INSTALLATION
FLOOR PROTECTOR
This heater must have a non-combustible floor protector
(ember protection) installed beneath it if the floor is of
combustible material. If a floor pad is used, it should
be UL listed or equal. The floor pad or non-combustible
surface should be large enough to extend under the stove
and beyond each side as indicated. If there is a horizontal
run of flue pipe, there needs to be floor protection under
it that extends two inches beyond either side of the pipe.
REAR
FRONT
SIDE
SIDE
Front *16” (407 mm)
Sides 8” (204 mm)
Rear 2” (51 mm)
*Canadian Installations require
18” (457 mm)
CLEARANCES TO COMBUSTIBLES
It is of utmost importance that the clearances to
combustible materials be strictly adhered to during
installation of the stove.
Do not place any combustible material within 4’ (1.2m)
of the front of the unit.
The clearance between the flue pipe and a wall are valid
only for vertical walls and for vertical flue pipe.
The chimney connector must not pass through an attic
or roof space, closet or similar concealed space, a floor,
or a ceiling.
For Canadian installations, where passage through a
wall, or partition of combustible construction is desired,
the installation must conform to CAN/CSA-B365.
A flue pipe crossing a combustible wall must have a
minimum clearance of 18” (457.2 mm).
To reduce flue clearances from combustible materials,
contact your local safety department.
Floor to ceiling height must be at least 7’ (2.13m).
D
B
A
C
E
F
E
Key in mm
A 17 432
B 21 534
C 20 508
D 29 737
E 14 356
F 22 559
OUTSIDE COMBUSTION AIR
Your wood stove is approved to be installed with an
outside air intake (4FAK) which is necessary for a mobile
home. This type of installation is also required in air tight
houses and houses with negative pressure problems.
You can purchase this option through your heater dealer.
Make sure to specify the part number mentioned in this
booklet. Installation instructions are supplied with the air
intake kit. Outside combustion air may be required if:
1. Your stove does not draw steadily, smoke roll-out
occurs, wood burns poorly, or back-drafts occur
whether or not there is combustion present.
2. Existing fuel-fired equipment in the house, such as
fireplaces or other heating appliances, smell, do
not operate properly, suer smoke roll-out when
opened, or back-drafts occur whether or not there is
combustion present.
3. Opening a window slightly on a calm (windless) day
alleviates any of the above symptoms.