MODEL CODE SETTINGS
2OWC12
2OAC/2OACH12
P1 = 85
P2 = 35
2OWC18
2OAC/2OACH18
P1 = 80
P2 = 50
2OWC24
2OAC/2OACH24
P1 = 70
P2 = 50
2OWC36
2OAC/2OACH36
P1 = 85
P2 = 35
2OWC60
2OAC/2OACH60
P1 = 85
P2 = 45
1) Plug in the power supply cord to power outlet.
2) Unit must be in the “OFF” mode.
3) Press these buttons on the thermostat in this sequence:
S TEMP SELECT
U UP
D DOWN
S TEMP SELECT
4) As the TEMP SELECT button is released, the display
will begin flashing P and a number. To adjust P
1 and other
numeric settings press the UP or DOWN button until
the proper value is displayed.
5 Use the “MODE” button to scroll through the
programmable parameters P
2 through P16.
6) If no buttons are pushed, the display will then return to
the “OFF” position after about 50 seconds.
TO CHECK THE NUMBER OF HOURS ON THE UNIT
1) Unplug unit.
2) Plug in unit.
3) When “888” appears in display, push and release
DOWN button.
4) The first set of numbers displayed reads thousands of
hours. 02 would be 2000 hours. 04 would be 4000
hours. 00 would be no thousand of hours.
5) The second set of numbers read hours directly. 58
would be 58 hours. 742 would be 742 hours.
6) Add the 2 number sets together for total hours.
03 and 486 would be 3486 hours. 01 and 59 would be
1059 hours.
HOURS REPRESENT COMPRESSOR “ON” TIME.
LAC…….. Low AC line power
HPF…….. High Pressure Fault (does not apply)
AAA…….Failed Air Sensor (unit will not run)
CON……. Empty Condensate Bucket or High
Pressure Switch needs re-setting
These are not default values, they are OceanAire factory values.
15
7) To cycle the evaporator fan with the
compressor, access code P-13. Press the up or
down button to switch to “CYC”, which means
cycle the fan with the compressor. The factory
default setting is “CON”, which means continuous
fan operation.