NOTE
Refer to the Universal Condenser Manual for the Dip Switch instructions and settings for the condenser.
mrcool.com Page 16
Fig. 2.8 Fig. 2.9
Location of
Dip Switch on
Air Handler
Main Board
Unit Installation
Converting Unit From 3 Ton to 2 Ton
Follow these instructions during unit installation in order to enable a Universal Series 3 ton condenser
and air handler split system to operate at 2 ton capacity.
1. DO NOT attempt this conversion while the unit is powered on.
2. Locate the capacity dip switch on the air handler main board. The capacity dip switch is circled on
the photo below.
3. The default position of the capacity dip switch is 1, 2, & 4 ‘Up’ and 3 ‘Down’ on both the SA2 and
SA1 switches.
4. The default position of the capacity dip switch is 36k.
5. To activate the 24k capacity, flip capacity dip switch 2 & 4 on SA2 and SA1 to Down. Flip capacity
dip switch 3 on SA2 and SA1 to Up.
Air Handler Field Conversion
DEFAULT 3 TON 2 TON SETTING