Inverter Window Air Conditioner
09
associated parts, appropriate fire extinguishing equipment shall be avail-
able to hand. Have a dry powder or CO2 fire extinguisher adjacent to the
charging area.
6)No ignition sources
No person carrying out work in relation to a refrigeration system which
involves exposing any pipe work that contains or has contained flammable
refrigerant shall use any sources of ignition in such a manner that it may
lead to the risk of fire or explosion. All possible ignition sources, including
cigarette smoking, should be kept sufficiently far away from the site of
installation, repairing, removing and disposal, during which flammable
refrigerant can possibly be released to the surrounding space. Prior to work
taking place, the area around the equipment is to be surveyed to make
sure that there are no flammable hazards or ignition risks. No Smoking
signs shall be displayed.
7)Ventilated area
Ensure that the area is in the open or that it is adequately ventilated
before breaking into the system or conducting any hot work. A degree of
ventilation shall continue during the period that the work is carried out. The
ventilation should safely disperse any released refrigerant and preferably
expel it externally into the atmosphere.
8)Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the
purpose and to the correct specification. At all times the manufacturer's
maintenance and service guidelines shall be followed. If in doubt consult
the manufacturer's technical department for assistance. The following
checks shall be applied to installations using flammable refrigerants:
• The charge size is in accordance with the room size within which the
refrigerant containing parts are installed;
• The ventilation machinery and outlets are operating adequately and are
not obstructed;
• If an indirect refrigerating circuit is being used, the secondary circuit shall
be checked for the presence of refrigerant; Marking to the equipment
continues to be visible and legible. Markings and signs that are illegible
shall be corrected;
• Refrigeration pipe or components are installed in a position where they
are unlikely to be exposed to any substance which may corrode
refrigerant containing components, unless the components are
constructed of materials which are inherently resistant to being corroded
or are suitably protected against being so corroded.
9)Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety
checks and component inspection procedures. If a fault exists that could
compromise safety, then no electrical supply shall be connected to the
circuit until it is satisfactorily dealt with. If the fault cannot be corrected