3-Wire Conduit Installation
(See Figures 2.1, 2.5 and 2.6)
1. Remove the Terminal Block Access Plate on the back of the
range by unscrewing the 6 fixing Screws (fig. 2.1).
2. Feed 3/4" trade size Conduit through the hole in the Conduit
Bracket and secure to the Conduit Bracket with a Conduit
Clamp.
3. Remove the 3 wire terminal nuts and washers from the
Terminal Block.
4. Plug the terminal holes of conductors. The Neutral or Ground
Wire of the Power Cord must be connected to the neutral
terminal located in the center of Terminal Block. The Power
Wires must be connected to the outside terminals.
5. Plug washers and tighten nuts securely.
Do not remove Ground strap.
6. Assemble the Terminal Block Access Plate.
4-Wire Conduit Installation
(See Figures 2.1, 2.5 and 2.7)
1. Remove the Terminal Block Access Plate on the back of the
range by unscrewing the 6 fixing Screws (fig. 2.1).
2. Feed 3/4" trade size Conduit through the hole in the Conduit
Bracket and secure to the Conduit Bracket with a Conduit
Clamp.
3. Remove the 3 wire terminal nuts and washers from the
Terminal Block.
4. Remove the Ground Strap from the frame of range and
terminal by removing its screw and cutting it as shown in
Figure 2.7.
5. Plug the terminal holes of conductors. The Neutral Wire of
the Power Cord must be connected to the neutral terminal
located in the center of Terminal Block; the Power Wires
must be connected to the outside terminals; the Ground
Wire must be attached to the frame of range by using the
(Ground) identified Grounding Screw.
6. Plug washers and tighten nuts securely.
7. Assemble the Terminal Block Access Plate.
Hole D 1" 1/8
(28.58 mm)
Counduit
Bracket
Power Wires
Terminal Block
Ground strap
Neutral Wire
Conduit
Conduit Clamp
Power Wires
Terminal Block
Neutral Wire
Grounding Wire
Cut Ground Strap
Grounding
Screw
Conduit
Conduit Clamp
Fig. 2.5
Fig. 2.6
Fig. 2.7
2