Bose FS FS 4CE Loudspeaker

User Manual - Page 9

For FS FS 4CE.

PDF File Manual, 100 pages, Read Online | Download pdf file

FS FS 4CE photo
Loading ...
Loading ...
Loading ...
English 9Installation Guide FreeSpace FS4CE
PRO.BOSE.COM
Installation
Safety and Regulatory Compliance
The Bose FreeSpace FS4CE loudspeaker has passed testing and complies with the following specifications and uses:
Listed to ANSI/UL 1480-2016, CAN/ULC-S541
Fire Protective Signaling Use – UL Category UUMW/UUMW7, File Number S 3241. Control Number 42S9.
Not for use with DC-supervised systems.
Suitable for use indoors in dry locations.
EN 54-24: 2008, Loudspeaker for Voice Alarm Systems for Fire Detection and Fire Alarm Systems for Buildings
Environmental: Type B (outdoor applications)
Suitable for installation using Class 1, Class 2, or Class 3 wiring methods in accordance with NFPA 70, National Electric Code, 2002, Article 640.
Suitable for use with fire alarm circuit wiring methods in accordance with NFPA 70, National Electric Code, 2002, Article 760.
Suitable for use in air handling plenum spaces.
UL-2043, Fire Test and Visible Smoke Release for Discrete Products and their Accessories Installed in Air Handling Spaces.
NFPA 70, National Electric Code, 2002, Article 300-22 (c).
NFPA 90-A, 2002, Installation of Air Conditioning and Ventilation Systems, Paragraph 4.3.10.2.6.5.
EMC Directive 89/336/EEC and Article 10 (1) of the directive, EN50081-1 and EN50082-1 as signified by the CE mark.
The FreeSpace FS4CE loudspeaker has been designed to the requirements defined in the following European regulatory specification for combination
systems:
British Standard Code of Practice BS 5839, Part 8, when used with the ceramic terminal block and thermal fuse.
Tested to IEC60268-5.
Nominal Coverage Angle (per UL 1480) Vertical: 130°/50° at –3 dB; 160°/20° at –6 dB
Horizontal: 135°/50° at –3 dB; 165°/15° at –6 dB
UL Sensitivity Wattage Tap Sound Pressure Level dBA at 3.1 meters (10 feet):
Wattage CAN/ULC-S541
Canada
Tap 70 V 100 V
2.5 W 83.9 dBA
5 W 86.4 dBA 86.9 dBA
10 W 89.3 dBA 89.4 dBA
20 W 92.1 dBA 92.4 dBA
40 W 94.2 dBA 94.8 dBA
8 Ω 93.8 dBA
SPLs given are per the UL 1480 specified reporting method.
Frequency response:
Fire alarm (UL): 80 Hz to 17000 Hz
Attaching the Grille
Note: Before attaching the grille, adjust the loudspeaker tap
settings to the appropriate setting for the installation. See
Loudspeaker Settings on page 6.
After determining the logo alignment appropriate for
the installation, line up the grille with the inside of the
loudspeaker enclosure and push upward until it is secured
into place. If necessary, push the grille tabs inward to
properly fit into the loudspeaker enclosure.
Removing the Grille
Insert a small tool (no larger than 1.5 millimeters in diameter) through the grille perforation at the edge of the grille and
pull to disengage the grille.
CAUTION: Do not use a screwdriver to pry the grille from the enclosure. This could result in damage to the
loudspeaker.
2531
Bose Corporation
100 The Mountain Rd, Framingham, MA 01701
20
DOP 434849-9
EN 54-24: 2008
FreeSpace FS4CE
For DOP 434849-9, see pro.Bose.com/FS4CEDOP_UK
Provided options:
Type B
Loudspeaker for voice alarm systems for fire detection and fire
alarm systems for buildings
Wattage ANSI/UL 1480-2016
United States
Tap 70 V 100 V
2.5 W 79.2 dBA
5 W 81.7 dBA 80.9 dBA
10 W 84.6 dBA 84.5 dBA
20 W 87.3 dBA 87.2 dBA
40 W 89.7 dBA 89.8 dBA
8 Ω 90.1 dBA
Loading ...
Loading ...
Loading ...