Loading ...
Loading ...
Loading ...
11
Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
GENERAL DATA
Table 2: Single Zone Standard Efciency System Specications.
System Model Number (IDU/ODU)
LS090HFV3
(LSN090HFV3 /
LSU090HFV3)
LS120HFV3
(LSN120HFV3 /
LSU120HFV3)
LS180HFV3
(LSN180HFV3 /
LSU180HFV3)
LS240HFV3
(LSN240HFV3 /
LSU240HFV3)
Cooling Capacity (Min/Rated/Max) (Btu/h)
3,070 ~ 9,000 ~10,330 3,070 ~ 12,000 ~ 13,780 3,685 ~ 18,000 ~ 18,493 3,685 ~ 22,000 ~ 24,000
Cooling Power Input
1
(kW)
0.82 1.25 1.65 2.2
Heating Capacity (Min/Rated/Max) (Btu/h)
3,070 ~ 10,900 ~ 12,520 3,070 ~ 12,000 ~ 13,780 3,685 ~ 19,000 ~ 22,997 3,685 ~ 22,000 ~25,260
Heating Power Input
1
(kW)
0.95 1.05 1.74 2.02
COP
11.47 11.43 10.92 10.86
Max. Heating Capacity (Btu/h)
Outdoor 17°F (WB)/Indoor 70°F (DB)
8,760 (80%) 9,640 (80%) 15,270 (80%) 17,680 (80%)
EER
10.98 9.60 10.91 10.00
SEER
17 17 17 17
HSPF
9.0 9.0 9.0 9.0
Power Supply (V/Hz/Ø)
208-230/60/1
Outdoor Unit Operating Range
Cooling (°F DB)
14 to 118
Heating (°F WB)
14 to 65
Indoor Unit Operating Range
Cooling (°F WB)
53 to 75
Heating (°F DB)
60 to 86
Indoor Temperature Setting Range
Cooling (°F)
64 to 86
Heating (°F)
60 to 86
Unit Data
Refrigerant Type
2
R410A
Refrigerant Control
EEV
IDU Sound Pressure
3
dB(A) (H/M/L/Sleep)
42 / 36 / 28 / 21 42 / 36 / 28 / 21 48 / 43 / 38 / 32 48 / 43 / 38 / 32
ODU Sound Pressure
3
dB(A)
50 50 55 55
Unit Weight (lbs)
IDU (Net / Shipping)
19.2 / 25.4 19.2 / 25.4 26 / 30 26 / 30
ODU (Net / Shipping)
55.3 / 60 55.3 / 60 98.1 / 108 98.1 / 108
Power/Communication Cable
4
(No. x AWG)
4 x 14
Compressor
Compressor Type (Qty)
Twin Rotary (1)
Fan
Indoor Unit Type (Qty)
Cross Flow (1)
Outdoor Unit Type (Qty)
Propeller (1)
Motor/Drive
Brushless Digital Controlled/Direct
Airflow Rate
Indoor Unit Max/H/M/L (CFM)
459 / 353 / 264 / 148 459 / 353 / 264 / 148 689 / 512 / 459 / 371 689 / 512 / 459 / 371
Outdoor Unit (Max. [CFM])
953 953 1,730 1,730
Piping
Liquid Line (in, OD)
1/4 1/4 1/4 1/4
Vapor Line (in, OD)
3/8 3/8 1/2 1/2
Condensation Line (OD, ID)
27/32, 5/8 27/32, 5/8 27/32, 5/8 27/32, 5/8
Additional Refrigerant Charge (oz/ft)
0.22 0.22 0.26 0.26
Pipe Length
5
(Minimum/Maximum)(ft)
9.8 / 49.2 9.8 / 49.2 9.8 / 65.6 9.8 / 65.6
Piping Length
5
(no add’l refrigerant, ft)
24.6 24.6 24.6 24.6
Max Elevation Difference (ft)
23 23 32.8 32.8
EEV: Electronic Expansion Valve IDU: Indoor Unit ODU: Outdoor Unit
This unit comes with a dry helium charge.
This data is rated 0 ft above sea level with 24.6 of refrigerant line per indoor unit and a 0 ft level
difference outdoor and indoor units.
Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 59ºF wet
bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1
Power Input is rated at high speed.
2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A
refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3
Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4
All communication / connection (power) cable from the outdoor unit to the indoor unit is field supplied
and must be a minimum of four-conductor, 14 AWG, stranded, shielded or unshielded (if shielded, it
must be grounded to the chassis of the outdoor unit only), and must comply with applicable local and
national codes. For detailed electrical information, please see the Electrical Data section.
5
Piping lengths are equivalent.
Specications
Loading ...
Loading ...
Loading ...