Installation Instructions (cont'd)
Venting (cont'd)
All vent gasesmust be completely vented to the outdoors of the
structure (dwelling,). Iustal[only the dra_ hood provided with
the new water heater and no other drafthood.
Vent pipes must be secured ateach joint with sheet metal screws.
TO
CHIMNEY
I
t
VENT PIPE INSTALLATION
There must be a minimum of 6" clearance between single wall
vent pipe and any combustible material. Fill and seal any clear-
ance between single wall vent pipe and combustible material
with mortar mix, cement, or other noncombustible substance.
For other than single wall, follow vent pipe manufacturer's clear-
ance specifications. To insure a tight fit of the vent pipe in a
brick chimney, seal around the vent pipe with mortar mix
cement.
Gas Piping
AWARNING
Make sure the gas supplied is the same type listed on the
model rating plate. The inlet gas pressure must not exceed
14 inchesw_. column ½ pound per square inch (3_kPa)]. I
The minimum mint gas pressure listed on the mdel rating
plate isfor the purpose of input edjus_,neat. [
I AWARNING I
if thegas€on valve pressures exceeding'A.I
pound per square inch (3.SkPa), the.damage to the gascon I
trol valve €ouldresult in a fire or explosionfrom leaking ga_ ]
AWARNING ]
If the main gas line s_gas appliances is used,]
also turn "off" the gas at each appliance. Leave all gasappli- |
ances sbutoff until the water heator installation iscomplete. ]
AWARNING
Failureto haverequiredclearancesbetweenventpipingandI
combustiblematerialwillresultinafire hazard.
AWARNING [
Besureventpipeisproperlyconnectedto preventescapeof
dangerousfluegaseswhich couldcausedeadlyasphyxiation.
AWARNING
Chemicalvaporcorrosionof the flue and vent systemmay
occurif air for combustioncontainscertainchemicalvapors.
Spraycanpropellants,cleaningsolvents,refrigerator and air
conditionerrefrigerants, swimmingpoolchemicals,calcium
and sodiumchloride,waxes,bleach,and processchemicalsare
typicalcompoundswhicharepotentiallycorrosive.
A gas line of sufficient size must be run to the water heater.
Consult the latest edition of National Fuel Gas Code ANSI
Z223.1, also referredto asNFPA54 and the gas company concern-
ing pipe size.
There must be:
A readily accessible manual shut off valve in the gas supply line
serving the water heater, and
A drip leg (sediment trap) ahead of the gas control valve to help
prevent dirt and foreign materials from entering the gas control
valve.
A flexible gas connector or a ground joint union between the
shutoffvalve and control valve to permit servicing of the unit.
Be sure to check all the gas piping for leaks before lighting the
water heater. Use a soapy water solution, not a match or open
flame. Rinse offsoapy solution and wipe dry.
Standard Models are for installation up to 3,300 feet above sea
level.
High Altitude Models are for installation from 3,300 to 5,500
feet above sea level.
Ifa standard model is installed above 3,300 feet or a high altitude
model is installed above 5,500 feet, the input rating must be
reduced at the rate of 4 percent for each 1,000 feet above sea level.
Contact your local Sears Service Center or gas utility for further
information.
AWARNING I
The appliance and its gas connection must be leak tested
before plac ngthe applance in operation.
14