Weil-McLain WTGO SERIES 4 OIL-FIRED WATER BOILER WTGO-5R Residential Boilers

Product's Documents

Below are documents related to this product, you can read online or download:
User Manual Other Documents
  • WTGO Series 4 Brochure - (English) Download
  • Carlin Burner Manual for WM GO Oil Boilers Series 3&4 - (English) Download
  • Riello Burner Manual for WM GO Oil Boilers Series 3&4 - (English) Download
  • Beckett AFG Burner Manual for WM GO Oil Boilers Series 3&4 - (English) Download
Installation Instruction
  • HydroStat 3250 Plus Temp Limit-LWCO Control Instructions - (English) Download
Energy Guide
  • WGO/WTGO ENERGY STAR Supplement - (English) Download
WTGO SERIES 4 OIL-FIRED WATER BOILER WTGO-5R photo

User Manual

This is the main product document for model WTGO SERIES 4 OIL-FIRED WATER BOILER WTGO-5R.

The file format is pdf, 44 pages, you can download this manual here .

background
Part number 550-142-332/0421
• Installation
• Startup
• Maintenance
• Parts
Boiler Manual
Series 4
Oil-Fired Water Boilers
This manual must only be used by a qualied heating installer/service technician. BEFORE installing, read
all instructions in this manual and all other information shipped with the boiler. Perform steps in the order
given. Failure to comply could result in severe personal injury, death or substantial property damage.
background
Part number 550-142-332/0421
2
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
HOMEOWNER and SERVICE TECHNICIAN — read and follow completely.
The following defined terms are used throughout this manual to bring attention to the presence of hazards
of various risk levels or to important information concerning the life of the product.
Indicates presence of hazards that will cause severe personal injury,
death or substantial property damage.
Indicates presence of hazards that can cause severe personal injury,
death or substantial property damage.
Indicates presence of hazards that will or can cause minor personal
injury or property damage.
Indicates special instructions on installation, operation or
maintenance that are important but not related to personal injury
or property damage.
Hazard definitions
Homeowner —
Read and follow all information on pages 1 through 7 ONLY.
Service technician —
Read and follow ALL information in the entire manual.
Failure to follow all instructions in proper order can cause severe personal injury, death or
substantial property damage.
Using this manual
When calling or writing about the boiler
Please have boiler model number and series from boiler rating label and Consumer Protection (CP)
number(s) from boiler jacket, burner and controls. On page 30 of this manual is space to list CP number(s).
Packaged boilers: Available only in sizes 3 through 6, are factory assembled, completed with block, collec-
tor hood, jacket, controls and trim. Burner is ordered and shipped separately.
Semi-packaged boilers: Available only in sizes 3 through 6, are shipped with block assembled with collector
hood and jacket installed. Control, trim, and burner are ordered and shipped separately
for field assembly.
Knocked-down boilers: Available in sizes 3 through 9, are shipped with block assembled only. All other compo-
nents are ordered and shipped separately for field assembly.
background
Part number 550-142-332/0421
3
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
HOMEOWNER and SERVICE TECHNICIAN — read and follow completely.
Contents
Using this manual . . . . . . . . . . . . . . . . 2
Homeowner. . . . . . . . . . . . . . . . . . 2
Service technicians . . . . . . . . . . . . . . . . . . .2
When calling or writing about the boiler . . . . . . . .2
Packaged, Semi-packaged and Knocked-down boilers 2
Hazard definitions . . . . . . . . . . . . . . . . 2
Contents . . . . . . . . . . . . . . . . . . . . 3
Please read before proceeding . . . . . . . . . 4
Homeowner. . . . . . . . . . . . . . . . . . 4
Service technicians . . . . . . . . . . . . . . . . . . .4
Tips for water systems — . . . . . . . . . . . . . . .4
Saltwater Damage . . . . . . . . . . . . . . . . . . .4
Electrical Damage . . . . . . . . . . . . . . . . . . .4
Frozen Water Damage Hazard . . . . . . . . . . . . .5
Routine maintenance schedule . . . . . . . . . 5
Beginning each heating season . . . . . . . . . . . .5
Daily during heating season . . . . . . . . . . . . . .5
Weekly during heating season . . . . . . . . . . . . .5
End of heating season . . . . . . . . . . . . . . . . .5
Boiler shutdown . . . . . . . . . . . . . . . . . . . .5
Operation . . . . . . . . . . . . . . . . . . . . 6
WTGO (see Figure 1) . . . . . . . . . . . . . . . . . .6
Troubleshooting . . . . . . . . . . . . . . . . . 7
Before installing boiler . . . . . . . . . . . . . 8
Installations must comply with . . . . . . . . . . . . .8
Before selecting boiler location . . . . . . . . . . . .8
Provide clearances around boiler (see Figure 2) . . .8
Provide air for combustion and ventilation . . . . . .9
Lay a foundation, if needed . . . . . . . . . . . . . .9
Install boiler — Packaged boilers only. . . . . .10
Place boiler . . . . . . . . . . . . . . . . . . . . . .10
Perform hydrostatic pressure test . . . . . . . . . .10
Install boiler - Semi-packaged & Knocked-down boilers 12
Place boiler . . . . . . . . . . . . . . . . . . . . . .12
Tankless heater, if used. . . . . . . . . . . . . . . . 12
Perform hydrostatic pressure test . . . . . . . . . .14
Install jacket (Knocked-down boilers only) . . . . . 14
Install boiler controls . . . . . . . . . . . . . . . . .14
Install burner — all boilers . . . . . . . . . . .15
Install burner (also refer to instructions
packed with burner) . . . . . . . . . . . . . . . . . 15
Connect breeching . . . . . . . . . . . . . . .16
General chimney requirements. . . . . . . . . . . . 16
Connect breeching . . . . . . . . . . . . . . . . . .16
Connect water piping . . . . . . . . . . . . . .18
General piping information . . . . . . . . . . . . . . 18
Install piping: . . . . . . . . . . . . . . . . . . . . .18
DIAPHRAGM expansion tank (Figure 9) . . . . . . .18
CLOSED expansion tank (Figure 10) . . . . . . . . . 18
To connect WTGO boilers to
indirect-fired water heaters. . . . . . . . . . . . . . 18
Piping MULTIPLE ZONES . . . . . . . . . . . . . . 20
Piping for systems requiring
temperatures below 140°F . . . . . . . . . . . . . .21
Use with refrigeration systems . . . . . . . . . . . . 22
Connect tankless heater piping . . . . . . . . .23
Connect wiring . . . . . . . . . . . . . . . . .24
General wiring requirements . . . . . . . . . . . . .24
Thermostat wiring . . . . . . . . . . . . . . . . . . 24
Zone valve wiring . . . . . . . . . . . . . . . . . . . 24
General wiring . . . . . . . . . . . . . . . . . . . . 24
Burner wiring . . . . . . . . . . . . . . . . . . . . .24
High temperature limit . . . . . . . . . . . . . . . . 24
3-Wire zone valve applications. . . . . . . . . . . . 24
Blocked vent shutoff switch . . . . . . . . . . . . . 27
Connect wiring - vent damper . . . . . . . . . .28
Connect oil piping . . . . . . . . . . . . . . . .28
General oil piping requirements . . . . . . . . . . .28
Start-up . . . . . . . . . . . . . . . . . . . . .29
Fill the system . . . . . . . . . . . . . . . . . . . . 29
When using antifreeze . . . . . . . . . . . . . . . . 29
To place in operation . . . . . . . . . . . . . . . . .29
Burner adjustments. . . . . . . . . . . . . . . . . . 29
Check-out procedure . . . . . . . . . . . . . .30
Check off Steps as completed . . . . . . . . . . . . 30
Installation and service certificate . . . . . . . . . .30
Annual service check list . . . . . . . . . . . .31
Controls requiring annual service . . . . . . . . . . 31
Detailed service procedures. . . . . . . . . . .32
Cleaning boiler flue ways. . . . . . . . . . . . . . . 32
General description of control operation . . . . . . 32
Handling ceramic fiber and fiberglass materials 33
Close clearance installation . . . . . . . . . . .34
Close clearance installation . . . . . . . . . . . . . 34
Replacement parts . . . . . . . . . . . . . . .36
Dimensions . . . . . . . . . . . . . . . . . . .41
Ratings . . . . . . . . . . . . . . . . . . . . .42
background
Part number 550-142-332/0421
4
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
HOMEOWNER and SERVICE TECHNICIAN — read and follow completely.
Please read before proceeding
Follow instructions below to prevent severe personal injury,
death or substantial property damage:
• To avoid electric shock, disconnect electrical supply to burner service
switch and additional external switches before performing service.
• To avoid severe burns, allow boiler to cool before performing service.
• Do not block flow of combustion or ventilation air to boiler.
• Boiler must be connected to a flue with sufficient draft at all times to
assure proper operation.
• Do not use this boiler if any part has been under water. Electrical and
mechanical failures may cause electric shock and fire risks. Immediately
call a qualified service technician to inspect chimney or vent, boiler
and burner. Have the boiler flue ways cleaned and have the following
replaced:
• all electrical and mechanical controls
• electrical wiring
• oil burner and controls
• insulation and chamber lining
Tips for water systems —
• Check boiler and system piping for leaks. Continual makeup water
will reduce boiler life. Minerals can build up in sections, reducing heat
transfer and causing cast iron to overheat, resulting in section failure.
Failure to maintain recommended pH and repair leaks can
cause section iron corrosion, leading to section failure and
leaks. Do not use petroleum-based sealing or stop-leak com-
pounds in boiler systems. Damage to system components
can result, causing property damage.
• Boiler water pH 7.0 to 8.5 is recommended. For pH conditions outside
7.0 to 8.5 range or unusually hard water areas (above 7 grains hard-
ness), consult local water treatment company.
• When using antifreeze:
Use antifreeze especially made for hydronic systems. Inhibited
propylene glycol is recommended.
Do not use automotive, ethylene glycol, undiluted or
petroleum-based antifreeze. Severe personal injury, death
or substantial property damage can result.
50% solution provides protection to about –30°F.
Local codes may require back-flow preventer or actual disconnect
from city water supply.
Determine quantity according to system water content. Boiler water
content is listed on back cover of Boiler Manual.
Percent of solution will affect sizing of heat distribution units,
circulator and expansion tank.
Follow antifreeze manufacturer’s instructions.
Do not add cold water to hot boiler. Thermal shock can cause
sections to crack.
Saltwater Damage The exposure of boiler components to saltwater
can have both immediate and long-term effects. While the immediate
effects of saltwater damage are similar to those of freshwater (shorting
out of electrical components, washing out of critical lubricants, etc.), the
salt and other contaminants left behind can lead to longer term issues
after the water is gone due to the conductive and corrosive nature of
the salt residue. Therefore, Weil-McLain equipment contaminated with
saltwater or polluted water will no longer be covered under warranty
and should be replaced.
Electrical Damage — If any electrical component or wiring came
into contact with water, or was suspected to have come into contact with
water, replace the boiler with a new Weil-McLain boiler.
continued - top of next page
Homeowner —
• For homeowner or person responsible for
simple start-up and routine maintenance of
the system
• Instructions on pages 1 through page 7 must
be followed to assure proper operation of
your boiler. See page 7 for a list of common
problems and possible corrections. In addi-
tion, it is your responsibility to:
• Have boiler and burner installed by a
qualified installer.
• Have boiler and burner serviced annually
by a qualified service technician.
• Review and understand start-up and
routine maintenance procedures with
qualified service technician.
• Perform routine maintenance as de-
scribed on page 5.
Service technician —
• For a qualified service technician who has
the necessary equipment to check the boiler
and system performance, and is responsible
for start-up and service of boiler and system.
• All instructions in this manual must be
followed to assure proper operation of this
boiler.
• Annually service boiler and burner to assure
proper operation. See page 31 for service
record.
• Review and explain start-up and routine
maintenance procedures with homeowner.
Follow instructions below to pre-
vent severe personal injury, death
or substantial property damage:
• Do not use crankcase drainings or any oil
containing gasoline. See burner manual for
proper fuel oil.
• Do not attempt to start burner when excess
oil has accumulated in combustion cham-
ber, when unit is full of vapor, or when
combustion chamber is very hot.
• Do not start burner unless collector hood,
flue cap, jacket cap, breeching and burner
mounting door are secured in place.
• Never burn garbage or paper in the boiler.
Never leave combustible material around
boiler.
• DO NOT TAMPER WITH UNIT OR CON-
TROLS. Always follow specific instructions
when starting up boiler or performing rou-
tine maintenance or service.
background
Part number 550-142-332/0421
5
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
HOMEOWNER and SERVICE TECHNICIAN — read and follow completely.
Routine maintenance schedule
Beginning
each heating season
Call a qualified service technician to perform annual service.
Daily
during heating season
Check that boiler area is free from combustible materials, gasoline
and other flammable vapors and liquids.
Weekly
during heating season
Check for and remove any obstructions to flow of combustion or
ventilation air to boiler.
Check that breeching is attached between boiler and chimney. If
breeching is loose or damaged, immediately turn off switch on
boiler and call service technician to repair.
Check for oil leaks in oil piping and around burner. If found, im-
mediately call qualified service technician to correct situation.
Check for water leaks in boiler and piping; also check for leaks
around tankless heater plate, if installed. If found, immediately call
service technician to repair.
End
of heating season
If tankless heater is installed, boiler will continue to operate. Check
for the following:
• All daily and weekly instructions listed on this page must be fol-
lowed.
• Burner motor may have to be oiled. Some motors are permanently
lubricated and do not need additional oil. Check for oiling instruc-
tions on burner or motor.
Boiler
shutdown
Do not drain boiler unless exposure to freezing temperatures will
occur.
Always keep manual fuel supply shut off if burner is shut down for
an extended period of time.
• Turn off switch at boiler and any external switch to boiler.
• Close fuel valves.
• Turn off water feed valve.
• Cover burner to protect from dust and dampness.
Frozen Water Damage Hazard
Residences or buildings that are unattended in severely cold weather, boiler system components failures, power outages, or
other electrical system failures could result in frozen plumbing and water damage in a matter of hours. For your protection, take
preventative actions such as having a security system installed that operates during power outages, senses low temperature, and
initiates an effective action. Consult with your boiler contractor or a home security agency.
background
Part number 550-142-332/0421
6
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
HOMEOWNER and SERVICE TECHNICIAN — read and follow completely.
Operation
WTGO (see Figure 1).
1. If burner does not fire, check for:
• Service switch on control or additional switches turned
off.
• Fuses or breaker switch tripped.
• Thermostat set below room temperature.
• Fuel valves turned off.
• Not enough oil in tank to supply burner.
Figure 1 WTGO Boilers
2. Correct problems found in Step #1. If burner does not fire,
press reset button on burner primary control only once.
Repeated presses will deposit oil in combustion chamber.
Burner must never be fired when oil is in combus-
tion chamber. Immediately call qualified service
technician.
3. If burner still does not fire, call qualified service technician.
1 Burner disconnect plug
2 Water relief valve
3 Temperature-pressure gauge
4 Circulator
5 Combination limit control,
tankless heater control and
low water cut-off (located in
tankless heater plate)
6 Reset button on burner
primary control
7 Burner primary control
background
Part number 550-142-332/0421
7
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
HOMEOWNER and SERVICE TECHNICIAN — read and follow completely.
Troubleshooting
Homeowners — The problems and corrections below represent common situations that can occur. There may be
others not listed below. It is important always to contact a qualified service technician if you have any questions
about the operation of your boiler or system.
Common Problems Common Causes Possible Corrections
Rapid cycling — burner
turns on and off
frequently.
Thermostat installed where
drafts or heat affect reading.
Locate thermostat on inner wall away from heat sources or cool drafts.
Heat anticipator in thermo-
stat adjusted incorrectly.
Adjust heat anticipator to match current draw. Refer to boiler wiring
diagram.
Incorrect limit setting. Have qualified service technician increase limit setting to decrease
cycling. Maximum setting 220° F.
Need to frequently add
makeup water.
Leaks in boiler or piping. Have qualified service technician repair leaks at once to avoid constant
use of makeup water.
Popping or percolating
noise heard in boiler.
Mineral deposits in sections
due to constant use of make-
up water, or incorrect pH.
Have qualified service technician de-lime boiler, repair leaks at once
to avoid constant use of makeup water and check pH (between 7.0
and 8.5).
Black water condition.
Oxygen corrosion due to
leaks in piping. Improper pH.
Have qualified service technician repair leaks at once to avoid constant
use of makeup water and check pH (between 7.0 and 8.5).
Frequent release of water
through relief valve.
Expansion tank sized too
small or water-logged.
Have qualified service technician check expansion tank operation.
Metal flakes found in flue
way.
Contaminated combustion
air supply in flue ways.
Remove sources of hydrocarbons in or near boiler area. (Bleaches,
cleaners, chemicals, sprays, fabric softeners, paint remover, etc.)
Condensation of combustion
gases.
Have qualified service technician check burner nozzle and oil pump
pressure for proper firing rate and check/adjust combustion settings
with an analyzer.
Some radiators or
baseboard units do not
heat or are noisy.
Air in system. Bleed air from system through air vents in radiators or baseboard units.
Low system pressure. Have qualified service technician check for leaks in boiler or piping
at once.
High limit set too low. Have qualified service technician adjust limit to higher setting.
Domestic water from
tankless heater is hot
then suddenly turns cold.
OR
Domestic water from
tankless heater is always
lukewarm.
Mineral deposits insulate
internal waterways of heater.
Have qualified service technician de-lime or replace coil.
Boiler stop-leak compound
has been added to boiler wa-
ter and is insulating outside
of coil.
Have qualified service technician remove and clean coil and drain,
and flush boiler to remove stop-leak.
Incorrect mixing valve setting
for tankless heater.
Have qualified service technician adjust mixing valve setting.
Domestic flow rate too high. Have qualified service technician install flow check valve set to rating
of tankless heater.
Incorrect setting on tankless
heater control.
Have qualified service technician raise tankless control setting. Adjust
differential on tankless control to lower setting.
background
Part number 550-142-332/0421
8
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Before installing boiler
Top View
Walls
24"
A
A
A
Wall
Left side
Ceiling
Wall
B
B
B
24"
Floor
Installations must comply with
United States
• State and local plumbing, heating and electrical codes.
• National codes where applicable.
• Standard for Controls and Safety Devices for Automatically
Fired Boilers, ANSI/ASME CSD-1, – latest edition, when re-
quired.
• National Electrical Code, ANSI/NFPA 70, – latest edition
and any additional national, state or local codes.
Canada
• Canadian Standards Association, CSA B139, Installation Code for
Oil-Burning Equipment – latest edition.
• CSA C22.1 Canadian Electrical Code Part One – latest edition.
• Applicable local or provincial codes.
Before selecting boiler location
• Check for nearby connections to:
• System water piping.
• Chimney. See page 16. Boiler can be top or back vented.
• Combustion and ventilation air supply. See page 9.
• Oil supply. See page 28 for oil line routing.
• Electrical power.
• Check area around boiler. Remove any combustible
materials, gasoline and other flammable liquids.
Provide clearances around boiler
(see Figure 2)
Jacket cap must be in place on boiler to
avoid requiring an 9" minimum clearance
from back or top of boiler to combustible
material.
• MINIMUM clearances from vent pipe to combustible
material:
• 6 inches Type “L double-wall vent*
• 9 inches Single-wall vent
Flue pipe clearances must take precedence
over jacket clearances.
• Recommended SERVICE clearances:
• 24 inches Front and top
• 6 inches Left side, back and right side
• 12 inches Right side for burner door swing
radius.
• Special close clearances (alcove, closet, under counters,
etc.) — see Close Clearances, page 34.
Homeowner — STOP! The procedures and information on this and following pages are intended only for a
qualified service technician who has the necessary equipment to inspect and adjust boiler and burner. A homeowner
should never attempt these procedures. The service technician must also read pages 1 through 7 before proceeding.
Failure to keep boiler area clear and free of combustible materials, gasoline and other flammable liquids and vapors
can result in severe personal injury, death or substantial property damage.
Figure 2 Recommended service clearances
A Provide 6" minimum clearance for service, provide 12" mini-
mum clearance for burner door swing.
B Minimum clearance from vent pipe to combustible material:
6" for type “L double-wall vent, 9" for single-wall vent.
background
Part number 550-142-332/0421
9
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Before installing boiler (continued)
Boiler
Size
Length
inches
Width
inches
Minimum
height
inches
WTGO-3L
17
22 2
WTGO-3
17
22 2
WTGO-4
20
22 2
WTGO-5
20
22 2
WTGO-6
23
22 2
WTGO-7
26
22 2
WTGO-8
29
22 2
WTGO-9
32
22 2
Table 1 Boiler foundation sizes
Provide air for combustion and ventilation
Do not install exhaust fan in boiler room.
Adequate combustion and ventilation air:
• Assures proper combustion.
• Reduces risk of severe personal injury or death from possible flue gas
leakage and carbon monoxide emissions.
Older buildings with single-pane windows, minimal weather-stripping and
no vapor barrier often provide enough natural infiltration and ventilation
without dedicated openings.
New construction or remodeled buildings are most often built tighter.
Windows and doors are weather-stripped, vapor barriers are used and
openings in walls are caulked. As a result, such tight construction is unlikely
to allow proper natural air infiltration and ventilation.
Follow state, provincial or local codes when sizing adequate combustion and
ventilation air openings. In absence of codes, use the following guidelines
when boiler is in a confined room (defined by NFPA 31 as less than 7200
cubic feet per 1 GPH input of all appliances in area. A room 8 ft. high x
33.5 ft. x 33.5 ft. is 7200 cu. ft.):
• Provide two permanent openings — one within 12 inches of ceiling,
one within 12 inches of floor. Minimum height or length dimension
of each rectangular opening should be at least 3 inches.
• When inside air is used — each opening must freely connect with areas
having adequate infiltration from outside. Each opening should be at
least 140 sq. in. per 1 GPH input (1 sq. in. per 1000 Btu input) of all
fuel-burning appliances plus requirements for any equipment that can
pull air from room (including clothes dryer and fireplace).
• When outside air is used — connect each opening directly or by ducts
to the outdoors or to crawl or attic space that freely connects with
outdoors. Size per below:
• Through outside wall or vertical ducts — at least 35 sq. in. per
1 GPH input (1 sq. in. per 4000 Btu input) of all fuel-burning
appliances plus requirements for any equipment that can pull air
from room (including clothes dryer and fireplace).
• Through horizontal ducts — at least 70 sq. in. per 1 GPH boiler
input (1 sq. in. per 2000 Btu input) of all fuel-burning appliances
plus requirements for any equipment that can pull air from room
(including clothes dryer and fireplace).
• Where ducts are used, they should have same cross-sectional area as
free area of openings to which they connect. Compensate for louver,
grille or screen blockage when calculating free air openings. Refer
to their manufacturer’s instructions for details. If unknown, use:
• Wood louvers, which provide 20-25% free air.
• Metal louvers or grilles, which provide 60-75% free air.
Lock louvers in open position or interlock with equipment to prove open
before boiler operation.
Lay a foundation, if needed
Boiler may be installed on non-carpeted combustible
flooring.
For residential garage installation, install boiler so
burner is at least 18 inches above floor to avoid contact
with gasoline fumes.
A level concrete or masonry foundation is required
when:
• Floor could possibly become flooded.
• Non-level conditions exist.
Solid concrete blocks can be used to create a pad.
Installation instructions:
Packaged boiler Continued on page 10
Semi-packaged and Knocked-down boiler — Continued on page 12
background
Part number 550-142-332/0421
10
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Install boiler — Packaged boilers only
Place boiler
1. Remove circulator strapped to pallet.
Circulator will be damaged if not removed before
boiler is lifted from pallet.
2. Remove boiler from pallet.
Do not drop boiler or bump jacket on floor or
pallet. Damage to boiler can result.
Smaller sized boilers may be top heavy. Use caution
when handling to avoid minor personal injury or
property damage.
3. Boiler is shipped for back flue outlet. To change to top flue
outlet (see Figure 3, page 11):
a. Remove the jacket cap and the 8.00” diameter piece of
insulation that covers the vent opening from the top
jacket panel.
b. Loosen two (2) screws holding flue cap strap to col-
lector hood. Remove strap and flue cap from opening.
Re-tighten screws.
c. Check rope placement inside flue cap.
(Read
under Step #6).
d. Loosen two (2) screws on back flue outlet. Set flue cap on
outlet. Install strap by engaging slots in screws. Tighten
screws. Make sure cap is securely installed.
e. Place the jacket cap insulation disc in the back opening
of the boiler covering the flue cap.
f. Snap jacket cap in back outlet opening.
Jacket cap and insulation disc must be in place on
boiler to avoid requiring an 18” minimum clear-
ance from back of boiler to combustible material.
4. Check level. Shim legs, if needed.
5. Check for secure placement of insulation on target wall,
chamber floor and burner door.
6. Visually check:
a. Flue collector hood seal.
b. Burner mounting door seal.
Obtain gas-tight seal to prevent possible flue gas
leakage and carbon monoxide emissions, which
can lead to severe personal injury or death.
Perform hydrostatic pressure test
1. Remove relief valve installed in boiler.
2. Install air vent in “N” tapping on top boiler.
3. Plug supply and return tappings.
4. Drain valve is already factory-installed.
5. Fill boiler. Vent all air. Pressure test boiler at 1½ times work-
ing pressure.
Do not leave boiler unattended. Cold water fill can
expand and damage cast iron, resulting in severe
personal injury, death or substantial property dam-
age.
6. Check for maintained gauge pressure for more than 10 min-
utes. Visually check for leaks if gauge pressure drops.
7. Drain boiler. Repair leaks if found.
Do not use petroleum-based sealing compounds
to repair leaks. Damage to system components can
result, causing property damage.
8. Retest boiler after repairing leaks.
9. Remove air vent and plugs. Reinstall relief valve.
background
Part number 550-142-332/0421
11
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Install boiler — Packaged boilers only (continued)
Figure 3 Change from back flue outlet to top flue outlet (optional)
Instructions for Packaged boilers are continued on page 15.
background
Part number 550-142-332/0421
12
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Install boiler –
Semi-packaged and Knocked-down boilers only
Fiberglass wool and ceramic fiber materials are
possible cancer hazards. See warning on page 33.
Place boiler
1. Semi-packaged WTGO-3 through 6 — position on site.
Smaller sized boilers may be top heavy. Use caution
when handling to avoid minor personal injury or
property damage.
a. Boiler is shipped for back flue outlet. To change to top
flue outlet (see Figure 4, page 13):
• Remove the jacket cap and the 8.00” diameter piece
of insulation that covers the vent opening from the
top jacket panel.
• Loosen two (2) screws holding flue cap strap to col-
lector hood. Remove strap and flue cap from opening.
Re-tighten screws.
• Check rope placement inside flue cap. (Read
under Step #3.)
• Loosen two (2) screws on back flue outlet. Set flue
cap on outlet. Install strap by engaging slots in screws.
Tighten screws. Make sure cap is securely installed.
• Place the jacket cap insulation disc in the back opening
of the boiler covering the flue cap.
• Snap jacket cap in back outlet opening.
Jacket cap and insulation disc must be in place on
boiler to avoid requiring an 18” minimum clearance
from back of boiler to combustible material.
2. Knocked-down WTGO-7, 8 & 9 — split the assembled block
for easier handling (see Figure 4, page 13):
a. Open burner mounting door and, using utility knife, slit
floor insulation at joint to be separated.
b. Remove 5½" draw rod and the longest draw rod from each
side. Pull block apart. Save draw rods, nuts, washers and
sealing rings for reassembly.
c. Move divided block to location.
d. Clean port openings with clean rag.
Do not use petroleum-based compounds to clean
openings. Damage to system components can result,
causing property damage.
e. Place rings in port openings. If ring slips out of groove,
stretch ring gently for several seconds, then place in groove.
f. Position sections so aligning lugs fit into sockets of next
section. Make sure sealing rope is in good condition and
in position.
g. Oil threads on draw rods. Install washer and nut on end
to be tightened. Use nut only on other end.
h. With wrench at washer/nut end, uniformly tighten nuts
starting with 5½" rod at large port, 5½" rod at small port,
bottom long rod and finally top long rod.
i. Torque on both 5½" rods and bottom long rod should
be 50–60 ft-lbs; long top rod should be 20–25 ft-lbs. Do
not back-off nuts.
j. Metal-to-metal contact should be made around port
openings. If gap does exist, it should be less than .020”.
Check with feeler gauge.
k. If gap around port openings exceeds .020”, check for dirt
on port openings, sockets or misaligned lugs. If correc-
tions are made and gap still exists, contact our Technical
Services group for assistance before continuing instal-
lation.
3. Knocked-down WTGO-3 through 9 — install flue collector
hood (see Figure 4, page 13):
Obtain gas-tight seal to prevent possible flue gas
leakage and carbon monoxide emissions, leading
to severe personal injury or death.
a. Thread Tinnerman clip on screw so that clip fits snugly
in notch of hold-down lug. Screw must not turn.
b. Remove paper on sealing rope. Starting at back section
near flue collar, position sealing rope around top of block
with adhesive side to sections. Do not stretch rope. Make
sure rope ends meet. Trim excess rope.
c. Position flue collector hood on top of boiler sections
and over screws and clips as shown in Figure 4, page 13.
d. Install washers and nuts. Tighten nuts until collector hood
makes contact with Tinnerman clip.
e. Back flue outlet boiler — Position flue cap and strap over
opening in flue collector hood. Make sure rope in cap is
in place and in good condition. Tighten strap to hood
with screws provided.
Top flue outlet boiler — Position flue cap and strap over
opening in back section.
f. Make sure rope in cap is in place and in good condition.
Tighten strap to boiler with screws provided in section.
Install remaining screws in holes in flue collector hood.
Tankless heater, if used
1. Remove tankless heater cover plate and gasket.
2. Install new gasket and tankless heater over studs around open-
ing. Secure with 3/8" nuts, tightening until metal-to-metal
contact is made (20–25 ft-lbs).
background
Part number 550-142-332/0421
13
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Sealing
rope in
groove
inside cap
Flue
cap
Flue cap
strap
Flue
collector
hood
Sealing
rope with
adhesive
tape
Separate
block here
for easier
handling
Nut
Washer
Tinnerman
clip
Screw
Hold-down
lug
Install boiler –
Semi-packaged and Knocked-down boilers only (continued)
Figure 4 Change from back flue outlet to top flue outlet (optional)
background
Part number 550-142-332/0421
14
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Location Size Function
B1 1½" Return piping
B2 1½" Alternate return piping for
WTGO
C 1½" Supply piping
E3 ¼" Pressure-temperature
gauge
H ¾" Drain valve
L ¾" High limit control
(in tankless heater cover
plate)
N ½" Air vent or expansion tank
piping
R1 ¾" Relief valve
Front section
E3
R1
C
L
B1
H
N
B2
Back section
Install boiler –
Semi-packaged and Knocked-down boilers only (continued)
Perform hydrostatic pressure test
1. Refer to Control Tapping Table 2 and Figure 5 to install:
a. Boiler drain.
b. Water pressure gauge (test only). Be sure gauge can
handle test pressure.
c. Air vent in upper “N” tapping.
d. Plugs in remaining tappings.
2. Fill boiler. Vent all air. Pressure test boiler at 1½ times work-
ing pressure. For boilers split and reassembled, test between
75 and 85 psig.
Do not leave boiler unattended. Cold water fill
could expand and damage cast iron, resulting in
severe personal injury, death or substantial prop-
erty damage.
3. Check for maintained gauge pressure for more than 10 min-
utes. Visually check for leaks if gauge pressure drops.
4. Drain boiler. Repair leaks if found.
Do not use petroleum-based compounds to repair
leaks. Damage to system components can result,
causing property damage.
5. Re-test boiler after repairing leaks.
6. Remove pressure gauge, air vent and plugs from tappings
used for controls.
7. Visually check:
a. Sealing rope placement
b. Metal-to-metal contact around port openings.
c. Flue collector hood seal.
d. Burner mounting door seal.
Obtain gas-tight seal to prevent possible flue gas
leakage and carbon monoxide emissions, which
can lead to severe personal injury or death.
Install jacket
(required on sizes 7 through 9 only)
Before installing jacket, remove burner mounting door. See jacket
instructions for details.
Install boiler controls
See Control tapping (Table 2), Figure 5 and Figure 6 to install
controls.
1. Install tankless heater control if tankless heater is used. If
not furnished, use operating control with maximum 10°F
differential.
2. Install limit control. If not furnished, use high limit with
maximum 220°F setting.
3. Affix Consumer Protection (CP) number label(s) on jacket
front panel.
Table 2 Control tappings Figure 5 Control tapping locations
background
Part number 550-142-332/0421
15
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Relief
valve
Water
pressure-temperature
gauge
Combination
Limit control
and low water
cut-off
Drain valve
Circulator
Figure 6 Water boiler controls
Install burner
(also refer to instructions packed with burner)
Use only burners specified for use on Weil-
McLain oil boilers. Contact individual
burner manufacturers for proper burner
selections.
For burners with OEM welded flanges:
1. Secure mounting flange and gasket to burner
mounting door. Use three (3) bolts provided.
2. Open door to verify secure placement of insulation
on target wall, chamber floor and burner mounting
door.
3. Securely close door and tighten nut.
For burners without OEM welded flanges:
1. Secure universal mounting flange and gasket to burner mounting
door. Use three (3) bolts provided.
2. Secure burner on flange with three (3) bolts.
3. Position burner so end of air tube is level to 1½-degree tilt down
toward chamber. Open door to verify burner position. End of air
tube should be flush to ¼" recessed from inside wall of burner door
refractory. Check for secure placement of insulation on target wall,
chamber floor and burner mounting door.
4. Securely close door and tighten nut.
Install burner — all boilers
background
Part number 550-142-332/0421
16
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Connect breeching
Table 3 Minimum chimney sizes
Boiler
Size
Minimum
breeching
diameter
(Note 3)
Minimum
AHRI
chimney size
Minimum
chimney
height
Rect. Round
WTGO-3
5"
8" x 8"
(Note 1) 6" 15'
WTGO-4
6"
WTGO-5
6"
8" x 8"
(Note 1) 7" 15'
WTGO-6
7"
WTGO-7
WTGO-8
7"
8" x 12"
(Note 2)
7" 20'
WTGO-9
NOTE:
1. 6¾" x 6¾" inside liner.
2. 6½" x 10½" inside liner.
3. Flue collar on boiler is 7" diameter
General chimney requirements
• Designed for natural draft firing. Connect boiler to vertical chim-
ney.
Insufficient draft can cause flue gas leakage and carbon
monoxide emissions, which will lead to severe personal
injury or death.
• Use vent material approved by local codes for oil-fired burners. In
their absence, refer to:
• NFPA 31 latest edition, Installation of Oil-Burning Equipment.
• NFPA 211 latest edition, Standard for Chimneys, Fireplaces,
Vents and Solid Fuel Burning Appliances.
• In Canada, refer to CSA B139, Installation Code for Oil-
Burning Equipment – latest edition.
• NFPA 211 requires chimney to be lined before connected to boiler.
Inspect existing chimney before installing new boiler.
Failure to do any of the following will result in severe
personal injury or death:
• Clean chimney, including removal of blockage.
• Repair or replace damaged pipe or liner.
• Repair mortar and joints.
To prevent downdrafts, extend chimney at least 3 feet above highest
point where it passes through roof and 2 feet higher than any portion
of building within 10 feet. Increase chimney cross-sectional area and
height at least 4% per 1,000 feet above sea level.
• Minimum clearances from vent pipe to combustible material:
Type “L double-wall vent 6 inches
Single-wall vent 9 inches
• Minimum chimney sizes should be used.
Oversized chimneys, outside masonry chimneys and/or
de-rated inputs can result in condensation in chimney.
Connect breeching
Long horizontal breechings, excessive numbers of tees
and elbows or other obstructions restricting combustion
gas flow can result in possibility of condensation, flue gas
leakage and carbon monoxide emissions, which can lead
to severe personal injury or death.
1. Install two (2) flue pipe brackets.
2. Connect full-sized breeching when possible. See Minimum Chim-
ney Size Table.
• Back outlet — see Figures 7 and 9, page 17.
• Top outlet — see Figures 8 and 10, page 17.
Connection must be made above bottom of chimney to avoid blockage.
Breeching must not enter chimney far enough to cause obstruction.
Use thimble or slip joint where breeching enters chimney to allow
removal for cleaning.
3. When burner and boiler are properly installed, draft
over fire will be approximately -0.01" to -0.02" W.C.
Install barometric control in breeching, per control
manufacturer’s instructions, when excess draft needs
to be relieved or to comply with applicable codes and
regulations. Use draft gauge to adjust proper opening.
4. An induced draft fan for the chimney may be neces-
sary if:
• Excessive resistance to flow of combustion gases
can be expected.
• Cross-sectional area of chimney is smaller than
minimum recommended.
• Chimney height is less than recommended.
Seal all vent joints. Interlock burner with fan
operation.
5. Boiler models ending in “D”, such as WTGO-3D, require
the installation of the Field Controls OVD-7 automatic
damper kit, Weil-McLain part number 381-800-515.
Refer to Figures 7 and 8, page 17.
background
Part number 550-142-332/0421
17
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Connect breeching (continued)
Figure 7 Back Outlet Breeching Vent Damper for
models which require a vent damper.
Figure 8 Top Outlet Breeching for models which require
a vent damper.
Figure 9 Back outlet breeching connection for models
which do not require a vent damper.
Figure 10 Top outlet breeching connection for models
which do not require a vent damper.
Typical location for
barometric control
(Also see control
manufacturer’s
instructions)
Flue pipe
bracket
(One on each
side of pipe)
Typical location for
barometric control
(Also see control
manufacturer’s
instructions)
Flue pipe bracket
(One on each
side of pipe)
0251-056_OVD
OVD Damper
(Required)
BVSS
(WMO-1)
(Integrated with damper)
BVSS must be installed
upstream of the barometric
damper.
Typical location for
barometric control
(Also see control
manufacturer’s
instructions)
Flue pipe
bracket
(One on each
side of pipe)
0250-056_OVD
OVD
Damper
(Required)
Flue pipe
bracket
(One on each
side of pipe)
Typical location for
barometric control
(Also see control
manufacturer’s
instructions)
BVSS
(WMO-1)
(Integrated with damper)
BVSS must be installed
upstream of the
barometric damper.
background
Part number 550-142-332/0421
18
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Connect water piping
Table 4 Water piping sizes
General piping information
• All Packaged WTGO boilers are shipped with an installed combination
temperature limit control/low water cut-off.
• If installation is to comply with ASME, an additional high temperature
limit is needed. If installation is to comply with Canadian requirements,
an additional high temperature limit maybe needed. Consult local
inspector. Install control in supply piping between boiler and isolation
valve. Set control to a minimum of 20°F above set point of combination
control. Maximum allowable set point is 220°F. Wire control as shown
on wiring diagram.
• Use back flow check valve in cold water supply as required by local codes.
Install piping:
• See Figure 11 or Figure 12, page 19 and Water Piping Size Table 4 for
near-boiler piping and single-zone piping. See page 20 to complete
multiple-zone piping or page 21 to complete piping for systems oper-
ating below 140°F.
• For multiple-boiler piping, contact Weil-McLain Technical Services
for assistance, if required.
• Install relief valve vertically in “R1” tapping on front of boiler. See
Figure 11 or Figure 12 and also refer to tag attached to relief valve for
manufacturer’s instructions.
Pipe relief valve discharge line near floor close to floor drain
to eliminate potential of severe burns. Do not pipe to any
area where freezing could occur. Do not plug, valve or place
any obstruction in discharge line.
DIAPHRAGM expansion tank
(Figure 11, page 19)
• Make sure expansion tank size will handle boiler and system water
volume and temperature. Tank must be located near boiler before inlet
to circulator. See tank manufacturer’s instructions for details.
Undersized expansion tanks cause system water to be lost
from relief valve and makeup water added through fill valve.
Eventual section failure can result.
• Install automatic air vent in “N” tapping as shown in Figure 11, page 19.
CLOSED expansion tank
(Figure 12, page 19)
• Ensure expansion tank size will handle boiler and system water volume
and temperature.
• Undersized expansion tanks cause system water to be lost from relief
valve and makeup water added through fill valve. Eventual section
failure can result.
• Connect tank from “N” tapping shown in Fig-
ure 12, page 19 to expansion tank. Use ½" NPT
piping. Pitch any horizontal piping up towards
tank 1 inch per 5 feet of piping.
To connect WTGO boilers to
indirect-fired water heaters
• Install and wire per water heater manual provided
with water heater.
• If boiler has a tankless heater installed:
• Remove tankless heater and install cover plate.
OR
• Leave tankless heater installed. Drain coil and re-
move piping. Do not plug holes in tankless heater
front plate.
Boiler
Size
To system From system
WTGO-3 1¼" 1¼"
WTGO-4 1¼" 1¼"
WTGO-5 1½" 1½"
WTGO-6 1½" 1½"
WTGO-7 1½" 1½"
WTGO-8 2" 2"
WTGO-9 2" 2"
* All piping sizes based on 20°F
temperature rise through boiler.
background
Part number 550-142-332/0421
19
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Connect water piping (continued)
Figure 11 Piping with DIAPHRAGM expansion tank
Figure 12 Piping with CLOSED expansion tank
Isolation
valve
From
system
Isolation valve
Cold water fill
To system
“C” tapping
“N” tapping
“B1” tapping
Relief valve
Circulator
Closed type expansion
tank
Circulator
(Alternate circulator location)
Isolation valve
Circulator
Automatic
air vent
Relief valve
To diaphragm
expansion tank
and fittings
From
system
To system
“C” tapping
“N” tapping
Isolation
valve
Cold water
fill
“B1”
tapping
Circulator
(Alternate circulator
location)
background
Part number 550-142-332/0421
20
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Zone 2
Zone 1
5
1
2
1
3
Connect water piping (continued)
Zone 2
Zone 1
4
5
1
1
Piping MULTIPLE ZONES
Follow instructions on page 18 and page 19 to install
piping near boiler.
See Figure 13 or Figure 14 to complete installation.
Zoning with circulators:
1. Size each circulator to individual circuit require-
ments.
2. Install balancing valves to adjust flow to distribute
heat to all zones.
3. Separate relay is required for each circulator.
Zoning with zone valves:
1. Install balancing valves to adjust flow to distribute
heat to all zones.
2. Separate transformer is required to power zone
valves. Refer to manufacturers installation instruc-
tions for wiring or contact our Technical Services
group for assistance.
3. Pressure bypass valve recommended on zone valve
systems to prevent excessive flow in a single zone
or water hammer when valves close.
Legend
1 Isolation valve
2 Flow control valve
3 Circulator
4 Zone valve
5 Drain valve
Figure 13 Multiple zoning with CIRCULATORS
Figure 14 Multiple zoning with ZONE VALVES
background
Part number 550-142-332/0421
21
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Connect water piping (continued)
Figure 15 Piping with CIRCULATORS
Figure 16 Piping with ZONE VALVES
Piping for systems requiring
temperatures below 140°F
In most systems, this type of piping is not required. If
system water temperature requirements are less than
140°F, such as radiant panels or converted gravity sys-
tems, use piping as shown in Figure 15 or Figure 16. If
system piping is plastic without an oxygen barrier, a
heat exchanger must be used.
Legend
1 Isolation valve
2 Flow control valve
3 Circulator
4 System temperature
gauge
5 Zone valve
6 Drain valve
7 System temperature
valves
Adjust valves so that:
- the temperature at
gauge 8 is at least 140°F
- the temperature at
gauge 9 is at least 160°F
8 Blend temperature
gauge
9 Boiler temperature
gauge
background
Part number 550-142-332/0421
22
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Use with refrigeration systems
• Install boiler so that chilled medium is piped in
parallel with heating boiler. Use appropriate valves
to prevent chilled medium from entering boiler.
Consult AHRI Installation and Piping Guides.
• If boiler is connected to heating coils located in
air handling units where they can be exposed to
refrigerated air, use flow control valves or other
automatic means to prevent gravity circulation
during cooling cycle.
Figure 17 Use with refrigeration system
Connect water piping (continued)
Supply
Circ.
Circ.
Chiller
Strainer
Exp. tank
Exp. tank
1
1
1
1
2
1 Isolation valves 2 Balancing valve
background
Part number 550-142-332/0421
23
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Connect tankless heater piping
Limit Control with
Tankless Control
Automatic Mixing
Valve
Flow Regulating
Valve
Cold Water
Supply
12" min.
Cold
Hot
Mixed
Figure 18 Tankless heater pipingTable 5 Tankless heater ratings
NSF/ANSI 372
Boiler
Size
Heater
number
Intermittent
draw
ratings
(gpm)*
Inlet
and
outlet
tapping
sizes
WTGO-3 WT-14 3.25 ½"
WTGO-4 WT-14 3.75 ½"
WTGO-5 WT-14 4.00 ½"
WTGO-6 WT-14 4.25 ½"
WTGO-7 WT-20 5.50 ½"
WTGO-8 WT-20 5.75 ½"
WTGO-9 WT-20 6.00 ½"
* Gallons of water per minute heated from 40°F
to 140°F with 200°F boiler water temperature.
Tested in accordance with AHRI Testing and
Rating Standard for Indirect Tankless Water
Heaters Tested with Boilers.
Studies have indicated that dangerous bacteria can form
in potable water distribution systems if certain minimum
water temperatures are not maintained. Contact local
health department for more information.
To pipe tankless heater:
1. Size piping no smaller than tankless heater inlet and outlet.
2. Following controls (furnished by others) must be installed:
a. Automatic mixing valve. - See Figure 18.
b. Flow regulating valve. Size according to intermittent draw of tankless
heater. See Table 5 Follow valve manufacturer’s instructions to install.
3. Additional anti-scald devices may be installed at each hot water faucet,
bath and shower outlet.
4. In hard water areas, soften cold domestic supply water to heaters to
prevent lime build-up
These single wall heat exchangers comply with National Standard
Plumbing Code provided that:
• Boiler water (including additives) is practically non-toxic, having a
toxicity rating or class of 1, as listed in Clinical Toxicology of Com-
mercial Products.
• Boiler water pressure is limited to max. 30 psig by approved water
relief valve.
Hot Water Can Scald!
• Consumer Product Safety Commission and
some states recommend domestic hot water
temperature of 130°F or less.
• When installing an automatic mixing valve,
selection and installation must comply with
valve manufacturer’s recommendations and
instructions.
• Water heated to a temperature suitable for
clothes washing, dish washing and other sanitiz-
ing needs will scald and cause injury.
• Children, elderly, infirm or physically handi-
capped persons are more likely to be injured
by hot water. Never leave them unattended in
or near a bathtub, shower or sink. Never allow
small children to use a hot water faucet or draw
their own bath. If anyone using hot water in the
building fits this description, or if state laws or
local codes require certain water temperatures
at hot water faucets, take special precautions:
• Install automatic mixing valve set according
to those standards.
• Use lowest practical temperature setting.
• Check water temperature immediately after
first heating cycle and after any adjustment.
Tankless water heaters for WTGO boilers have
been tested and certified by the CSA Group
(certificate # 2552127).
background
Part number 550-142-332/0421
24
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
DO NOT connect directly from 3-wire
zone valves to the T-T terminals on
the boiler
. When using 3-wire zone valves,
install an isolation relay. Connect the zone
valve end switch wires to the isolation relay
coil. Connect the isolation relay contact across
the boiler T-T terminals. Failure to comply
can result in damage to boiler components
or cause unreliable operation, resulting in
possible severe property damage.
General wiring requirements
Electric shock hazard – Can cause severe personal
injury or death if power source, including service
switch on boiler, is not disconnected before install-
ing or servicing.
• Installations must follow these codes:
• National Electrical Code, ANSI/NFPA 70, – latest edition
and any additional national, state or local codes.
• In Canada, CSA C22.1 Canadian Electrical Code Part 1,
– latest edition and any local codes.
• Wiring must be NEC Class 1. If original wire as supplied
with boiler must be replaced, type 105°C wire or equivalent
must be used. Supply wiring to boiler and additional control
wiring must be 14 gauge or heavier.
• Provide electrical ground at boiler as required by codes.
Thermostat wiring
• Install thermostat on inside wall away from influences of
drafts, hot or cold water pipes, lighting fixtures, television,
sun rays or fireplaces.
• Follow instructions with thermostat. If it has a heat an-
ticipator, set heat anticipator in thermostat to match power
requirements of equipment connected to it. Boiler wiring
diagrams give setting for standard equipment.
Zone Valve Wiring
4- wire zone valves may be connected directly to the boiler
control.
General wiring
• Packaged boilers have harnesses furnished.
• For Semi-packaged and Knocked-down boilers, trim kits are
furnished with burner and limit harnesses integrated with
Hydrolevel control.
• All field-provided high voltage wiring must be sheathed in
flexible metal conduit.
• Connect incoming line voltage “HOT” wire to service switch,
and neutral wire to white wire. Field-install equipment
ground wire to green wire with wire nut inside Hydrolevel
control.
• Service switch is integrated into the Hydrolevel control.
• Some local codes may require an emergency shut-off switch
installed at a location away from boiler. Follow local codes.
Burner wiring
• Burner harness incorporates a disconnect plug, providing a
convenient way to disconnect wiring when burner mounting
door is opened.
• All Packaged boilers have a power disconnect plug installed
on burner.
• On Semi-packaged and Knocked-down boilers, mount the
plug (P/N 591-391-850, included in water trim carton) on
the burner housing as shown in Figure 19, page 25. For Carlin
burners, screw burner plug into threaded conduit coupling,
then mount this assembly to the burner housing using the
chase nipple.
High temperature limit
• To comply with ASME, UL 726 or Canadian requirements,
an additional high temperature limit is needed.
• Install the secondary control in the supply piping between
boiler and isolation valve.
• Set the control to a minimum of 20˚F above the set point of
the combination control.
• The maximum allowable set point is 220˚F.
• Wire the control as shown on page 26.
Connect wiring
background
Part number 550-142-332/0421
25
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Limit control
Service
switch on
control
Burner
wiring
harness
Burner
disconnect
plug
Figure 19 Boiler wiring for forced hot water
Connect wiring (continued)
background
Part number 550-142-332/0421
26
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Figure 20 Wiring diagram
Connect wiring (continued)
background
Part number 550-142-332/0421
27
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
120 vac
field wiring
Low voltage
field wiring
120 vac
factory wiring
Low voltage
factory wiring
Connect wiring — blocked vent shutoff switch option
Figure 21 Blocked vent shutoff switch installation Figure 22 BVSS wiring diagram
Blocked vent shutoff switch
Canada, blocked vent shutoff switch kit
(see parts list page 36) must be installed.
See Figure 21.
When using the OVD damper kit, the
BVSS is required, and is integrated into
the damper harness wiring.
When using the BVSS without the OVD
damper, the BVSS is wired directly to the
Combination limit control as follows.
The wiring diagram in Figure 22 shows
boiler wiring only up to the burner
disconnect. For additional information,
refer to manufacturer’s instructions.
Electric shock hazard – Turn off electrical
power supply at service entrance panel
before making any electrical connections
to avoid possible electric shock hazard.
Failure to do so can cause severe personal
injury or death.
After installing BVSS switch, proceed as follows
1. Disconnect power.
2. Install Shutoff Switch (BVSS) Wiring Harness (P/N 591-391-942, which
is included in BVSS kit P/N 591-624-650) as follows:
a. Remove cover from BVSS Box.
b. Install straight fitting end of the harness on the BVSS Box. Install
elbow (90º) end fitting on the right side of the Hydrolevel control.
c. Install both the fork ends to the screw terminals on the BVSS Switch
as per the wiring diagram, (see Figure 22).
d. Replace BVSS box cover.
e. Locate Combination Control, remove cover, and disconnect red
wire from “B1” terminal.
f. If red wire from Step e” has uninsulated female end, replace it
with insulated female end as supplied in kit.
g. Connect female end of Shutoff Switch BVSS Harness (blue wire)
to “B1” terminal.
h. Connect male end of Shutoff Switch BVSS Harness to the red wire
removed in Step e”.
i. Replace Combination Control Cover.
3. Turn on power and verify safe operation of the appliance.
4. Restore boiler to normal operation.
background
Part number 550-142-332/0421
28
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Flare fitting
See local codes for appropriate
arrangement and piping of filter
control valves, etc., back to oil tank.
General oil piping requirements
• Location and installation of oil tanks, oil piping and
burners must follow:
• NFPA 31 - latest edition, Standard for the Installation
of Oil-Burning Equipment.
• In Canada, CSA B139, Installation of Oil-Burning
Equipment.
• Local codes and regulations.
• Information provided with burner and fuel pump.
• If any part of fuel oil tank is above level of burner, instal-
lation of an anti-siphon device is highly recommended
to be used to prevent flow of oil in case of oil line break.
• Support oil lines as required by codes.
• Make tank connections with swing joints or copper tubing
to prevent breaking in case the tank settles. Make swing
joints so they will tighten as tank settles. Non-hardening
pipe joint compounds should be used on all threads.
Do not use Teflon tape as an oil pipe sealant. It
can cause valves to fail, creating hazards. Do not
use compression fittings.
• Underground pipe must be run in a casing to prevent oil
leaking into ground or under floor. Check local codes for
information.
Oil piping connection at burner
See Figure 24 for recommended connection at burner, al-
lowing burner mounting door to swing open completely for
servicing.
Figure 23 OVD Vent damper wiring diagram
1. WTGO Boiler models ending in “D”, such as WTGO-3D,
require the installation of the Field Controls OVD-7 damper,
Weil-McLain part number 381-800-515.
2. When installing the boiler, wire all controls from vent damper
and thermal switch in accordance with the OVD damper
manual and the following wire diagrams.
3. Connect damper wires to the boiler as follows:
a. Remove black wire (burner disconnect harness) from
the B1 terminal, and connect that wire to the Yellow
wire from damper, using a wire nut.
b. Connect the orange wire from the damper to the B1
screw terminal.
c. Connect the black wire from the damper to the L1
screw terminal.
d. Connect the white wire from the damper to the L2
screw terminal.
e. Connect the green wire from the damper to ground.
Connect oil piping
Connect wiring - vent
damper
Figure 24 Recommended oil piping connection to
burner
background
Part number 550-142-332/0421
29
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Start-up
Fill the system
1. Close manual and automatic air vents and boiler
drain cock.
2. Fill to correct system pressure. Correct pressure will
vary with each installation. Normal cold water fill
pressure for residential systems is 12 psig. Boiler
water pH 7.0 to 8.5 is recommended.
Failure to maintain recommended pH
level can cause section failure and leaks.
3. Open automatic air vent one turn.
4. Open other vents.
a. Starting on the lowest floor, open air vents one
at a time until water squirts out. Close vent.
b. Repeat with remaining vents.
5. Refill to correct pressure.
When using antifreeze
Do not use automotive, ethylene glycol,
undiluted or petroleum-based antifreeze.
Severe personal injury, death or substan-
tial property damage can result.
• Use antifreeze especially made for hydronic systems.
Inhibited propylene glycol is recommended.
• 50% solution provides protection to about -30°F.
Do not exceed 50% mixture.
• Local codes may require back-flow preventer or
actual disconnect from city water supply.
• Determine quantity according to system water con-
tent. Boiler water content is listed on back cover of
manual. Percent of solution will affect sizing of heat
distribution units, circulator and expansion tank.
• Follow antifreeze manufacturer’s instructions.
• Do not add cold water to hot boiler. Thermal shock
can cause sections to crack.
To place in operation
1. Verify boiler is filled with water.
2. Open burner mounting door and verify rear tar-
get wall, floor and burner door insulations are in
proper position.
3. Verify burner mounting door is closed tightly and
burner wiring harness is connected to Hydrolevel
control.
Factory burner adjustment and settings may not be
suitable for specific job conditions. See “Burner adjust-
ments”, below.
A burner nozzle change may be required -
refer to the burner instructions or boiler’s
rating label for correct nozzle selection
Make final burner adjustments using
combustion test equipment to assure
proper operation. Do not fire boiler
without water. Sections will overheat,
damaging boiler and resulting in sub-
stantial property damage.
4. Vent air from system. Repeat Steps 4 and 5 under
“Fill the system. Air in system can interfere with
water circulation and cause improper heat distri-
bution.
5. Check boiler and system piping for leaks. See Tips
for water systems” on page 4.
6. Inspect breeching and venting for proper operation.
background
Part number 550-142-332/0421
30
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Date Installed: ____________________________
Boiler Model Number: _______ Series: ____________
Consumer Protection (CP) Number(s): _________
Measured Btu or GPH Input: ________________
Installation instructions have been followed.
Check-out procedure has been performed.
Above information is certified to be correct.
Information received and left with owner/
maintenance person.
Installation and service certificate
Installer: ________________________________________________________________________________________________
(Company) (Address) (Phone)
_________________________________________
(Installer’s Signature)
Installation and service certificate
Check off Steps as completed
Boiler and heat distribution units filled with water?
Automatic air vent, if used, opened one full turn?
Air purged from system? Piping checked for leaks?
Air purged from oil piping? Piping checked for leaks?
Flue cap in place and tightened? Burner door closed, sealed
and nut tight? Burner plugged in and service switch on?
Obtain gas-tight seal to prevent possible flue gas
leakage and carbon monoxide emissions, leading
to severe personal injury or death.
Proper draft and burner flame? Final adjustment made with
combustion test equipment?
Test limit control: While burner is operating, move indica-
tor on limit control below actual boiler water temperature.
Burner should go off while circulator continues to operate.
Raise setting on limit control above water temperature and
burner should re-ignite.
Test additional field-installed controls: If boiler has a low
water cutoff, additional high limit or other controls, test for
operation as outlined by manufacturer. Burner should be
operating and should go off when controls are tested. When
controls are restored, burner should re-ignite.
Limit control set to system temperature requirements (max.
220°F)?
For multiple zones, flow adjusted to distribute heat in all
zones?
Thermostat heat anticipator setting (if available) set properly?
Refer to “Connect wiring, page 24.
Boiler cycled with thermostat? Raise to highest setting and
verify boiler goes through normal start-up cycle. Lower to
lowest setting and verify boiler goes off.
Observed several operating cycles for proper operation?
Set room thermostat(s) to desired room temperature?
Completed Installation and Service Certificate below?
Reviewed pages 1–7 with owner or maintenance person and
instructed person to keep for future reference?
Returned all instructions provided with boiler to its envelope
and placed with boiler for future reference?
Check-out procedure
background
Part number 550-142-332/0421
31
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Annual service check list
Annual Service Call
Checklist
(follow in order listed below)
Dates Comments
1
Check that boiler area is free from combus-
tible materials, gasoline and other flam-
mable vapors and liquids.
2
Check for and remove any obstruction
to combustion and ventilation air flow to
boiler.
3
Check breeching and chimney or vent for
obstructions, damage, etc. Repair or replace
as necessary.
4
Clean boiler flue ways. See page 32.
5
Perform service on relief valve and circula-
tor. See below.
6
Check boiler and piping for leaks and repair
if found. Check for leaks at tankless heater
plate. Tighten nuts only if leaks are found
(for WTGO torque to 20-25 ft.lbs.).
7
Inspect and adjust burner. See burner
manual and:
• change nozzle.
• check ignition electrode settings.
• clean blower housing and wheel.
• make sure blower wheel turns freely.
• oil burner motor if required.
• clean air inlet.
• clean or change fuel filter and strainer.
8
Make sure boiler is filled with water.
9
Start unit and verify combustion settings
with combustion test equipment.
See page 34.
10
Verify operation of all controls on boiler.
See page 30.
Any parts of the boiler furnished by Weil-McLain must be replaced by parts listed in Weil-McLain Boiler and Repair Parts Book.
Controls requiring annual service
Water Relief Valve
Check operation of water relief valve.
Follow instructions on label fastened to
relief valve.
Scald potential. Do not check
operation of relief valve un-
less discharge piping has
been installed according to
Boiler Manual. If piping is
not in place, a qualified ser-
vice technician must prop-
erly install piping.
Circulator
Follow oil-lubricating instructions on cir-
culator. Over-oiling will damage circulator.
Water-lubricated circulators do not need
oiling.
background
Part number 550-142-332/0421
32
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Detailed service procedures
Cleaning boiler flue ways
Make sure all electrical connections to
boiler are turned off and wait until boiler
is warm, not hot, before cleaning. Failure
to do so will result in severe personal
injury, death or substantial property
damage.
1. Top flue boilers — remove breeching and jacket
top panel. Rear flue boilers — remove jacket top
panel.
2. Remove flue collector hood, saving hardware for
reassembly.
3. Shut off oil valves. Arrange drip pans under the
areas of oil piping that will be disconnected. Dis-
connect oil line at burner so that you can swing
open the door completely.
4. Line combustion chamber floor with newspaper to
catch any soot that will be loosened in the cleaning
process.
5. Starting at the top of the boiler, use a wire flue brush
to thoroughly clean between all pins at all angles. Be
careful not to damage side walls of rear refractory.
6. Move to the bottom of the flue ways and clean up
between the sections to reach pins left uncleaned
in Step #5.
7. Once the flue ways are cleaned, carefully remove the
paper from the floor of the combustion chamber.
8. Verify sealing rope around flue area is intact. Visually
check condition and position of insulation in combus-
Figure 25 Thoroughly clean flue ways between
all pins at all angles. Start on top of
boiler, finish from the bottom.
tion chamber floor, and the refractories at the rear of boiler and in the burner
mounting door. Replace any parts as necessary.
9. Close burner mounting door and tighten nut securely. Place flue col-
lector hood on top of boiler. Secure with hardware from Step #2.
Maintain a gas-tight seal to avoid possible flue gas leakage
and carbon monoxide emissions, which can lead to severe
personal injury or death.
10. Check breeching for sooting and clean if necessary. Install jacket top
panel and breeching.
11. Reconnect oil line and all electrical connections.
General description of control operation
Automatic air vent
Air is released when cap is unscrewed one turn. If air vent leaks, remove
small cap on top of vent, push in stem of valve and then release to clean
valve seat. Screw cap completely on, then unscrew one turn.
Water relief valve
Provides discharge if boiler pressure exceeds 30 psig.
Temperature limit control
If high boiler water temperature occurs, control shuts down burner, but allows
circulator to run as long as there is a call for heat. Limit should be set higher
than temperature needed for the system. Maximum limit setting is 220°F.
Circulator
Circulator provides forced water circulation through boiler and piping system.
Pressure-temperature gauge
Provides reading of boiler pressure and temperature. Maximum boiler
pressure is 50 psig, maximum water temperature is 220°F. Temperature
will vary according to system and daily heating demands. The range will
be from room temperature up to limit control setting.
Tankless water heater
Weil-McLain tankless heater ratings are based on 200°F boiler water tem-
perature. To get rated output, set tankless heater control to 200°F. Control
can be adjusted to meet system hot water requirements.
Expansion tank
As water heats up, it expands. Tank provides a place for increased water volume.
May be open, closed, or diaphragm-type. If relief valve opens frequently, expan-
sion tank may be water-logged. Drain tank and re-establish proper air cushion.
1. Open-type — Located above highest radiator or baseboard unit, usu-
ally in the attic or closet. Has a gauge glass and overflow pipe to drain.
2. Closed-type — Welded gas tight and located above boiler. Tank is par-
tially filled with water, leaving an air cushion for expansion.
3. Diaphragm-type — Welded gas tight with a rubber diaphragm to separate
air from water. Tank must be located near boiler before inlet to circulator.
An air vent must be installed in air vent tapping on boiler when this type
of tank is used. This eliminates air in system. Normal cold water fill pres-
sure is 12 psig. Tank pressure may be checked with an air pressure gauge.
background
Part number 550-142-332/0421
33
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Handling ceramic fiber and fiberglass materials
REMOVAL OF COMBUSTION CHAMBER
LINING OR BASE PANELS
The combustion chamber lining or base insula-
tion panels in this product contain ceramic fiber
materials
that have been identified as carcinogenic,
or possibly carcinogenic, to humans
. Ceramic
fibers can be converted to cristobalite in very
high temperature applications. The International
Agency for Research on Cancer (IARC) has con-
cluded, “Crystalline silica inhaled in the form of
quartz or cristobalite from occupational sources
is carcinogenic to humans (Group 1).”:
Precautionary measures
Avoid breathing fiberglass dust and contact with skin
or eyes.
• Use NIOSH certified dust respirator (N95).
This type of respirator is based on the OSHA
requirements for fiberglass wool at the time this
document was written. Other types of respirators
may be needed depending on the job site condi-
tions. Current NIOSH recommendations can be
found on the NIOSH web site at http://www.
cdc.gov/niosh/homepage.html. NIOSH approved
respirators, manufacturers, and phone numbers are
also listed on this web site.
• Wear long-sleeved, loose fitting clothing, gloves,
and eye protection.
Apply enough water to the combustion chamber lining
or base insulation to prevent airborne dust.
Remove combustion chamber lining or base insulation
from the boiler and place it in a plastic bag for disposal.
Wash potentially contaminated clothes separately from
other clothing. Rinse clothes washer thoroughly.
NIOSH stated First Aid
Eye: Irrigate immediately
Breathing: Fresh air
REMOVAL OF FIBERGLASS WOOL
or
INSTALLATION OF FIBERGLASS WOOL
OR BASE PANELS:
This product contains fiberglass jacket
insulation and ceramic fiber materials in
combustion chamber lining or base panels
in gas fired products. Airborne fibers from
these materials have been listed by the State
of California as a possible cause of cancer
through inhalation.
Precautionary measures
Avoid breathing fiberglass dust and contact with
skin or eyes.
• Use NIOSH certified dust respirator
(N95). This type of respirator is based
on the OSHA requirements for fiberglass
wool at the time this document was writ-
ten. Other types of respirators may be
needed depending on the job site condi-
tions. Current NIOSH recommendations
can be found on the NIOSH web site at
http://www.cdc.gov/niosh/homepage.html.
NIOSH approved respirators, manufactur-
ers, and phone numbers are also listed on
this web site.
• Wear long-sleeved, loose fitting clothing,
gloves, and eye protection.
Operations such as sawing, blowing, tear out, and
spraying may generate airborne fiber concentra-
tion requiring additional protection.
Wash potentially contaminated clothes separately
from other clothing. Rinse clothes washer thor-
oughly.
NIOSH stated First Aid
Eye: Irrigate immediately
Breathing: Fresh air
background
Part number 550-142-332/0421
34
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Close clearance installation
Manual reset
temperature switch
Thermostat
44156
Figure 26 Manual reset temperature switch location Figure 27 Manual reset temperature switch wiring
Area above boiler
Bracket
1 to 5
inches
Manual reset
temperature
switch
Combustible surface
#6 X ½" Phillips
Sheet metal
screw
#10 X ½" Phillips
sheet metal screw
Close clearance installation
Substitute these instructions for corresponding material in manual.
All other procedures and practices must remain the same.
Recommended service and minimum clearances shown on page 8
should be used where possible. Where closer clearances are required:
• Top of boiler — If less than 24" available, provide removable
surface to allow for cleaning boiler flue ways.
• Right or left side — Minimum 2 inches.
• Front — Minimum 2 inches from burner.
• Type “L double-wall flue pipe to combustible surface — as listed
in Table 6, page 35 and Figure 28 through Figure 30, page 35.
Jacket cap must be in place on boiler to avoid requiring
an 9" minimum clearance from back or top of boiler
to combustible material. Flue pipe clearances must
take precedence over jacket clearances.
1. Install boiler using clearances described at left.
2. Install barometric control 18-20 inches from boiler in breeching.
3. Attach manual reset temperature switch near upper surface of
enclosed area. See Figure 26.
4. Wire switch in series with thermostat. See Figure 27.
5. Provide two combustion/ventilation openings when installing in
confined space. Size opening 140 sq. in. (1000 Btu) per 1 GPH
input. Locate openings near top and bottom of enclosed space.
To provide close clearances as described on pages 34 and 35:
Obtain the Close Clearance Kit, Weil-McLain Part No. 386-500-050. Install the kit as described below. Failure to use
kit or install as described can result in a fire hazard, causing severe personal injury, death or substantial property
damage.
Burner adjustments
Final burner adjustments must be made using
combustion test equipment to assure proper
operation. Do not fire boiler without water or
sections will overheat.
1. Refer to burner manual for start-up.
2. Allow boiler to heat to design condition.
3. Burner should be adjusted to 13% CO
2
or less with a
smoke level of zero and over-fire of -0.01” to -0.02”. Re-
adjust burner combustion to account for environmental
conditions. Actual CO
2
value will vary and should be
adjusted for clean and safe combustion operation. Seasonal
variations as well as sufficient combustion air supply can
affect proper combustion and boiler performance. The
burner should only be adjusted by a service professional
with appropriate instrumentation.
background
Part number 550-142-332/0421
35
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Dimension A
(When desired minimum
clearance from
Type “L” double-wall
vent pipe to combustible
surface is:)
Use the following
protection**:
3"
½” thick insulation board
***
over one-inch glass fiber
or mineral wool batts+
2"
24 gauge sheet metal with
one-inch ventilated air
space
3"
½” thick insulation board
***
with one-inch ventilated
air space
* All clearances measured from outer surface of
equipment to combustible surface, not to the
protection used.
** Apply to combustible surface unless otherwise
noted. Cover all surfaces as specied in Table and
Figure25. icknesses are minimum.
*** Factory-fabricated board made of non-
combustible materials, normally bers, having
thermal conductivity in range of one (Btu-inch)/
(hr./sq. ./°F) or less.
+ Mineral wool batts (blanket or board), having min.
density of 8 lb./3 and a min. melting point of
1500°F.
Other dimensions available. Refer to NFPA-31.
Close clearance installation (continued)
Figure 28 Flue pipe clearances Figure 29 Back vent clearances
Figure 30 Top vent clearances
Table 6 Protection required for clearances
less than 6 inches from double-wall
vent pipe*
Combustible surface
Protection
Type "L"
double-wall
vent pipe
6"
A
6"
24" For servicing
or min. 2" For close
clearances
Combustible
surface
Combustible
surface
A
A
2"
Note: 2" min. on sides
Combustible
surface
Combustible
surface
A
A
Note: 2" min. on sides
2"
2"
24" For
servicing
or min. 2"
For close
clearances
background
Part number 550-142-332/0421
36
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Replacement parts
Repair parts must be purchased through Weil-McLain for the specific boiler as indicated in the list below. Results from
using modified or other manufactured parts will not be covered by warranty and may damage boiler or impair operation.
Table 7 WTGO Section and flue collector part numbers for Series 4
Item Description Part No.
A
Front section w/heater opening
7013
316-700-260
B
Wide intermediate section
(WTGO-3) 7010
316-700-075
B Narrow intermediate section 7015 316-700-065
C
Intermediate section w/draw rod
lugs 7016
316-700-070
D
Back section w/7" ue, supply &
2" return 7027
316-700-235
E
Section replacement kit
(for 1 joint, includes seals, rope,
adhesive and collector hood
hardware) front or back section
386-700-852
Section replacement kit
(for 2 joints, includes seals, rope
and adhesive) intermediate
section
386-700-851
Section assembly, for WTGO-3 with
jacket & collector hood installed
386-701-038
Section assembly, for WTGO-4 with
jacket & collector hood installed
386-701-039
Section assembly, for WTGO-5 with
jacket & collector hood installed
386-701-040
Section assembly, for WTGO-6 with
jacket & collector hood installed
386-701-041
Section assembly only, for WTGO-3
386-700-978
Section assembly only, for WTGO-4
386-700-980
Section assembly only, for WTGO-5
386-700-981
Section assembly only, for WTGO-6
386-700-982
Section assembly only, for WTGO-7
386-700-662
Section assembly only, for WTGO-8
386-700-663
Section assembly only, for WTGO-9
386-700-664
F
Collector hood kit for WTGO-3*
386-700-337
F
Collector hood kit for WTGO-4*
386-700-337
F
Collector hood kit for WTGO-5*
386-700-338
F Collector hood kit for WTGO-6* 386-700-339
F
Collector hood kit for WTGO-7*
450-020-188
F
Collector hood kit for WTGO-8*
450-020-189
Item Description Part No.
F
Collector hood kit for WTGO-9*
450-020-190
G Tie rod ½ x 5½ (WTGO-7, 8, 9) 560-234-464
G Tie rod ½ x 10¾ (WTGO-7) 560-234-491
G Tie rod ½ x 12 (WTGO-7) 560-234-492
G Tie rod ½ x 14 (WTGO-3, 4, 8, 9) 560-234-470
G Tie rod ½ x 15 (WTGO-9) 560-234-495
G Tie rod ½ x 17 (WTGO-5) 560-234-472
G Tie rod ½ x 20 (WTGO-6) 560-234-534
G Tie rod ½ x 23¼ (WTGO-7) 560-234-538
G Tie rod 11/42 x 26 3/8 (WTGO-8) 560-234-542
G Tie rod ½ x 29½(WTGO-9) 560-234-497
H
Heater cover plate carton (cover
plate, gasket, studs, & nuts)
386-700-360
J
Combustion chamber kit (rear &
front Ref., Door ref. Blanket,
rope, blanket & water glass)
386-700-355
Burner mounting door assembly
(door, obs. port, rope, ins. & pins)
386-700-358
K Burner mounting door 7070 330-054-302
L Door hinge 7054 330-054-300
M Door refractory 386-700-359
N Door refractory blanket 591-222-115
P Observation port shutter 460-039-867
Q Door seal rope 5' 590-735-105
R
3/8" Glass rope for collector hood
(7' for largest size hood)
590-735-109
S
Flue cap assembly (cap, strap,
rope & screws)
386-700-344
Flue brush 123D 591-706-214
Blocked vent shutoff switch
(Canada only)
511-624-650
* Includes ue cap assembly, rope and hardware for
installation.
background
Part number 550-142-332/0421
37
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Replacement parts (continued)
Figure 31 WTGO Section and flue collector parts for Series 4
D
S
Q
K
P
G
C
G
J
E
G
F
R
B
A
H
L
M
N
J
background
Part number 550-142-332/0421
38
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Replacement parts (continued)
Table 8 WTGO Trim part numbers for Series 4
Item Description Part no.
1
Combination pressure-temperature gauge kit, 60° – 360° F., 0 - 75 psi,
31/8" dia., 1/4" NPT, short shank, with 1/4" x 1/2" reducing bushing
380-000-000
2
ASME pressure relief valve, set to relieve at 30 PSIG, 3/4" male inlet, 3
/4" female outlet
511-546-920
3
Electronic aquastat, high limit or combination high/low limit, with LWCO, high limit 100°–
220°, low limit 110°- 200°, circulator amps: 5.8 FLA, anticipator: 0.2 amps
381-300-000
4
Drain cock, 3/4" NPT, 11/2" shank 511-210-423
Drain cock, 3/4" NPT 511-246-392
5 Circulator
WTGO 3 & 4 – Taco 007e ECM 511-405-153
WTGO 3 - 6 – Taco 007 511-405-113
6
Circulator universal hardware kit 11/4" (Includes: (1) Flange, (1)
Gasket, (2) Screws and (2) nuts) for sizes 2, 3 & 4 only
381-354-526
Circulator universal hardware kit 11/2" (Includes: (1) Flange, (1)
Gasket, (2) Screws and (2) nuts) for sizes 5 & 6 only
381-354-531
7 Well 3/4" NPT, 6.25" long, extended shank type 592-300-027
8 Burner harness assembly 591-391-850
9 Barometric damper 510-512-267
10 Flue pipe brackets (set of 2) (Not shown) 426-700-268
11
Vent damper kits - Required for ENERGY STAR
®
compliance, (Version 3.0 Boilers speci-
cation of 87% AFUE), with reduced rates only
WTGO-3RD (Optional equipment)
WTGO-4RD (Optional equipment)
WTGO-5RD (Optional equipment)
WTGO-6RD (Optional equipment)
WTGO-7RD (Optional equipment)
Vent damper kit - Required for High Input nozzle installation
WTGO-3D, WTGO-3LD, WTGO-4D, WTGO-5D, WTGO-6D, and WTGO-7D
381-800-502
381-800-503
381-800-504
381-800-505
381-800-506
381-800-515
12 Outdoor - temperature sensor (Wireless) 386-701-047
background
Part number 550-142-332/0421
39
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Replacement parts (continued)
Figure 32 WTGO Trim part for Series 4
background
Part number 550-142-332/0421
40
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Replacement parts (continued)
Boiler
Size
Jacket panel with
insulation — front
Left side & rear Right side & rear
Top panel with
cap
WTGO-3L 381-355-962 381-355-963 381-355-982 381-355-969
WTGO-3 381-355-964 381-355-965 381-355-974 381-355-970
WTGO-4 381-355-964 381-355-966 381-355-974 381-355-971
WTGO-5 381-355-964 381-355-967 381-355-975 381-355-972
WTGO-6 381-355-964 381-355-968 381-355-976 381-355-973
Table 9 WTGO part numbers for Series 4
Common jacket parts for all boilers
Plastic ue cap cover with insulation 560-917-105
Jacket hardware kit 386-700-853
Touch up paint, Cloud spray can 381-359-278
Touch up paint, Slate spray can 384-000-141
Figure 33 WTGO Boiler jacket for Series 4
Complete Jacket cartons
3 section WTGO-3 416-700-468
3 section WTGO-3L 416-700-469
4 section 416-700-470
5 section 416-700-471
6 section 416-700-472
7 section 416-700-473
8 section 416-700-474
9 section 416-700-475
background
Part number 550-142-332/0421
41
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Dimensions
6 ¼
[158.8]
29 ⁄
[750.9]
For 7
dia.
[177.8]
Vent pipe
Alternate
return
(“A”
boilers
only)
7 Dia.
[177.8]
7 ⁄
[182.6]
2
[66.7]
15 ½
[393.7]
14
Approx.
B
L
7 Dia
[177.8]
7 Dia
[177.8]
Left side Front
Intermediate Back
14 [358.8]
Boiler Size WTGO-3L WTGO-3 WTGO-4 WTGO-5 WTGO-6 WTGO-7 WTGO-8 WTGO-9
B
inches
13
1
/
2
13
1
/
2
13
5
/
8
16
7
/
8
20 23
1
/
8
26
1
/
4
29
3
/
8
mm
342.9 342.9 345.9 428.7 508 587.2 666.7 746.2
L
inches
13
3
/
4
16
7
/
8
16
7
/
8
20 22
1
/
8
26
1
/
4
29
3
/
8
32
1
/
2
mm
349.2 428.7 428.7 508 587.2 666.7 746.2 825.5
Figure 34 WTGO dimensions — inches (mm)
background
Part number 550-142-332/0421
42
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
DOE
®
Ratings
Table 10 WTGO Series 4 oil-red water boiler ratings
AHRI Certified Ratings
Boiler
Model
(9)
Burner Input
Heating
Capacity
Seasonal
Efciency
Net
Rating
(water)
Draft
Loss
Thru
boiler
Boiler
Water
Content
Flue
Outlet
Diameter
Minimum
Chimney
OVD
Damper
Required
GPH
(3)
MBH
(3)
MBH
(2)
AFUE
%
MBH
(2) (5)
In W.C.
(8)
Gallons
Inches
(7)
Rect.
Inches
Round
Inches
Height
Feet
Yes/No
WTGO-3LR 0.70 98 86
(4) 86.4 75 0.010
11.0 7 8 x 8 6 15
No
WTGO-3LD 0.95 133 115 (4) 86.0 100 0.010 Yes
WTGO-3R 0.80 112 98 (4) 86.2 85 0.020
14.9 7 8 x 8 6 15
No
WTGO-3RD 0.80 112 98 (4) 87.0 85 0.010 Yes
WTGO-3D 0.95 133 115 (4) 86.0 100 0.020 Yes
WTGO-4R 1.00 140 122 (4) 86.2 106 0.010
13.4 7 8 x 8 6 15
No
WTGO-4RD 1.00 140 123 (4) 87.0 107 0.010 Yes
WTGO-4D 1.20 168 146 (4) 86.0 127 0.010 Yes
WTGO-5R 1.20 168 147 (4) 86.1 128 0.015
15.9 7 8 x 8 7 15
No
WTGO-5RD 1.20 168 148 (4) 87.0 129 0.015 Yes
WTGO-5D 1.45 203 176 (11) 86.0 153 0.015 Yes
WTGO-6R 1.40 196 171 (4) 86.1 149 0.015
18.4 7 8 x 8 7 15
No
WTGO-6RD 1.40 196 173 (4) 87.0 150 0.015 Yes
WTGO-6D 1.75 245 213 (11) 86.0 185 0.015 Yes
WT GO-7R 1.60 224 196 (4) 86.0 170 0.015
20.8 7 8 x 8 8 15
No
WT GO-7RD 1.60 224 197 (4) 87.0 171 0.015 Yes
WTGO-7D 2.00 280 244 (11) 86.0 212 0.015 Yes
WTGO-8 2.30 322 266 (4)(6) - 231 0.025 23.3
7 8 x 12 8
20 No
WTGO-9 2.55 357 295 (4)(6) - 257 0.030 25.8 20 No
background
Part number 550-142-332/0421
43
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Ratings
NOTES:
(1) WTGO boiler designed with convertible vertical and horizontal ue outlet.
(2) MBH refers to thousands of Btu per hour.
(3) Based on 140,000 Btu/gal.
(4) Based on standard test procedures prescribed by the United States Department of Energy at combustion condition of
13.5% CO
2
and -0.02" W.C. dra over re.
(5) Net AHRI ratings are based on net installed radiation of sucient quantity for the requirements of the building and
nothing need be added for normal piping and pick-up. Water ratings are based on a piping and pick-up allowance of
1.15.
An additional allowance should be made for unusual piping and pick-up loads.
(6) AHRI gross output.
(7) See page16 for minimum breeching diameter.
(8) Listed dra losses are for factory-shipped settings.
(9) Boiler model suxes: R” designates a reduced input version. No separate/additional damper kit required. “D”
designates that the separate High Input OVD Automatic Vent Damper P/N 381-800-515 is required. “RD” designates
a reduced input version and the separate ES Vent damper is required (P/N 381-800-501 through 381-800-506).
(10) "L" designates a boiler with special front section (1½” supply tapping).
(11) Based on standard test procedures prescribed by the United States Department of Energy at combustion of 13.0%
CO
2
and -0.02” W.C. dra over re.
NOTE: A burner nozzle change may be required - refer to the burner instructions or boiler’s rating label for correct
selection
.
Table 11 WTGO Series 4 oil-red water boiler rating notes
background
44
Part number 550-142-332/0421
WTGO
OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 4 — Boiler Manual