Installation Instructions (cont'd)
Venting (cont'd) Gas Piping
All vent gases must be completely vented to the outdoors of the
structure (dwelling). Installonly the draft hood provided with
the new water heater and no other draft hood.
Vent pipes must be secured at each joint with sheet metal screws.
CHITHONEY
R I I
!
VENT PIPE INSTALLATION
There must be a minimum of 6" clearance between single wall
vent pipe and any combustible material. Fill and seal any clear-
ance between single wall vent pipe and combustible material
with mortar mix, cement, or other noncombustible substance.
For other than single wall, follow vent pipe manufacturer's clear-
ance specifications. To insure a tight fit of the vent pipe in a
brick chimney, seal around the vent pipe with mortar mix
cement.
AWARNING
Failureto haverequired clearancesbetweenvent pipingand
combustiblematerialwillresult ina Erehazard.
AWARNING
Besureventpipeisproperlyconnectedto preventescapeof
dangerousfluegaseswhichcouldcausedeadlyasphyxiation.
_,WARNING
Chemical vapor corrosionof the flue and vent systemmay
occurif air for combustioncontainscertainchemicalvapors.
Spraycan propellants,cleaningsolvents,refrigerator and air
conditioner refrigerants,swimmingpool chemicals,calcium
andsodiumchloride,waxes,bleach,andprocesschemicalsare
typicalcompoundswhicharepotentiallycorrosive.
AWARNING
Make sure the gassuppliedisthe same type listedon the
model rating plate.The inletgaspressuremustnot exceed
10.5in.water column(2.6kPa)for naturalgasor 13in.water
column(3.2kPa) for propane(I-R) gas.The minimum inlet
gaspressurelistedon the model rating plate isfor the pur-
poseofinputadjustment.
AWARNING , I
If the gascontrolvalveissubjectedto pressuresexceeding½
poundper squareinch(3.SkPa),the damageto the gascon-
tre valvecoudresut n a Ereor exposlonfrom eaknggas.
AWARNING
If the main gaslineshutoffserving all gasappliancesisused,
alsoturn "OFF" the gasat eachappliance. Leaveallgasappli-
ancesshutoffunt the water heater nstai at on scompete.
A gas line of sufficient size must be run to the water heater.
Consult the latest edition of National Fuel Gas Code ANSI
Z223.1, also referred to as NFPA 54 and the gas company con-
cerning pipe size.
There must be:
A readily accessible manual shut offvalve in the gas supply line
serving the water heater, and
A drip leg (sediment trap) ahead of the gas control valve to help
prevent dirt and foreign materials from entering the gas control
ValVe.
A flexible gas connector or a ground joint union between the
shutoff valve and control valve to permit servicing of the unit.
Be sure to check all the gas piping for leaks before lighting the
water heater. Use a soapy water solutiott, nor a match or opert
flame. Rinse offsoapy solution and wipe dry.
Standard ModeLs are for installatiott up to 3,300 feet above sea
level.
High Altitude Models are for installation from 3,300 to 5,500
feet above sea level.
lfa standard model is installed above 3,300 feet or a high altitude
model is installed above 5,500 feet, the input rating must be
reduced at the rate of 4 percent for each 1,000 feet above sea level.
Contact your local Sears Service Center or gas utility for further
information.