Pioneer WYS020GMHI22M2 Air Conditioner Multi Split Heat Pump

Service Manual - Page 41

For WYS020GMHI22M2. Also, The document are for others Pioneer models: YN020GMFI22M2D, YN030GMFI22M3D, YN040GMFI22M4D, YN050GMFI22M5D

PDF File Manual, 82 pages, Read Online | Download pdf file

WYS020GMHI22M2 photo
Loading ...
Loading ...
Loading ...
8.4.1.6 Inverter module (IPM) malfunction diagnosis and solution.
Malfunction decision
conditions
When the voltage signal that IPM send to compressor drive
chip is abnormal, the display LED will show “P6” and AC will
turn off.
Supposed causes
Wiring mistake
IPM malfunction
Outdoor fan ass’y faulty
Compressor malfunction
Outdoor PCB faulty
Trouble shooting:
IPMmoduleprotection
Checkwhetherthevoltagerange
ofP‐NonIPMmoduleisnormal?
DC277‐356Vfor18‐27KBtu/h;
DC277‐410Vfor36K‐48KBtu/h
Yes
Yes
No
Yes
Checkwhethertheinput
powersupplyiscorrect?
208‐230V,1N,60Hz
No No
Regulateittocorrect,then
checkwhetherthesystem
canworknormally?
Checkwhetherthe
powersupplylineis
connectedcorrectlyand
tightly
Yes
Connectitcorrectly
andtightly,checkok
ornot?
No
Checkwhethertheconnecting
linebetweenmainboardand
theIPMmoduleisconnected
tightly
Yes
Connectittightly,
checkokornot?
No
No
No
Connectitwell,check
okornot?
Checkwhethertheconnecting
lineofthecompressoris
connectedcorrectlyortightly
ReplacetheIPMmodule,
checkwhetherthesystemcan
worknormally?
No
No
Replacethemainboard;check
whetherthesystemcanwork
normally?
No
Replacethecompressor,check
whetherthesystemcanwork
normally?
Checkwhetherthelines
inE‐partboxare
connectedtightly
Yes
Connectittightly,
checkokornot?
No
No
Yes
No
Replacethebridgerectifiers
Checkwhetherthebridgerectifiersare
normal?Usethemultimetertomeasure
theresistancebetweeneachtwo
terminals,checkwhetherthereisthe
conditionthatvalueofresistanceis0
Check whether the connecting line of
every reactor is normal? If the line is
broken,theresistanceofthetwoportsis
Check whether the PFC module
broken.
Replacetheconnectinglineor
reactororreplacethePFCmodule
Yes
No
No
Yes
Troubleissolved
Checkiftheoutdoorfan
runsproperlyortheoutdoor
unitventilationisgood.
No
ForACfanmodels, pleaserefer
to9.4 TroubleCriterionOfMain
Parts,checkwhetherthe
resistanceofthefanmotoris
normal.Ifnot,replacethefan
motor.
ForDCfanmodels,referto
thesolutionoffanspeedhas
beenoutofcontrolmalfunction
.Findoutthecauseandhaveit
solved.
Yes
Yes
Yes
Loading ...
Loading ...
Loading ...