VENT RESTRICTOR INSTALLATION (continued)
The restrictors are installed by removing the 2 screws on the ceiling of the firebox, place the desired
restrictor in place and use the screws to fasten the restrictor to the firebox. You must first remove the
firebox baffle (4 screws) before installing the desired restrictor. Return the firebox baffle after installing
the restrictor.
Typical Dura- Vent & Security Chimney’s Installation:
Vent terminals shall not be recessed into a wall or siding.
Horizontal Wall Vent Terminations
The position of the horizontal vent termination must be positioned in such a way as to meet all local building
codes. Attach the correct length of pipe. Mark the center line of the pipe facing the wall (allowing for a 1/4”
rise per foot of horizontal, example 10 ft of horizontal would require a rise of 2.5”).
NOTE
ALLOWING THE VENT PIPE TO SLOPE DOWN TOWARDS THE VENT TERMINATION COULD
CAUSE POOR COMBUSTION AND/OR HIGH TEMPERATURES THAT MAY PRESENT A FIRE
HAZARD.
PERMETTRE LA tuyau de ventilation vers descendent vers la sortie de ventilation POURRAIT
PROVOQUER une mauvaise combustion et / ou de températures élevées qui peuvent présenter
des risques d'incendie.
Fireplace