Loading ...
Loading ...
Loading ...
ALL UNITS
WIRE SIZE
Use recommended wire size given in Table 1 and install on a single branch circuit. All wiring must
comply with local and national codes.
All units are designed to operate off ONE single
branch circuit only.
ELECTRICAL DATA
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal
injury or death and/or property damage. DO NOT use an extension cord.
POWER CONNECTION OPTIONS
The appropriate power cord accessory kit is determined by the voltage, and amperage of the branch
circuit. The unit does not come with a power cord (or hard wire kit). An accessory power cord kit must
be installed on the unit. If the unit is to be hard wired, an accessory hard wire kit must be ordered.
Be sure that your outlet matches the appropriate blade configuration of the plug and that it is
within reach of the service cord. All wiring, including installation of the receptacle, must be in
accordance with the NEC and local codes, ordinances and regulations. National codes require the
use of an arc fault or leakage current detection device on all 208/230V power cords. Be sure to
select the correct cord for your installation.
IMPORTANT: For 265V units, the power cord is only 18 inches long and must plug
into the accessory electrical 265V subbase.
WARNING
CAUTION
WARNING
WARNING
EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment
damage or improper operation. Using a 30 amp cord on 7000 or 9000 BtuH models could
result in damage to the unit. For these models, use 15 or 20 amp power cords only.
WARNING
CAUTION
WARNING
CAUTION
NOTE: Use copper conductors only.
76
Loading ...
Loading ...
Loading ...