REPLACEMENT PROCEDURE FOR PARTS
IT IS RECOMMENDED THAT ALL OCEANAIRE UNITS BE
SERVICED BY A LICENSED TECHNICIAN
WARNINGTO AVOID INJURY, DISCONNECT UNIT POWER
PRIOR TO SERVICING
A. FAN MOTOR
1. Remove cabinet left-side panel (when looking at the front of the unit).
2. Evaporator fan motor—disconnect evaporator motor wires from evaporator fan
contactor and fan speed rocker switch.
3. For all model sizes 12, 18, 24, and 36, remove the screws securing motor and
inlet-ring to blower housing (all screws are external and visible), and remove blower
wheel-motor assembly. Remove the blower wheel set screw and disassemble the blower
wheel from the motor shaft and remove the motor.
For model size 60—loosen blower wheel shaft set screw, and remove the screws
securing the motor mount to the blower housing and remove motor and mount. Remove
the motor from the motor mount.
4. Install the new motor, reversing the removal procedure.
B. THERMOSTAT (NO BATTERIES REQUIRED)
1. Along both sides of the thermostat, insert a small flat blade screwdriver in the groove.
With a twisting motion, remove the cover plate from the sub base. Make sure the small
thermistor located near the top of the casing for temperature sensing, is not bent or
damaged.
2. To remove the thermostat sub-base, remove the 2 mounting screws and the 4 wires
(black, red, white, green). Make sure the 4 wires do not fall into the cabinet. Install
sub-base by reversing removal procedure.
C. CONDENSATE ALARM LIGHT
To replace the Condensate Alarm Light, disconnect the wires from the lamp and bend
the tinnerman clip retaining light and pull out. Install new light, reversing the procedure.
D. CONDENSATE PUMP
1. Remove brackets securing condensate pump in base pan.
2. Disconnect pump wire leads at Molex connectors. Remove retainer clamp and tubing.
3. Replace pump, install by reversing procedure.
E. HIGH PRESSURE SAFETY SWITCH
1. Remove cabinet right side panel, or rear panel of Model 60.
2. Remove flare nut that secures capillary to the refrigeration system high pressure side.
A Schrader valve is located in the discharge port, and allows removal without losing
the refrigerant charge.
3. Remove two screws that secure high pressure switch.
4. Disconnect wire leads from compressor contactor and condensate pump safety switch.
5. Install new High Pressure Control, reversing the procedure.
To gain access to compressor and compressor run capacitor, remove left side panel.