Mr. Heater Series Heater Operating Instructions and Owner’s Manual
SECTION 7
Wiring
Heatersarenormallycontrolledbythermostats.Linevoltage
thermostatsarewireddirectly(seeFigure15),24Vthermostatsare
wireddirectlyusingtheterminalsonburnerbox(seeFigure16).
HeatersmustbegroundedinaccordancewiththeNationalElectric
CodeANSI/NFPA-70orcurrentCanadianElectricalCode,CSA
C22.1.Heatersmayalsobecontrolledwithamanuallinevoltage
switchortimerswitchinplaceofthethermostat.
FIGURE 15: Line Voltage Thermostat Wiring
T
H
N
120v – 60 Hz
White
White
Green
Green
Supply Circuit
120v – 60 Hz
Supply Circuit
Burners
(Maximum – 2 per Thermostat)
Burners
(Maximum – 1 per Thermostat)
Black
Black
H
N
T
FIGURE 16: Low Voltage Thermostat Wiring
T
H
N
120v – 60 Hz
White
White
Green
Green
Supply Circuit
120v – 60 Hz
Supply Circuit
Burners
(Maximum – 2 per Thermostat)
Burners
(Maximum – 1 per Thermostat)
Black
Black
H
N
T
FIGURE 17: MR. Heater Burner Internal Wiring
• Ifanyoftheoriginalwireassuppliedwiththe
appliancemustbereplaced,itmustbereplacewith
wiringmaterialhavingatemperatureratingofatleast
105°Cand600volts.
• Eachburnermustbeelectricallygroundedin
accordancewiththeNationalElectricCodeANSI/NFPA
-70orcurrentCanadianElectricalCode,CSAC22.1.
FIGURE 18: MR. Heater Burner Internal Wiring Ladder Diagram
VAC
120
120V
24V
Black
Black
Purple
Yellow
Yellow
Black
Black
Black
Green
Green
Orange
Transformer
White
White
White
THERMOSTAT
White
Blue
Gas Valve
Air Switch
Ignitor
Sensor
Motor / Blower
Door Switch
Terminal
Bushing
120V
L2
(NEUTRAL)
White
White
White
White
White
White
Gray
Orange
Transfomer
Thermostat
Air Switch
Gas Valve
Door Switch
Motor / Blower
Ignitor
Sensor
Blue
Yellow
Yellow
Purple
Black
Black
Black
Black
L2 (HOT)
24V