Part Number 550-142-303/1120
4
EG
/
PEG sEriEs 6
EGH sEriEs 5 Gas-firEd boilErsboilEr manual
Installation must follow these codes:
• Local, state, provincial, and national codes, laws, regulations and ordinances.
• National Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest edition.
• National Electrical Code, ANSI/NFPA 70 – latest edition and/or the Canadian Electrical Code
Part I, CSA C22.1, Electrical Code.
• Canadian installations must comply with the Natural Gas and Propane Installation Code, CAN/
CSA B149.1 or B149.2 Installation Codes.
• Where required by the authority having jurisdiction, the installation must conform to the Standard
for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD1.
The equipment shall be installed in accordance with those installation regulations in force in the local
area where the installation is to be made. These shall be carefully followed in all cases. Authorities having
jurisdiction shall be consulted before installations are made.
Commonwealth of Massachusetts
When the boiler is installed within the Commonwealth of Massachusetts:
• Thisproductmustbeinstalledbyalicensedplumber.
• Ifantifreezeisused,areducedpressureback-owpreventerdeviceshallbeused.
Certification
Safe operating and other performance criteria were met with the gas manifold and con-
trol assembly provided on boiler when boiler underwent tests specified in ANSI Z21.13
- latest edition.
Before locating the boiler:
Check for nearby connection to:
•Ventingconnections
•Gassupplypiping
•Electricalpower
Check area around boiler. Remove any combustible materials, gasoline and other flammable liquids.
Failure to keep boiler area clear and free of combustible materials, gasoline and other
flammable liquids and vapors can result in severe personal injury, death or substantial
property damage.
Boiler must be installed so that gas control system components are protected from dripping or spray-
ing water or rain during operation or service.
If new boiler will replace existing boiler, check for and correct system problems, such as:
•Systemleakscausingoxygencorrosionorsectioncracksfromhardwaterdeposits.
Glycol — potential fire hazard —
All glycol is flammable when exposed to high temperatures. If glycol is allowed to accumulate in or
around the boiler or any other potential ignition source, a fire can develop. In order to prevent poten-
tial severe personal injury, death or substantial property damage from fire and/or structural damage:
• Neverstoreglycolofanykindneartheboileroranypotentialignitionsource.
• Monitorandinspectthesystemandboilerregularlyforleakage.Repairanyleaksimmediatelyto
prevent possible accumulation of glycol.
Codes & Checklist