Installation Manual 49
Function
ENGLISH
18/24(1Ø) kBtu/h
48/54(1Ø) kBtu/h
30/36(1Ø) kBtu/h
DIP-SW
SW01N
60(1Ø) kBtu/h
DIP-SW01D
12345678910
DIP SW2
Adding the refrigerant in winter.
Setting Procedure
1. Set the Dip Switch as follow after shutting the power
source down.
2. Reset the power.
3. Check that the Red LED of PCB is on during work. (The indoor unit is operated by force.)
4 Add the specific amount of refrigerant.
12345678910
CAUTION
• When the green LED of PCB is on, compressor is going to be off because
of low pressure.
• You should return the Dip Switch to operate normally after finishing the
operation.
Forced Cooling Operation