U-Line U3036WCWCS00B Modular 3000 Series 36 Inch Stainless Steel Wine Cooler

User Manual - Page 60

For U3036WCWCS00B.

PDF File Manual, 65 pages, Read Online | Download pdf file

U3036WCWCS00B photo
Loading ...
Loading ...
Loading ...
USER GUIDE
Thermistor 1
u-line.com
SAFETY • INSTALLATION & INTEGRATION • OPERATING INSTRUCTIONS • MAINTENANCE • SERVICE
Thermistors
Thermistors are used for various temperature readings.
Thermistors provide reliable temperature readings using a
resistance which varies based on surrounding
temperatures. If a faulty thermistor is suspected it may
be tested using an accurate ohmmeter.
All thermistors in the unit are identical. If a thermistor is
suspected of being defective the resistance can be
verified. Place the thermistor in an ice water bath, the
resistance should read 16.1k OHMs +/-5% on your meter.
Thermistor connections must be kept clean. A thermistor
connection that has become corroded can cause
resistance values from the thermistor to change as they
pass through a dirty connection to the board.
It is for that reason that we apply dielectric grease to all of
our thermistor connections. Dielectric grease will help to
keep thermistor connections clean and dry.
If you change a thermistor in the unit please re-apply
dielectric grease to the connection. If you encounter a
dirty thermistor connection, you should replace the
thermistor and the thermistor harness.
Thermistor error information can be found in the Control
Operations - Service section.
This unit has five thermistors.
Thermistor one (Zone):
Located along the right hand side wall in the top/left
compartment. It is used to maintain the operating
temperature within that zone.
Thermistor two (Evaporator):
Located on the evaporator in the top/left compartment. It
is used for defrost.
Thermistor three (Zone):
Located along the right hand side wall in the bottom/right
compartment. It is used to maintain the operating
temperature within that zone.
Thermistor four (Evaporator):
Located on the evaporator in the bottom/right
compartment. It is used for defrost.
Thermistor five (Ambient):
Located in the base of the unit (secured to the
condenser). It is used to monitor the ambient temperature
within the base compartment. It is used for diagnostics.
THERMISTOR FAILURE
Zone Thermistors
If a zone thermistor(s) in the unit fails the unit will
continue to cool in a backup mode (Self Preservation
Mode) to preserve the integrity of the contents. The unit
will otherwise operate normally.
2000 Series Self Preservation Mode:
The unit will cycle on for 10 minutes then off for 40
minutes.
3000 Series Self Preservation Mode:
Cycle times determined by zone - see chart. The error will
be displayed on the main display, “Self Test” and logged in
All Errors.
Self Preservation Mode Data Table - 3000 Series
Mode ON OFF
Beverage/Drinks 10 45
Market/Fresh 10 45
Root 5 90
Pantry 10 45
Deli 10 45
White Wine 5 60
Red Wine 5 60
Sparkling Wine 10 60
Polar 55 5
60