LG Electronics LUU248HV LG Air Conditioner Cooling Area,

User Manual - Page 55

For LUU248HV.

PDF File Manual, 82 pages, Read Online | Download pdf file

LUU248HV photo
Loading ...
Loading ...
Loading ...
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
PRODUCT DATA | 55
Product Data
Table 29: Cooling Capacity Table for LUU428HV + LVN420HV.
Cooling Capacity Table for LV420HV (LUU428HV + LVN420HV)
Outdoor
Air
Temp.
(°F DB)
Indoor Air Temp. °F DB / °F WB
68 / 57 72 / 61 77 / 64 80 / 67 86 / 72 90 / 75
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
-4 41.29 29.99 2.25 43.86 31.68 2.33 46.42 30.67 2.42 48.27 31.32 2.44 51.55 31.58 2.49 54.11 32.18 2.54
0 41.27 30.16 2.27 43.83 31.86 2.36 46.40 30.85 2.44 48.25 31.50 2.47 51.52 31.77 2.52 54.08 32.37 2.57
5 41.24 30.42 2.31 43.80 32.14 2.39 46.36 31.12 2.48 48.21 31.77 2.51 51.48 32.04 2.56 54.04 32.65 2.61
10 41.20 30.67 2.34 43.76 32.39 2.43 46.32 31.37 2.52 48.17 32.03 2.55 51.44 32.30 2.59 54.00 32.91 2.65
15 41.17 30.91 2.38 43.73 32.65 2.46 46.29 31.61 2.55 48.13 32.28 2.58 51.40 32.55 2.63 53.96 33.17 2.69
20 41.14 31.15 2.41 43.70 32.91 2.50 46.25 31.86 2.59 48.10 32.53 2.62 51.36 32.81 2.67 53.92 33.43 2.72
25 41.11 31.39 2.45 43.66 33.16 2.54 46.22 32.11 2.63 48.06 32.78 2.66 51.32 33.06 2.71 53.88 33.69 2.76
30 41.08 31.63 2.48 43.63 33.41 2.57 46.18 32.35 2.66 48.02 33.04 2.70 51.28 33.31 2.75 53.83 33.95 2.80
35 41.05 31.87 2.51 43.60 33.67 2.61 46.15 32.60 2.70 47.99 33.29 2.73 51.24 33.57 2.78 53.79 34.20 2.84
40 41.02 32.11 2.55 43.56 33.92 2.64 46.11 32.85 2.74 47.95 33.54 2.77 51.20 33.82 2.82 53.75 34.46 2.88
45 40.98 32.35 2.58 43.53 34.18 2.68 46.07 33.09 2.78 47.91 33.79 2.81 51.17 34.07 2.86 53.71 34.72 2.92
50 40.95 32.59 2.62 43.50 34.43 2.71 46.04 33.34 2.81 47.88 34.04 2.84 51.13 34.32 2.90 53.67 34.97 2.96
55 40.92 32.83 2.65 43.46 34.68 2.75 46.00 33.58 2.85 47.84 34.29 2.88 51.09 34.58 2.94 53.63 35.23 2.99
60 40.89 33.07 2.69 43.43 34.93 2.78 45.97 33.82 2.89 47.80 34.54 2.92 51.05 34.83 2.97 53.59 35.49 3.03
65 40.86 33.31 2.72 43.40 35.18 2.82 45.93 34.07 2.92 47.77 34.78 2.96 51.01 35.08 3.01 53.55 35.74 3.07
70 40.83 33.54 2.75 43.36 35.43 2.85 45.90 34.31 2.96 47.73 35.03 2.99 50.97 35.33 3.05 53.50 36.00 3.11
75 39.84 32.99 2.90 42.37 34.90 3.01 44.90 33.83 3.12 46.73 34.57 3.15 49.96 34.90 3.21 52.49 35.59 3.28
80 38.86 32.43 3.05 41.39 34.35 3.16 43.91 33.33 3.28 45.73 34.09 3.32 48.95 34.46 3.38 51.48 35.17 3.45
85 37.89 31.84 3.20 40.41 33.77 3.32 42.92 32.81 3.44 44.74 33.58 3.48 47.96 33.99 3.54 50.47 34.73 3.61
90 36.91 31.23 3.35 39.43 33.18 3.47 41.94 32.28 3.60 43.75 33.07 3.64 46.96 33.52 3.71 49.47 34.27 3.78
95 35.86 30.91 3.50 38.36 32.88 3.62 40.85 32.04 3.76 42.00 32.34 3.80 45.85 33.34 3.87 48.35 34.12 3.95
100 34.98 30.08 3.65 37.48 32.05 3.78 39.98 31.27 3.92 41.46 31.84 3.96 44.98 32.62 4.04 47.47 33.42 4.12
105 34.11 29.25 3.79 36.61 31.22 3.93 39.11 30.51 4.08 40.91 31.34 4.12 44.10 31.90 4.20 46.60 32.72 4.28
110 33.24 28.25 3.94 35.74 30.21 4.09 38.23 29.57 4.24 40.04 30.40 4.28 43.23 31.00 4.36 45.73 31.83 4.45
115 32.37 27.41 4.09 34.86 29.36 4.24 37.36 28.78 4.40 39.17 29.63 4.45 42.36 30.26 4.53 44.86 31.10 4.62
118 31.84 27.21 4.18 34.34 29.18 4.33 36.84 28.64 4.49 38.64 29.50 4.54 41.83 30.16 4.63 44.33 31.02 4.72
122 31.67 27.14 4.30 34.16 29.12 4.46 36.66 28.59 4.62 38.47 29.45 4.67 41.66 30.12 4.76 44.16 30.99 4.86
PERFORMANCE DATA
Cooling Capacity Tables
DB: Dry Bulb Temperature (°F) WB: Wet Bulb Temperature (°F) TC: Total Capacity
(kBtu/h)
SHC: Sensible Capacity (kBtu/h) PI: Power Input (kW) (includes compressor, indoor fan
motor and outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Cooling operating range with the Low Ambient Baffle Kit (sold separately) is -4°F to
+122°F.
3. Grey shading indicates reference data. When operating the unit at this temperature,
these values can be different by discontinuous operation.
4. Direct interpolation is permissible.
Do not extrapolate.
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry
bulb (DB) and 67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb
(DB) and 75ºF wet bulb (WB).