH'D\FDOFXODWHGZDWHUWHPSHUDWXUHZDVÛ)DQGWKH
6HWEDFNZDVÛ)WKH1LJKW6FKHGXOHZLOOUXQDWÛ)Û) Û)
-- DAY SCHEDULE ----
07:**Am
BACK SAVE
-- NIGHT SCHEDULE --
10:**Pm
BACK SAVE
 ,IWKH%RRVWIHDWXUHLVEHLQJXVHGLWXVHVWKH'D\6FKHGXOHDVD%RRVWHQGLQJSRLQW7KDWLVLIWKH'D\6FKHGXOHLVVHWWRVWDUW
DW$0WKH%RRVWZDVVHWWR)DQGWKH%RRVW3HULRGZDVPLQXWHVWKH%RRVWZLOOVWDUWDW$07KHQZKHQLQ
%RRVW%&3:ZLOOUDLVHWKHFDOFXODWHGZDWHUWHPSHUDWXUHE\WKH%RRVWDPRXQW8VLQJWKHSUHYLRXVH[DPSOHDW$0WKH
%&3:ZLOOUDLVHWKHFDOFXODWHGZDWHUWRÛ)Û)Û)XQWLO$0ZKHUHLWZLOOGURSEDFNWRWKHQRUPDOFDOFXODWHG
temperature of 150ÛF.
6(735(6(177,0(
Hold Button: MENU/<System Settings>/<Setback Schedule>/Present Time
Hold Button: MENU/<Maintenance>/Present Time
 7KH7LPHLVXVHGIRU'D\1LJKW6FKHGXOHDQG+LVWRU\JUDSK
 $GMXVWWKHWLPHE\VHOHFWLQJ7LPHIURPWKHPHQXDQGWKHQVFUROOLQJWKURXJKWKHKRXUV
followed by the minutes. If hours are to be set to PM, scroll through the AM hours to
reach the PM hours.
- SET PRESENT TIME
**:**
BACK SAVE
$/(57
Remember that the battery is used as a time backup. If no power is supplied to the BCP-8W, the battery will die in
three months and time clock values will be lost. Thus, DO NOT power down the control during off-season.
background
28
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
'+:6(77,1*6
Hold Button: MENU/<System Settings>/<DHW Settings>
 $'+:FDOOFDQEHLQLWLDWHGE\VKRUWLQJWKH'+:LQSXWWHUPLQDOV33 and 34. In
DGGLWLRQXVLQJD:HLO0F/DLQWHPSHUDWXUHVHQVRURQWKHVDPHWHUPLQDOVLQVWHDGRID
dry-contact input will add the DHW Set Point and Differential control capability.
 On a DHW call, the BCP-8W will raise the Target to either 200ºF or the Maximum
Target, which ever is lower.
 The BCP-8W provides three levels of DHW pump operation. The ¿UVWLVZKHQ3ULPDU\
Secondary is selected as the DHW Piping from the Startup Menu on page 18. This
option will provide no DHW Priority. And, if there was a DHW call during the Summer
or when the outdoor temperature is above the Outdoor Cutoff, both the DHW Pump and
WKH6\VWHPUHOD\VZLOOHQHUJL]H8SRQWKHWHUPLQDWLRQRIWKH'+:FDOOWKH'+:3XPS
UHOD\ZLOOGHHQHUJL]HOHDYLQJWKH6\VWHPUHOD\HQHUJL]HGIRUWKH5XQ2QGHOD\
-- DHW SETTINGS ---
DHW Temp. 140 F
DHW Prior Tmr 60min
DHW Set Point120
F
DHW Diff. 5
F
BACK SELECT
 ,I3DUDOOHOZDVVHOHFWHGDVWKH'+:3LSLQJIURPWKH6WDUWXSPHQXRQSDJH18 and the Season was set to Winter while the DHW
3ULRULW\7LPHUZDVVHWWR12D'+:FDOOZLOONHHSWKH6\VWHPUHOD\HQHUJL]HGLQDGGLWLRQWRHQHUJL]LQJWKH'+:3XPSUHOD\
8SRQWHUPLQDWLRQRIWKH'+:FDOOWKH'+:3XPSUHOD\ZLOOGHHQHUJL]HOHDYLQJWKH6\VWHPUHOD\RQ
 +RZHYHULQ:LQWHULIWKH'+:3ULRULW\7LPHUZDVVHWWRDYDOXHRWKHUWKDQ12D'+:FDOOZLOOGHHQHUJL]HWKH6\VWHPUHOD\
DQGHQHUJL]HWKH'+:3XPSUHOD\7KLVZLOOUHPDLQIRUWKHSHULRGRIWKH'+:3ULRULW\7LPHUVHWWLQJRUXQWLOWKH'+:FDOO
terminates, whichever is sooner. If the DHW call was still active after the DHW Priority Timer elapses, the System relay will
HQHUJL]HIRUWKHUHPDLQLQJRIWKH'+:FDOOSHULRG
'+:35,25,7<7,0(5$9$,/$%/(:,7+3$5$//(/'+:3,3,1*
$GMXVWDEOH12WRPLQXWHV 'HIDXOWPLQXWHV
Hold Button: MENU/<System Settings>/<DHW Settings>/DHW Prior. Timer LQ3DUDOOHO
 7KH'+:3ULRULW\7LPHULVRQO\DYDLODEOHZKHQ'+:3LSLQJLVVHWWR3DUDOOHO6HHSDJH
18). It provides the user with the capability of selecting the DHW Priority period. If
12ZDVVHOHFWHGD'+:FDOOZLOOHQHUJL]HWKH'+:SXPSUHOD\ZLWKRXWDIIHFWLQJWKH
System Pump operation. That is, when in Summer or Outdoor Cutoff, a DHW call will
HQHUJL]HRQO\WKH'+:3XPSUHOD\OHDYLQJWKH6\VWHPUHOD\RII
DHW PRIORITY TIMER
2min
[ ]
BACK SAVE
 ,Q:LQWHULIWKH'+:3ULRULW\7LPHUZDVVHWWRDYDOXHRWKHUWKDQ12D'+:FDOOZKHQWKHRXWGRRUWHPSHUDWXUHLVEHORZWKH
2XWGRRU&XWRIIZLOOFDXVHWKH6\VWHPUHOD\WRGHHQHUJL]HDQGWKH'+:3XPSUHOD\WRHQHUJL]HIRUWKHSHULRGRIWKH'+:
Priority Timer or until the DHW call expertise, whichever happens sooner. If the DHW call did not expire within the Priority
SHULRGWKHQWKH6\VWHPUHOD\ZLOOHQHUJL]H
'+:6(732,175(48,5(6$1237,21$/'+:7(03(5$785(6(1625
$GMXVWDEOH°)°&WR)& 'HIDXOW°)°&
Hold Button: MENU/<System Settings>/<DHW Settings>/DHW Set Point
 7KLVLVWKHGHVLUHG'+:WHPSHUDWXUHVHWWLQJDWZKLFKWKH'+:3XPSUHOD\ZLOOGH
HQHUJL]HZKHQUHDFKHG
 7KH%&3:FDQDFFHSWD'+:FDOOLQWZRZD\V$QDTXDVWDWFDQSURYLGHDGU\
FRQWDFWFORVXUHWRWHUPLQDOVDQGLVWKH¿UVWRSWLRQ
-- DHW SET POINT --
140 F
[ ]
BACK SAVE
 7KHVHFRQGRSWLRQZLOOEHFRQQHFWLQJD:HLO0F/DLQWHPSHUDWXUHVHQVRUIRULPPHUVLRQLQD,'ZHOO
ZLOORIIHUWKHFDSDELOLW\RIDGMXVWLQJWKH'+:6HW3RLQWDQG'LIIHUHQWLDOWKURXJKWKH%&3:HDV\WRIROORZPHQX
(See page 28). In addition to being able to view and log DHW temperature history.
'+:',))(5(17,$/
$GMXVWDEOH°)°&WR)& 'HIDXOW°)°&
Hold Button: MENU/<System Settings>/<DHW Settings>/DHW Diff.
 7KLVUHSUHVHQWVWKHQXPEHURIGHJUHHVWKH'+:WHPSHUDWXUHFDQGURSIURPWKH'+:
6HW3RLQWEHIRUHD'+:FDOOFDQEHUHFRJQL]HGDQGWKH'+:3XPSUHOD\HQHUJL]HG
 $ODUJH'+:'LIIHUHQWLDOZLOOUHVXOWLQRVFLOODWLRQLQWKH'+:WHPSHUDWXUH+RZHYHUD
small DHW Differential will have a tighter control over the DHW temperature but might
result in boilers coming on frequently for short periods to satisfy the DHW Set Point and
Differential settings.
DHW DIFFERENTIAL
10 F
[ ]
BACK SAVE
background
29
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
38039$/9($1'&20%867,21$,5'$03(523(5$7,21
 7KH%&3:FRQWUROVPXOWLSOHUHOD\VHDFKFRQWUROOLQJGLIIHUHQWW\SHVRIHTXLSPHQW,QDGGLWLRQWRWKHFRQWURORIWKHERLOHUVLW
can control the primary system pump, boiler pumps or valves, a DHW pump, and a combustion air damper. The operation of
those relays depends on the Startup and System Settings.
58121
$GMXVWDEOHWRPLQXWHV 'HIDXOWPLQXWHV
Hold Button: MENU/<System Settings>/Run-On
 7KH5XQ2QDSSOLHVWRDOOSXPSVYDOYHVDQGGDPSHUV,WLVWKHDGGLWLRQDOWLPHDSXPS
valve, or a combustion air damper relay will run after the output boiler relays has de-
HQHUJL]HG)RUSXPSVDQGYDOYHVLWLVXVHGWRGLVVLSDWHWKHH[FHVVHQHUJ\IURPWKH
heating system into the building. For a combustion air damper, it brings in enough fresh
DLUIRUWKHQH[WERLOHU¿UHXS
------- RUN-ON -------
2min
[ ]
BACK SAVE
 7KH5XQ2QWLPHVKRXOGEHVHWEDVHGRQWKHVL]HDQGW\SHRIWKHHTXLSPHQW$ERLOHUZLWKORZZDWHUFRQWHQWZLOOQHHGDORQJHU
Run-On than a boiler with more water content.
3803(;(5&,6(
$GMXVWDEOH2II2Q 'HIDXOW2II
Hold Button: MENU/<System Settings>/Pump Exercise
 7KH%&3:SURYLGHVDQRSWLRQWRH[HUFLVHSXPSVIRUVHFRQGVZKHQQRWXVHGIRU
seven days. This option reduces pumps' impellers locking after a long off-season period.
--- PUMP EXERCISE --
Off
On
BACK SAVE
background
30
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
0$,17(1$1&(
Hold Button: MENU/<Maintenance>
The Maintenance menu gives access to sensor and output trimmings in addition to viewing
WKH6WDUWXSFRQ¿JXUDWLRQVHWWLQJVDVZHOODVVHQVRU+LVWRU\
$/(57
To be able to change the BCP-8W settings the Program/Run Switch must be set
to Program. The switch is located under the Enclosure Wiring Cover for security.
The Enclosure Wiring Cover can be securely closed using a padlock.
---- MAINTENANCE ----
Unit F
Present Time12:30P
<Sensor Trim>
<Histories>
<Configuration>
BACK SELECT
6<67(0287'2256(162575,0
$GMXVWDEOH°)°&WR°)°& 'HIDXOW°F
Hold Button: MENU/<Maintenance>/System Trim
Hold Button: MENU/<Maintenance>/Outdoor Trim
Hold Button: MENU/<Maintenance>/Return Trim
Hold Button: MENU/<Maintenance>/DHW Trim
 7KH:HLO0F/DLQWKHUPLVWRUW\SHVHQVRUVDUHYHU\DFFXUDWHDQGQRUPDOO\UHTXLUHQR
calibration. However, sometimes it may be desirable to make small adjustments to the
displayed value.
 'RQRWXVHWKH7ULPVHWWLQJWRPDNHWKH2XWGRRUVHQVRUPDWFKWKHRQHUHSRUWHGRQWKH
UDGLRRU792XWGRRUWHPSHUDWXUHFDQYDU\ZLGHO\RYHUDEURDGFDVWUDQJH
--- SENSOR TRIM ----
System Trim +0 F
Outdoor Trim +0
F
Return Trim +0 F
DHW Trim +0
F
BACK SELECT
+,6725<
Hold Button: MENU/<Histories>
The BCP-8W provides users with a graphical history of the System, Outdoor, DHW, and Return
sensors for the previous 24 hours. The temperatures are sampled every 12 minutes. That is,
readings of temperatures are recorded and stored every 12 minutes for the last 24 hours.
 7RYLHZWKHYDOXHVRIDVSHFL¿FSHULRGXVHWKHWZRPLGGOHEXWWRQVWRVFUROOWRWKDWWLPH
and read the upper left temperature.
 7KH¿UVWVFUHHQZLOOEHWKH6\VWHP7HPSHUDWXUH+LVWRU\%\FOLFNLQJRQWKH1H[WEXWWRQ
you will be able to view the Outdoor Temperature History, then, the Return History
followed by the DHW History.
Sys=120 F 10:00AM
BACK NEXT
BCP-8W V1.00
Outdoor reset
Heating-BreakOnRise
Day/Night Schedule
DHW Parallel
BACK NEXT
8 X On/Off
PID,Fault Stgs Off
BACK NEXT
&21),*85$7,21
Hold Button: 0(180DLQWHQDQFH!&RQ¿JXUDWLRQ!
 7KLVPHQXSURYLGHVDFRQVROLGDWHGYLHZRIWKH6WDUWXSVHWWLQJV
 $GGLWLRQDOFRQWUROVHWWLQJVZLOOEHDYDLODEOHE\VHOHFWLQJWKH1(;7RSWLRQ
',63/$<$1'%877216
The BCP-8W display layout provides a variety of information that gives an immediate
picture of the operation status. The display shows four heating boilers at a time. The
two middle buttons scrolls the screen to view any additional boilers. Moreover, all the
information is brightly displayed. It can be viewed in brightly or dimly lit rooms.
 7KHEXWWRQVIXQFWLRQDOLW\FKDQJHVEDVHGRQWKHVFUHHQDQGPHQXOHYHO7KHEXWWRQV
functionality is displayed on a dark background on the screen's bottom line.
 7KHVHFRQGOLQHIURPWKHWRSLVWKH0HVVDJH'LVSOD\/LQH,QQRUPDORSHUDWLRQLW
displays the Target Set Point. If a Return sensor was connected, the Target display will
be alternating its value with the Return temperature. When the control is to display a
status message, the message will replace Target and Return temperatures. See Display
Messages on page 1.
background
31
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
7KHWZRPLGGOHEXWWRQVIXQFWLRQVDUHDVIROORZV
 7KH+RUL]RQWDODUURZVDUHWRVFUROOWKURXJKWKHDYDLODEOHVWDJHV
 7KH9HUWLFDODUURZVDUHWRVFUROOWKURXJKWKHPHQXIXQFWLRQVZKHQLQ
PHQXVRUWRFKDQJHYDOXHVRIVHWWLQJVZKHQLQLWVVSHFL¿FVFUHHQ
Sys=
155
F OD=
58
F
DHW all (200 F)
<AB > DE GH JK
HI HI LO ----
BOILER MENU
Outdoor Temp
System Temp
Message Display Line
Units and their
Status
Button functions
',63/$<28738767$786
7KH%&3:XQLWVHTXHQFLQJVWDWXVJLYHVLPPHGLDWHDFFHVVWRHDFKERLOHUVWDWXV7KHIROORZLQJOLVWVKRZVDOOSRVVLEOHERLOHUVWDWXV
 $%! 7ZR6WDJHERLOHUDQG%RLOHU$%LVWKH/HDGLQVHTXHQFLQJ%UDFNHWVLQGLFDWH/HDG6WDJH
  %RLOHULVGHHQHUJL]HG7KHERLOHU0RGHLVVHWWR$XWR
 67% %RLOHULVGHHQHUJL]HG7KHERLOHU0RGHLVVHWWR6WDQGE\
 +, %RLOHUKLJKHVWVWDJHLVDFWLYH7KHERLOHU0RGHLVVHWWRHLWKHU$XWRRU6WDQGE\
 0(' %RLOHU0LGGOHVWDJHLVDFWLYH$YDLODEOHLQ7KUHHVWDJHERLOHUVRQO\7KHERLOHU0RGHLVVHWWRHLWKHU$XWRRU6WDQGE\
 0+, %RLOHU0LGGOH+LJKVWDJHLVDFWLYH$YDLODEOHLQ)RXUVWDJHERLOHUVRQO\7KHERLOHU0RGHLVVHWWRHLWKHU$XWRRU
Standby.
 0/2 %RLOHU0LGGOH/RZVWDJHLVDFWLYH$YDLODEOHLQ)RXUVWDJHERLOHUVRQO\7KHERLOHU0RGHLVVHWWRHLWKHU$XWRRU
Standby.
 /2 %RLOHU/RZHVWVWDJHLVDFWLYH7KHERLOHU0RGHLVVHWWRHLWKHU$XWRRU6WDQGE\
 21 $OO%RLOHU6WDJHVDUHVHWWR21
 2)) $OO%RLOHU6WDJHVDUHVHWWR2))RUWKHERLOHUGRHVQRWH[LVW
 &( %RLOHURQ([WHQVLRQSDQHOLVQRWFRPPXQLFDWLQJEDFNWRWKH%&3:
 Boiler Pumps are being controlled by the BCP-8W.
 %RLOHU9DOYHVDUHEHLQJFRQWUROOHGE\WKH%&3:
',63/$<0(66$*(6
The BCP-8W normal display layout reserved the second line for message indications. The following is a list of the most common
0HVVDJH'LVSOD\/LQHLQIRUPDWLRQ
 6XPPHU 7KHFRQWUROLVVHWWR6XPPHU1RKHDWLVDFWLYH
 2XWGRRU&XWRII 7KH2XWGRRUWHPSHUDWXUHLVDERYHWKH2XWGRRU&XWRII
 6KXWGRZQ$FWLYH 7KH6KXWGRZQ7HUPLQDOVDUH6KRUWHG1RKHDWLQJERLOHUVZLOOEHDFWLYH
 6KXWGRZQE\(06 7KH(06LVEHORZP$RUDERYHP$
 '+:&DOOÛ) 7KHUHLVD'+:'RPHVWLF+RW:DWHUFDOO7KH%&3:ZLOO5DLVHV\VWHP6HW3RLQWWRWKH
LQGLFDWHGWHPSHUDWXUH'+:LQFUHDVHVFDOFXODWHGWHPSHUDWXUHWRÛ)RU0D[:DWHU7HPSHUDWXUH
whichever is lower.
 +ROGLQJ5HWXUQDWÛ) 5HWXUQVHQVRULVUHDGLQJOHVVWKDQWKH0LQLPXP5HWXUQ%&3:LVWU\LQJWRUDLVHUHWXUQWRÛ)
 +ROGLQJ8QWLOÛ) 7KH/HDGERLOHULVLQ/DVW6WDJH+ROG7KLVH[DPSOHVKRZVWKDWWKHOHDGVWDJHZLOOWXUQRIIZKHQ
V\VWHPWHPSHUDWXUHUHDFKHVÛ)
 :DLWLQJIRU&RPE3URYH 7KH6\VWHPRU&RPEXVWLRQ$LU'DPSHUUHOD\LV21DQGWKHSURYHWHUPLQDOVDUHRSHQEHIRUHWKHOHDG
ERLOHUUHOD\FDQHQHUJL]H
 6<63URYH)DLOXUH $IWHUERLOHUVKDYHUXQIRUDZKLOH3URYHVLJQDOZDVRSHQHG7KHERLOHUUHOD\VZLOOGHHQHUJL]H
+RZHYHUWKH6\VWHPUHOD\ZLOOUHPDLQHQHUJL]HG
background
32
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
%2,/(56(77,1*6
Button: BOILER/
 ,QPRVWLQVWDOODWLRQVDOODFWLYHERLOHUDGMXVWPHQWVDUHWKHVDPHEXWHDFKFDQEH
FRQ¿JXUHGGLIIHUHQWO\LIGHVLUHG
 :KHQWKH%2,/(5EXWWRQLVGHSUHVVHGWKH%RLOHU$6HWWLQJVPHQXZLOOEHVKRZQ
----- BOILER AB -----
Mode Auto
Runtime 58Hrs
<Prev Boiler>
<Next Boiler>
BACK SAVE
 0DNHDOOWKHDSSURSULDWHVHWWLQJVIRU%RLOHU$%LI6WDJHZDVVHOHFWHGDVWKH%XUQHU7\SHIURPWKH6WDUWXSRQSDJH19).
 7KHQVHOHFWWKH1H[W6WDJHRSWLRQIURPWKHPHQXWREULQJXSWKH%RLOHU&'6HWWLQJVPHQXDQGPDNHDOOWKHVHWWLQJV&RQWLQXH
until all boilers have been set.
 ,ID%&3;LVFRQQHFWHGWRWKH%&3:VFUROOLQJWKURXJKVWDJHVXVLQJWKH1H[WDQG3UHYPHQXRSWLRQVZLOOVFUROOWKURXJKWKH
BCP-8X stages as well.
$/(57
To be able to change the BCP-8W settings, the Program/Run Switch must be set
to Program. The switch is located under the Enclosure Wiring Cover for security.
The Enclosure Wiring Cover can be securely closed using a padlock.
PROGRAM RUN
02'(
$XWR6WDQGE\2II2Q 'HIDXOW$XWR
Button: BOILER/Mode
 7KH%&3:RQO\FRQWUROVDQ\ERLOHUVHWWR$XWRRUDIWHUDGHOD\WKRVHVHWWR6WDQGE\
 $Q\RXWSXWZLWKRXWDQDFWLYHERLOHUFRQQHFWHGPXVWEHVHWWR2II
 7KHIROORZLQJOLVWGHVFULEHVWKH02'(RSWLRQV
-- BOILER AB MODE -
Auto
Standby
Off
On
BACK SAVE
$XWR - The BCP-8W will control the boilers operation to maintain the desired Set Point. Only boilers set to Auto can be lead
boiler.
6WDQGE\ These boilers can only be activated when all boilers in Auto have been at HI for an adjustable Standby delay period.
Standby boilers are generally used as a backup in extreme load conditions. Note that, a Standby boiler cannot be a lead
boiler. Standby Delay is only available in PID mode.
2II Any output boiler not connected to a physical boiler should be set to Off. The Off Mode can also be used to disable
boilers that are being serviced.
2Q The On Mode should only be used when testing a boiler. The On Mode overrides the PROVE and SHUTDOWN inputs.
Once set to On the boiler will immediately start all of its stages.
5817,0(
&OHDU
Button: BOILER/RunTime
 7KH5XQ7LPHSURYLGHVDQDFFXPXODWLYHKRXUO\UXQIRUWKHVHOHFWHGERLOHU
 7KH5XQ7LPHIRUDVSHFL¿FERLOHUFDQEHUHVHWWR]HURE\SUHVVLQJWKHPLGGOHWZR
buttons.
BOILER AB RUNTIME
58hrs
BACK CLEAR OK
background
33
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
7528%/(6+227,1*
7(03(5$785(,13876
'LVSOD\VKRZV6HQVRU23(1
Check the sensor is connected and the wires are continuous to the BCP-8W. Finally follow the procedure for Incorrect
Temperature Display.
'LVSOD\VKRZV6HQVRU6+257
The BCP-8W sees a short across the input terminals. Remove the wires from the the sensor terminals. The display should change
to read OPEN. If it doesn’t, the BCP-8W may be damaged.
'LVSOD\VKRZVDQ,QFRUUHFW7HPSHUDWXUH'LVSOD\
Remove the wires from the sensor terminals. The display should change to read OPEN. If it doesn’t, the BCP-8W may be
damaged. Take an ohm reading across the detached sensor wires. Take an ohm reading across the detached sensor wires. The
ohm reading should correspond to the Temperature sensor Table. If it does not, the sensor may be damaged.
5HWXUQ6HQVRUGRHVQRW'LVSOD\7HPSHUDWXUH
Check the sensor is connected and the wires are continuous to the BCP-8W. Finally follow the
procedure for Incorrect temperature display.
&21752/23(5$7,21
7RR0XFK+HDW
&KHFNLIWKHFRQWUROKDVDQ\RIWKHIROORZLQJFRQGLWLRQV
 'RPHVWLF+RW:DWHUFDOO- The BCP-8W will raise the temperature of the system to either
Û)RU0D[LPXP7DUJHWRQD'+:FDOO
 5HVHW5DWLRDQG2IIVHW- If excessive heat occurs only in certain weather conditions, adjust
the Reset Ratio and Offset (See Understanding Operating Concept on page 5). If excessive
heat occurs year round, reduce the Offset.
 %RLOHU0RGH6HWWLQJV- The BCP-8W will only sequence boilers with a Mode set to Auto or
Standby. Check to if any boiler stage is set to On.
 &RQWURO6HWWLQJV7KH/DVW6WDJH+ROGZLOODOORZRQO\WKH/HDGERLOHUWRH[FHHGWKHVHWSRLQW
,IWKHVHWWLQJLVWRRKLJKDQGRQO\WKH/HDGERLOHULVRQWKHV\VWHPFDQRYHUKHDW5HGXFHWKH
/DVW6WDJH+ROGVHWWLQJ7KLVZLOOPRVWO\RFFXULQPLOGZHDWKHU
7RR/LWWOH+HDW
&KHFNLIWKHFRQWUROKDVDQ\RIWKHIROORZLQJFRQGLWLRQV
 5HVHW5DWLRDQG2IIVHW- If reduced heat occurs only in certain weather conditions, adjust the
Reset Ratio and Offset (See Understanding Operating Concept on page 5). If reduced heat
occurs year round, increase the Offset.
 6HWEDFNDQG'D\1LJKW6FKHGXOH,IUHGXFHGKHDWRFFXUVRQO\GXULQJVSHFL¿FKRXUVFKHFN
the Day/Night Schedule and the Setback, Boost, and Boost Period values. Either reduce the
Setback or Boost settings or change the Day and Night Schedules.
 %RLOHU0RGH6HWWLQJV- The BCP-8W will only modulate boilers their mode is set to Auto or
Standby. Check if any boiler stage is set to Manual, Off, or Standby.
%RLOHUVDUH6KRUW&\FOLQJ
 0LQLPXP5XQWLPH- Increase the Minimum Runtime only if all boilers tend to short-cycle.
 /DVW6WDJH+ROG,QFUHDVHWKH/DVW6WDJH+ROGRQO\LIWKHOHDGERLOHUWHQGVWRVKRUWF\FOH
6\VWHPLV2YHUVKRRWLQJRU8QGHUVKRRWLQJ
 5HDFWLRQ7LPHDQG0LQLPXP5XQWLPH- If the system is overshooting or undershooting,
adjust Minimum Runtime or the Reaction Time. That depends on if the stages are brought on
fast and were not allowed to turn off until the Minimum Runtime elapsed. Or, the stages were
brought on slowly, however, were allowed to turn off quickly.
 3,'YV266- If the application the system is used on requires fast response that the normal
PID mode cannot provide, try using the OSS mode and adjust the Throttle Range according to
the system requirements.
7HPSHUDWXUH6HQVRU&KDUW
7(03(5$785(
LQ'HJUHHV°)
9DOXH
LQ2KPV
-30 117720
-20 82823
-10 59076
0 42683
10 31215
20 23089
25 19939
30 17264
35 14985
40 13040
45 11374
50 9944
55 8714
60 7653
70 5941
80 4649
90 3667
100 2914
110 2332
120 1879
130 1524
140 1243
150 1021
160 842
170 699
180 583
190 489
200 412
210 349
220 297
230 253
240 217
250 187
background
34
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
08/7,3/(%2,/(56:,7+380363,3,1*:,5,1*',$*5$06
Outdoor
Sensor
System
Sensor
120VAC
Boiler 1 Boiler 2 Boiler 3 Boiler 4
Building Heating Loop
SQ-Elite
SQ-Elite-8
SEQUENCING CONTROL
SYSTEM
DHW PUMP
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
LN
12
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11 13
Stage E
15
Stage F
17
Stage D
6 8 10 12 14
16 18
RS485
SYS=144F OD=35F
<A
> C E G
HI HI -- OFF
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27 29 31
DHW
33
SHUTDOWN
/SETBACK
35
RETURN
TEMP
20 22 28 30 32 34 36
STAGE MENU
Stage E
Stage F
Stage G
Stage H
Stage A
Stage B
Stage C
Stage D
25 26
PRESS
+ -
37 38
PROVE
SYSTEM
TEMP
PROGRAM RUN
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
COMB. AIR
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
CUS
System
Pump
SQ-Elite-8
SEQUENCING CONTROL
SYSTEM
DHW PUMP
INPUT RATINGS:
115VAC 60Hz, 12VA MAX
Use Copper Conductors Only.
CAUTION:
Risk of Electric Shock.
PWR
LN
12
SENSORS MUST BE GOLD SERIES
SYSTEM
3
DHW
PUMP
5
Stage A
7
Stage B
9
Stage C
11 13
Stage E
15
Stage F
17
Stage D
6 8 10 12 14
16 18
RS485
SYS=144F OD=35F
<A
>C E G
HI LO -- OFF
4
Stage G
19
Stage H
21
OUTDOOR
TEMP
27 29 31
DHW
33
SHUTDOWN
/TSTAT
/SETBACK
35
RETURN
TEMP
20 22 28 30 32 34 36
STAGE MENU
Stage E
Stage F
Stage G
Stage H
Stage A
Stage B
Stage C
Stage D
25 26
PRESS
+ -
37 38
PROVE
SYSTEM
TEMP
PROGRAM RUN
23 24
COMB.
AIR
DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS
COMB. AIR
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
CUS
Sensor Shiled
System Sensor
Shutdown
Dry Contact
Unit1
Pump1
L
N
Prove
Dry Contact
Unit2
Pump2
Unit3
Pump3
Unit4
Pump4
L
N
The BCP-8W sequencing 4 single-
stage boilers and their boiler pumps.
The boilers are piped in Reverse
Return on the primary loop. The
System output is controlling the
System Pump.
:HLO0F/DLQLVDZDUHWKDWHDFK
LQVWDOODWLRQLVXQLTXH7KXV:HLO
0F/DLQLVQRWUHVSRQVLEOHIRUDQ\
LQVWDOODWLRQUHODWHGWRDQ\HOHFWULFDORU
SOXPELQJGLDJUDPJHQHUDWHGE\:HLO
0F/DLQ7KHSURYLGHGLOOXVWUDWLRQVDUH
WRGHPRQVWUDWH:HLO0F/DLQ¶VFRQWURO
RSHUDWLQJFRQFHSWRQO\
background
35
%&3:8VHU2SHUDWLRQ0DQXDO
S
8
6
(5
0
(1
8
6
(
4
8
(1
&(
------ SETTINGS ------
Season Winte
r
Set Point
170
F
EMS StPont
170
F
Outdoor Rese
t
1
7
0
F
Target Offse
t
+0
F
Outdoor Cutoff
70
F
Setback
20
F
BACK SELECT
-
--- SEASON ---
Winter
Summer
BACK SAVE
-
---- SET POINT ----
-
140
F
[
]
BACK SAVE
-
---
SETBACK
-------
20
F
[
]
BACK SAVE
-
OUTDOOR CUTOFF -
70
F
[
]
BACK SAVE
2SHUDWLQ
J
XVHUVKDYHDVLPSOL¿HGPHQXWKDWFDQEHDFFHVVHGE
\
FOLFNLQ
J
WKH0HQXEXWWRQ,QVWDOOHUPHQXZLOOKDYHWKHVDPH
s
ett
i
ngs
i
n a
ddi
t
i
on to Startup an
d
more a
d
vance
d
operat
i
on sett
i
ngs. T
h
e
i
nsta
ll
er menu can
b
e access
b
y
h
o
ldi
ng
d
own t
h
e Men
u
b
utton for t
h
ree secon
d
s or more.
3
5
2
*
5$0
&
+$1
*
(
6
(77,1
*
6
T
o be able to chan
g
e the BCP-8W settin
g
s the Pro
g
ram/Run Switch must be set to Pro
g
ram.
Th
e sw
i
tc
h
i
s
l
ocate
d
un
d
er t
h
e Enc
l
osure W
i
r
i
ng Cover for secur
i
ty. T
h
e Enc
l
osure W
i
r
i
ng
C
over can
b
e secure
ly
c
l
ose
d
us
i
n
g
a pa
dl
oc
k.
PROGRAM RUN
6
($
621
B
utton: ME
NU/S
easo
n
:LQWHU
6
XPPHU '
H
ID
X
OW
:
LQWHU
7K
H%&3:Z
LOO
WXUQD
OO
E
R
LO
HUUH
O
D
\
VRIIZ
K
HQ
L
W
L
V
L
Q6XPPHUVHWW
L
Q
J
7
K
H0HVVD
J
H
'LVSOD
\
/LQHZLOOUHDG
Summer
t
o show status
.
----
SEASON
--
-
Winter
Summer
BACK SAVE
:
K
HQ
L
Q:
L
QWHUW
K
H%&3:Z
LOO
DFW
L
YDWHW
K
H6
\
VUH
O
D
\
Z
K
HQHYHUW
K
H2XW
G
RRUWHPSHUDWXUHID
OO
VWRRU
E
H
O
RZW
K
H2XW
G
RRU&XWRII
s
etting. In addition, it will begin heating whenever the System temperature falls below the Set Point. The Message Display
/L
QHZ
LOO
QRW
GL
VS
O
D\DQ\VHDVRQ
L
QIRUPDW
L
RQ
$
/(57
D
O
N
O
T turn power o
ff
to the
B
C
P-
8
W when in off-season
I
f
you do so, the battery will
r
u
n
do
wn
a
n
d
will h
a
v
e
t
o
b
e re
pl
ace
d
.
I
nstea
d
, sw
i
tc
h
S
eason to
S
ummer
.
-
-
EMS SET POINT
-
-
170
F
BACK SAVE
-
NIGHT SCHEDULE -
-
07
:**
Pm
BACK SAVE
-
- DAY SCHEDULE ----
07
:**
Am
BACK SAVE
SYS=
168
FOD
=
45
F
T
GT=172
F
AB
C
<EFG
>
----
LO
BOILER MENU
---
TARGET OFFSET
-
-
+
0
F
[ ]
BACK SAVE
----
RESET RATIO
---
Custom
1(8.00 OD:1.0
0
SYS)
2(4.00 OD:1.0
0
SYS)
3(3.00
OD
:
1.00
SYS)
4(2.00
OD
:
1.00
SYS)
5(1.50
OD
:
1.00
SYS)
6(1.25 OD:1.0
0
SYS)
7(1
.
00
OD
:
1
.
00
SYS)
8(1.00
OD
:
1.25
SYS)
9(1.00
OD
:
1.50
SYS)
10(1.00
O
D:2.00 SYS)
11(1.00
O
D:3.00 SYS)
12(1.00
OD
:
4.00
SYS)
BACK SAVE
background
36
%&3:8VHU2SHUDWLRQ0DQXDO
6(732,17127$'-867$%/(,1(0602'(
$GMXVWDEOHº)º&º)ºC 'HIDXOWº)º&
Button: MENU/Set Point ,Q6HW3RLQWRU(06P$
 7KH6HWSRLQWLVWKHWHPSHUDWXUHYDOXHWKH%&3:ZLOOXVHWRFRQWUROWKHV\VWHP
 7KH%&3:ZLOODGGVXEWUDFWRUKROGWKHVWDJHVRIWKHERLOHUVWRPDLQWDLQWKHV\VWHP
temperature around the Set point.
----- SET POINT -----
140 F
[
]
BACK SAVE
 7KHV\VWHPWHPSHUDWXUHFDQEHH[SHFWHGWRÀXFWXDWHDURXQGWKHVHWSRLQW7KHDPRXQWRIÀXFWXDWLRQGHSHQGVRQWKH6\VWHP
Settings and Stage Settings.
 ,IWKH(060RGHZDV(QDEOHGWKH6HW3RLQWZLOOEHVHWE\WKH(06%06V\VWHPDQGZLOOEHDYDLODEOHWREHRQO\UHDG
 7KHUDQJHRI6HW3RLQWLQWKH(06LVVHWLQWKH6WDUWXSPHQXDWP$DQGP$
 $Q\UHDGLQJEHORZWKHP$RUDERYHP$ZLOOLQGLFDWHDShutdown by EMSPHVVDJHRQWKH0HVVDJH/LQH
5(6(75$7,2
&XVWRP2'6\VWR2'6\V'HIDXOW2'6\V
Button: MENU/Outdoor Reset/Reset Ratio ,Q2XWGRRU5HVHW2QO\
 7KH5HVHW5DWLRGHWHUPLQHVKRZWKH6\VWHPZDWHUWHPSHUDWXUHZLOOYDU\ZLWKWKH
outside temperature. With any of the ratios, the colder it becomes outside, the hotter the
temperature of the system water. (See Understanding Operation Concept on page 5)
 :LWKD2'6<6UDWLRWKH6\VWHPZDWHUWHPSHUDWXUH6<6ZLOOLQFUHDVH
UDSLGO\DVWKHRXWVLGHWHPSHUDWXUHIDOOVKLWWLQJWKH0D[LPXPRI)DW)RXWVLGH
WHPSHUDWXUH:LWKD2'6<6UDWLRWKH6\VWHPZDWHUWHPSHUDWXUH6<6
ZLOOLQFUHDVHVORZO\DVWKHRXWVLGHWHPSHUDWXUHIDOOV(YHQDW)WKHV\VWHPZDWHU
will only be 125°F, and at 22°F outside, the system water will be 112°F. Such a low
5HVHW5DWLRPLJKWEHXVHGZLWKUDGLDQWÀRRUKHDWLQJDSSOLFDWLRQV
 :LWKPRVWEDVHERDUGKHDWLQJDSSOLFDWLRQVD2'6<6VHWWLQJLVDJRRG
SODFHWRVWDUW:LWKD2'6<6UDWLRIRUHYHU\GHJUHHWKHRXWVLGH
temperature falls, the system water temperature is increased one degree.
---- RESET RATIO ---
Custom
1(8.00
OD:1.00 SYS)
2(4.00
OD:1.00 SYS)
3(3.00
OD:1.00 SYS)
4(2.00
OD:1.00 SYS)
5(1.50
OD:1.00 SYS)
6(1.25
OD:1.00 SYS)
7(1.00 OD:1.00 SYS)
8(1.00
OD:1.25 SYS)
9(1.00
OD:1.50 SYS)
10(1.00
OD:2.00 SYS)
11(1.00
OD:3.00 SYS)
12(1.00
OD:4.00 SYS)
BACK SAVE
Outdoor Temperature
Water Temperatur e
70 405060
130
120
110
100
1:4 1:1
4:1
Colder
Warmer
 ,IUHTXLUHG$GMXVWWKH5(6(75$7,2LQFROGZHDWKHU If the ambient building
temperatures are too cold in cold weather, move the ratio to a higher selection. That is,
LI2'6<6ZDVLQLWLDOO\VHOHFWHGFKDQJHWKHVHOHFWLRQWR2'
6<6,IWKHEXLOGLQJWHPSHUDWXUHVDUHWRRZDUPLQFROGZHDWKHUPRYHWKHUDWLRWR
DORZHUVHOHFWLRQ7KDWLVLI2'6<6ZDVLQLWLDOO\VHOHFWHGFKDQJHWKH
VHOHFWLRQWR2'6<6
&86720,=('5(6(75$7,2
Button: MENU/Outdoor Reset/Reset Ratio/Custom
 )RUVLWXDWLRQVZKHUHWKHDYDLODEOHUHVHWUDWLRVGRQRWSURYLGHWKHSHUIHFWEXLOGLQJKHDWORVVHTXLOLEULXPWKHFXVWRPL]HGRSWLRQ
can be used by selecting Custom from the Reset Ratio menu option.
 ,WSURYLGHVWKHXVHUZLWKWKHFDSDELOLW\RIDVVLJQLQJWZRSRLQWVRQWKHUHVHWUDWLRGLDJUDPDQGXVHWKHOLQHWKDWFRQQHFWVWKRVH
WZRSRLQWVDVWKHFXVWRPL]HGUHVHWUDWLRFXUYH(DFKRIWKHWZRSRLQWVZLOOQHHGDVSHFL¿F6\VWHPDQG2XWGRRU7HPSHUDWXUHWR
identify it on the diagram.
 7R6HWWKH¿UVWSRLQWVSHFLI\6\V7HPSDQG2'7HPS7KHQVSHFLI\6\V7HPSDQG2'7HPSWRVHWWKHVHFRQGSRLQW
on the curve. The two points can be anywhere on the line, not necessarily at the ends.
 7KHFKDUWVKRZVDQH[DPSOHRIDFXVWRPL]HGFXUYH2'6<6WKDWGRHVQRWH[LVWLQWKHVWDQGDUGFXUYHRSWLRQV,IWKH
RXWGRRUWHPSHUDWXUHUHDFKHV)WKHV\VWHPWDUJHWZLOOEH)
 5HPHPEHUWKDWWKH2IIVHW0LQ7DUJHWDQG0D[7DUJHWDSSO\WRDOOUHVHWUDWLRVLQFOXGLQJWKHFXVWRPL]HGUHVHWUDWLRRQHV
background
37
%&3:8VHU2SHUDWLRQ0DQXDO
-- SET SYS TEMP.1 -
120 F
[
]
BACK SAVE
-- SET SYS TEMP.2 -
170 F
[
]
BACK SAVE
-- AT OD TEMP.1 ---
60
F
[
]
BACK SAVE
-- AT OD TEMP.2 ---
0
F
[ ]
BACK SAVE
Outdoor Temperature (in °F)
70 60 50 40 2030 0 -1010 -2
0
120
140
130
150
160
170
180
100
110
Water Temperature (in °F)
Custom Reset Ratio
Point1: System=120°F
Oudoor=60°F
Point2: System=170°F
Oudoor=0°F
Point1
Point2
Customized Reset Ratio
Max Target
Min Target
287'225&872))7(03(5$785(
$GMXVWDEOH2IIº)º&º)º&2Q 'HIDXOW)&
Button: MENU/Outdoor Cutoff LQ6HW3RLQW
 ,Q2XWGRRU5HVHWPRGH2XWGRRU&XWRIIZLOODOZD\VH[LVW+RZHYHULQ6HW3RLQWPRGH
if the outdoor sensor is installed, the Outdoor Cutoff screen will automatically appear
after the temperature Set Point has been selected.
- OUTDOOR CUTOFF -
70
F
[
]
BACK SAVE
 :KHQWKHRXWGRRUWHPSHUDWXUHULVHVWRWKH2XWGRRU&XWRIISOXVD)GLIIHUHQWLDOWKH%&3:ZLOOWXUQDOOERLOHUVRII7KH
6\VWHPDQG&RPE$LUUHOD\VWKDWZHUHHQHUJL]HGZLOOUHPDLQHQHUJL]HGIRUWKH5XQ2QGHOD\
 7KH2XWGRRU&XWRIIFDQEHVHWWR21RU2)),QWKH21SRVLWLRQWKH6\VWHP5HOD\ZLOOUXQUHJDUGOHVVRIWKH2XWGRRU
temperature and the burner stages will be active to hold the set point.
 ,QWKH2))SRVLWLRQWKH6\VWHP5HOD\ZLOODOZD\VEHRIIDQGDOOVWDJHVZLOOEHRIIDVZHOO
6(7%$&.
$GMXVWDEOH°)°&WR)& 'HIDXOW°)°&
Button: MENU/Setback
 7KH6HWEDFNIHDWXUHFDQEHXVHGWRSURYLGHWKH%&3:ZLWKDORZHU6HW3RLQWZKHQ
less load is required.
---- SETBACK -------
0 F
[ ]
BACK SAVE
 :KHQWKHRXWGRRUWHPSHUDWXUHIDOOVWRWKHDGMXVWDEOH2XWGRRU&XWRIIWHPSHUDWXUHWKH%&3:ZLOOFRQWURODQGVHTXHQFHWKH
boiler stages to hold the calculated temperature.
 :KHQWKHRXWGRRUWHPSHUDWXUHULVHVWRWKH2XWGRRU&XWRIISOXVD)GLIIHUHQWLDOWKH%&3:ZLOOWXUQDOOERLOHUVRII7KH
6\VWHP&RPEXVWLRQ$LU'DPSHUDQGDQ\RWKHU3XPSRUYDOYHUHOD\VWKDWZHUHHQHUJL]HGZLOOUHPDLQHQHUJL]HGIRUWKH5XQ2Q
GHOD\DQGWKHQGHHQHUJL]H
 ,QDGGLWLRQWKH2XWGRRU&XWRIIFDQEHVHWWR21RU2)),QWKH21RSWLRQWKH6\VWHP5HOD\ZLOOUXQUHJDUGOHVVRIWKH2XWGRRU
temperature and the burner stages will be active to hold the target water temperature.
 ,QWKH2))SRVLWLRQWKHV\VWHPSXPSZLOODOZD\VEHRIIDQGDOOVWDJHVZLOOEHRIIDVZHOO
'$<1,*+76&+('8/(6
Button: MENU/Setback/Day Schedules/Night Schedule
 7KH%&3:KDVWZROHYHOVRIKHDW7KH'D\OHYHOLVXVHGZKHQDEXLOGLQJLVRFFXSLHG
and people are active.
 7KH1LJKW6HWEDFNOHYHOLVXVHGZKHQDEXLOGLQJLVQRWRFFXSLHGRUZKHQSHRSOHDUH
sleeping. This setting reduces the calculated temperature by the Setback setting based
RQWKHSURYLGHGVFKHGXOH,IWKH'D\FDOFXODWHGZDWHUWHPSHUDWXUHZDVÛ)DQGWKH
6HWEDFNZDVÛ)WKH1LJKW6FKHGXOHZLOOUXQDWÛ)Û) Û)
-- DAY SCHEDULE ----
07:**Am
BACK SAVE
-- NIGHT SCHEDULE -
10:**Pm
BACK SAVE
 ,IWKH%RRVWIHDWXUHLVEHLQJXVHGLWXVHVWKH'D\6FKHGXOHDVD%RRVWHQGLQJSRLQW7KDWLVLIWKH'D\6FKHGXOHLVVHWWRVWDUW
DW$0WKH%RRVWZDVVHWWR)DQGWKH%RRVW3HULRGZDVPLQXWHVWKH%RRVWZLOOVWDUWDW$07KHQZKHQLQ
%RRVW%&3:ZLOOUDLVHWKHFDOFXODWHGZDWHUWHPSHUDWXUHE\WKH%RRVWDPRXQW8VLQJWKHSUHYLRXVH[DPSOHDW$0WKH
%&3:ZLOOUDLVHWKHFDOFXODWHGZDWHUWRÛ)Û)Û)XQWLO$0ZKHUHLWZLOOGURSEDFNWRWKHQRUPDOFDOFXODWHG
WHPSHUDWXUHRIÛ)
background
38
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
background
39
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
background
40
%&3:,QVWDOODWLRQDQG2SHUDWLRQ0DQXDO
63(&,),&$7,216
9ROWDJH,QSXW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9$&+]
3RZHU&RQVXPSWLRQ ..................................................9$0D[
2SHUDWLQJ7HPSHUDWXUH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20qF/-7qC to 120qF/49qC
2SHUDWLQJ+XPLGLW\ .................................................20% to 80%
'LPHQVLRQV ...................................................:[+[ô
:HLJKW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 pounds
%&3:63(&,),&$7,216
/HDG6WDJH5RWDWLRQ .......................Time ( 1 to 999 Hours (41 days)), Manual, First-On/First-Off
%&3:2XWSXWVDQG/('V . . . . . . . . . . 11 N.O. S.P.S.T (8 Stages, 1 System, 1 DHW Pump, 1 Combustion Air)
%&3:,QSXWV . . . . . . . . . . . . 1 Sys(Temp), 1 Outdoor, Return Temp, DHW Temp, Ext Setback/Shutdown, Prove
6WDJH0RGHV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auto, Standby, Off, On
6WDQGE\7LPH3,'RQO\ ............................................WRPLQXWHV
2XWSXW%XLOWLQ5HOD\5DWLQJV . . . . . . . . . . . . . . . . . 2 Amp inductive (Maximum of 1/4 HP) DW9$&+]
$GG2Q%&3;3DQHOV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . up two BCP-8X Panels using RS485
7HPSHUDWXUH'LVSOD\ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fahrenheit or Celsius.
'LVSOD\ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Graphical Alphanumeric (7 rows x 21 char. each)
7HPSHUDWXUH6HQVRU5DQJHV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . qF to 250qF
2XWGRRU&XWRII5DQJH . . . . . . . . . . . . . . . . . . . . . . . . . . . )&WR)&21DQG2))
6HW3RLQW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . )&WR)&
([WHUQDO6HW3RLQW .................. )&WR)& using 420MOD Interface (optional)
5HVHW5DWLR5DQJH2XWGRRU5HVHW2QO\ . . . . . . (WR2XWGRRU6\VWHP:DWHUDQG&XVWRP5HVHW5DWLR
2IIVHW$GMXVWPHQW2XWGRRU5HVHW2QO\ . . . . . . . . . . . . . . . . . . . . . .minus -40°F/-22°C to plus 40°F/22°C
0LQLPXP7DUJHW2XWGRRU5HVHW2QO\........................ 70qF/21qC to 170qF/77qC
0D[LPXP7DUJHW2XWGRRU5HVHW2QO\ . . . . . . . . . . . . . . . . . . . . . . . 90q)qC to 240q)&
5HDFWLRQ7LPH3,'RQO\ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 to 10 minutes
0LQLPXP5XQ7LPH3,'RQO\ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . WRPLQXWHV
3XUJH'HOD\3,'RQO\ ........................................... 0.0 to 10.0 minutes
/DVW6WDJH+ROG3,'RQO\ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . )&WR)&
7KURWWOH5DQJH266RQO\ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2°F/1°C to 20°F/11°C
'RPHVWLF+RW:DWHU3ULRULW\2SWLRQV . . . . . . Parallel Piping with Priority or without Priority and Primary Secondary
3XPS5XQ2Q ...................................................WRPLQXWHV
3XPS([HUFLVH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . <HVRU1R
6FKHGXOHV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Day and 1 Night (Setback) settings per day
1LJKW6HWEDFN ................................................0°F/0°C to 80°F/44°C
3RZHU%DFNXS ......../LWKLXPFRLQEDWWHU\GD\VPLQLPXP\HDUUHSODFHPHQW0DLQWDLQV&ORFNLQSRZHURXWDJHV
([WHUQDO,QSXWV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Shutdown Input, and Prove Input. (Dry Contacts Only)
6HDVRQ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Winter and Summer.
%&3;63(&,),&$7,216
([WHQVLRQ1XPEHULQJ ...........................................Toggle Switch A or B
/(' . . . 1 Power (Dual Color Green (A)/Red (B)), 1 Communication, 8 Stage Output relays (Dual Color Green (A)/Red (B))
6WDJH2XWSXWV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 N.O. S.P.S.T.
2XWSXW%XLOWLQ5HOD\5DWLQJV . . . . . . . . . . . . . . . . . 2 Amp inductive (Maximum of 1/4 HP) DW9$&+]
&RQQHFWLRQWR%&3:DQGDQRWKHU%&3; ................................ Two RS485
500 Blaine Street
Michigan City, Indiana 46360
219-879-6561
http://www.weil-mclain.com
HT #059072-00 A
Part Number 550-100-071/0408