Electrical System Installation
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ELECTRICAL SYSTEM INSTALLATION
Do not install power wiring to the outdoor unit
and the communication / connection (power) cable
to the indoor unit in the same conduit. Use separate
conduits. Communication problems will occur.
Figure 99: Example of Conduit.
Connecting Outdoor Unit Wiring, continued.
6. Using a JIS screwdriver, connect wires as shown at right. See
also indoor unit wiring diagram found on its bottom cover, and
outdoor unit wiring diagram on the inside of its chassis cover.
Each wire must be individually and securely attached to each
terminal.
Loose, damaged, or cracked wires will cause electric shock, bodily
injury and / or death.
Loose wires can cause the wiring to burn out, damaging the outdoor
unit.
Secure wiring / cables with cable ties.
Pay attention to the location / connection of the ground cable.
Maintain a minimum of 1/4 inches of wire length from terminal block
to cable bundle.
7. When finished, reattach the piping / control box cover or con-
trol box cover (depends on model) to the outdoor unit with the
screws.
Figure 100: HEV2, HFV3, and HXV2 Outdoor Unit
Conduit Holes / Access Points.
Figure 101: Outdoor Unit Electrical Connections.
Outdoor Unit Electrical Connections
LS090-120HEV2, LS090-120HFV3 and LS090-120HXV2 indoor units and outdoor units have similar frames; however,
LS090-120HEV2 and LS090-120HFV3 systems require 208-230V, 60Hz, 1ph power supply. LS090-120HXV2 systems require
115V, 60Hz, 1ph power supply. Verify which system is being installed. An incorrect power supply will result in electric shock,
re, physical injury, or death.
LSU090-240HEV2, LSU090-240HFV3,
LSU090-120HXV2
LSU180-240HEV2 Outdoor Unit Terminal Block
LSU090-120HEV2 Outdoor Unit Terminal Block
LSU090-120HXV2 Outdoor Unit Terminal Block
LSU090-120HFV3 Outdoor Unit Terminal Block
LSU180-240HFV3 Outdoor Unit Terminal Block