LG Electronics LUU248HV LG Air Conditioner Cooling Area,

User Manual - Page 57

For LUU248HV.

PDF File Manual, 82 pages, Read Online | Download pdf file

LUU248HV photo
Loading ...
Loading ...
Loading ...
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
PRODUCT DATA | 57
Product Data
Table 31: Heating Capacity Table for LUU188HV + LVN180HV4.
Heating Capacity Table for LV180HV4 (LUU188HV + LVN180HV4)
Outdoor Air
Temp.
Indoor Air Temp.: °FDB
61.0 64.0 68.0 70.0 72.0 75.0
°F DB °F WB TC PI TC PI TC PI TC PI TC PI TC PI
-4 -4.4 7.66 1.26 7.08 1.31 7.05 1.32 6.97 1.33 6.90 1.34 6.59 1.39
0 -0.4 9.23 1.26 8.68 1.31 8.55 1.33 8.43 1.35 8.33 1.36 7.98 1.40
5 4.5 11.10 1.27 10.58 1.32 10.33 1.35 10.16 1.36 10.03 1.38 9.62 1.42
10 9 12.35 1.28 11.85 1.33 11.52 1.36 11.32 1.38 11.16 1.39 10.72 1.44
17 15 13.73 1.29 13.25 1.34 12.83 1.38 12.60 1.40 12.41 1.42 11.94 1.46
20 19 14.56 1.30 14.10 1.34 13.63 1.39 13.37 1.41 13.17 1.43 12.67 1.47
25 23 15.96 1.32 15.49 1.36 14.95 1.41 14.66 1.44 14.44 1.46 13.89 1.50
30 28 17.37 1.34 16.83 1.39 16.25 1.43 15.95 1.46 15.72 1.49 15.14 1.52
35 32 18.78 1.37 18.18 1.41 17.56 1.45 17.24 1.48 16.99 1.51 16.38 1.55
40 36 19.73 1.41 19.18 1.45 18.57 1.50 18.25 1.53 17.99 1.55 17.34 1.59
45 41 20.93 1.46 20.43 1.50 19.83 1.55 19.50 1.58 19.24 1.60 18.54 1.65
47 43 21.41 1.48 20.93 1.52 20.33 1.57 20.00 1.60 19.73 1.62 19.02 1.67
50 46 21.47 1.47 21.04 1.51 20.52 1.55 20.22 1.58 19.98 1.60 19.31 1.64
55 51 21.58 1.45 21.22 1.49 20.83 1.52 20.59 1.54 20.40 1.55 19.79 1.59
60 56 21.68 1.44 21.40 1.46 21.14 1.49 20.95 1.50 20.81 1.51 20.28 1.53
63 59 21.74 1.43 21.51 1.45 21.32 1.47 21.18 1.48 21.06 1.48 20.57 1.50
68 64 21.81 1.42 21.62 1.43 21.51 1.45 21.40 1.46 21.31 1.46 20.86 1.47
PERFORMANCE DATA
Heating Capacity Tables
DB: Dry Bulb Temperature (°F) WB: Wet Bulb Temperature (°F) TC: Total
Capacity (kBtu/h)
PI: Power Input (kW) (includes compressor, indoor fan motor, and outdoor
fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Direct interpolation is permissible.
Do not extrapolate.
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant
piping.
0 ft. level difference between outdoor and indoor units.
Nominal heating capacity rating obtained with air entering the indoor
unit at 70ºF dry bulb (DB) and 60ºF wet bulb (WB), and outdoor ambient
conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).