TROUBLESHOOTING & REFERENCES
J-8
ENGLISH
Topic TitleResistance Values
Cassette Louver Motor
Red
Orange 200 Ω
Yellow 200 Ω
Blue 200 Ω
Violet 200 Ω
Ducted Horizontal & Vertical Louver Motors
Red
Blue
200 Ω
Violet 200 Ω
Yellow 200 Ω
Orange 200 Ω
Highwall Horizontal Louver Motor (FlexFit)
Blue Violet Yellow Orange Red
Blue
- 393 Ω 394 Ω 395 Ω 196 Ω
Violet - - 396 Ω 397 Ω 198 Ω
Yellow - - - 398 Ω 199 Ω
Orange - - - - 200 Ω
Red - - - - -
Highwall Vertical Louver Motor (FlexFit)
Blue Violet Yellow Orange Red
Blue
- 383 Ω 388 Ω 390 Ω 195 Ω
Violet - - 381 Ω 385 Ω 189 Ω
Yellow - - - 388 Ω 193 Ω
Orange - - - - 196 Ω
Red - - - - -
EEV (6-pin, 6 wire)
White Yellow Orange Blue Brown Red
White - OL 92 Ω OL 46 Ω OL
Yellow - - OL 92 Ω OL 46 Ω
Orange - - - OL 46 Ω OL
Blue - - - - OL 46 Ω
Brown - - - - - OL
Red - - - - - -
EEV (6-pin, 5 wire)
White Yellow Orange Blue X Red
White - 92 Ω 92 Ω 92 Ω - 46 Ω
Yellow - - 92 Ω 92 Ω - 46 Ω
Orange - - - 92 Ω - 46 Ω
Blue - - - - - 46 Ω
X - - - - - -
Red - - - - - -
Highwall Horizontal Louver Motor
Orange Yellow Pink Blue Grey
Red
193 Ω 189.5 Ω 185.4 Ω 191.5 Ω -
Orange - 381.6 Ω 377.4 Ω 383.3 Ω 47 Ω
Yellow - - 373.9 Ω 379.9 Ω -
Pink - - - 375.8 Ω 46.8 Ω
Blue - - - - -
Grey - - - - -
Highwall Vertical Louver Motor
Yellow Orange Blue Red Grey
White - 92.6 Ω - 47 Ω -
Yellow - - 93.1 Ω - 47 Ω
Orange - - - 46.5 Ω -
Blue - - - - 46.8 Ω
Red - - - - -
Grey - - - - -