Step 5:
Connect drain hose
By default, the drain hose is attached to the left-
hand side of unit (”left” when facing the back
of the unit). However, it can also be attached to
the right-hand side.
1.
To ensure proper drainage, attach the drain
hose on the same side that your refrigerant
piping exits the unit.
2.
Attach drain hose extension (sold
separately) to the end of drain hose.
3.
Wrap the connection point rmly with Teon
tape to create a good seal, and to prevent
leaks.
4.
For the portion of the drain hose that will
remain indoors, wrap it with foam pipe
insulation to prevent condensation.
5.
Remove the air filter and pour a small amount
of water into the drain pan to make sure that
water flows from the unit smoothly.
NOTE ON DRAIN HOSE
PLACEMENT
Make sure to arrange the drain hose
according to
Fig. 3.5 .
DO NOT
kink the drain hose.
DO NOT
create a water trap (siphon).
DO NOT
put the end of the drain hose
in water or in a container that will
collect water.
DUAL DRAIN HOLE LOCATIONS EXIST
The indoor unit has 2 drain connections on left and
right sides. Either one can be utilized. One side will
have a hose connected, while the other is plugged.
CORRECT
Make sure there are no
kinks, dents or siphons in
the drain hose, to ensure
proper drainage.
NOT CORRECT
Kink/siphon in the drain hose,
will create water traps.
NOT CORRECT
Do not place the end
of the drain hose in
water or in containers
that collect water. This
will prevent proper
drainage.
NOT CORRECT
Kink/siphon in the drain hose,
will create water traps.
Fig. 3.5
Fig. 3.6
Fig. 3.7
Fig. 3.8
Indoor Unit
Installation