En-2
3. Obstacles in front (blowing) only
When there is an obstacle in front of
theunitasshowninthegure,open
spaceabove,behind,andonthesides
oftheunitisrequired.
2. Front (blowing) side open
As long as space indicated
in the figure is provided, it
is allowed to install the unit
where obstacles are behind
and on the sides of the unit.
(Noobstacleabovetheunit)
FREE SPACE REQUIRED AROUND OUTDOOR UNIT
1-4. SELECTING THE INSTALLATION LOCATION
• Whereitisnotexposedtostrongwind.
• Whereairowisgoodanddustless.
• Whererainordirectsunshinecanbeavoidedasmuchaspossible.
• Whereneighboursarenotannoyedbyoperationsoundorhotair.
• Whererigidwallorsupportisavailabletopreventtheincreaseofopera-
tionsoundorvibration.
• Wherethereisnoriskofcombustiblegasleakage.
• Wheninstallingtheunit,besuretosecuretheunitlegs.
• Whereitisatleast3mawayfromtheantennaofTVsetorradio.Opera-
tionoftheairconditionermayinterferewithradioorTVreceptioninareas
wherereceptionisweak.Anampliermayberequiredfortheaffected
device.
• Installtheunithorizontally.
• Pleaseinstallitinanareanotaffectedbysnowfallorblowingsnow.In
areaswithheavysnow,pleaseinstallacanopy,apedestaland/orsome
bafeboards.
Note:
Itis advisable to make a piping loopnear outdoor unit so as to reduce
vibrationtransmittedfromthere.
500ormore
200ormore
350ormore
100ormore
1. Obstacles above
When there is no obstacle in front and
onthe sidesof theunit, itis allowed
toinstalltheunitwhereanobstacleis
abovetheunitonlyifthespaceshown
inthegureisprovided.
100ormore
500ormore
100ormore
Servicespace
350ormore
350ormore
6. Service space
Providespaceforserviceandmaintenanceasshowninthegure.
500ormore
100ormore
• Wheninstallingtheunitinanareathatisenclosedwithwallssuch
asaverandah,besuretohaveenoughspaceasshownbelow.
Inthiscase,theairconditioningcapacityandpowerconsumption
might deteriorate.
• Whenthereisalackofairoworthereisapossibilityofbecoming
shortcycle,installanoutletguideandmakesurethereisenough
spacebehindoftheunit.
• Wheninstallingtwoormoreunits,donotinstalltheunitsinfrontor
behind each other.
100ormore
200ormore
350ormore
500ormore
500ormore
(Unit:mm)
5. Obstacles in front, behind and on side(s)
4. Obstacles in front and behind
The unit can be used by at-
tachinganoptionaloutdoor
blowingguide(PAC-
SH96SG-E)(butbothsides
andtopareopen).
100ormore
500ormore
Blowingguide(PAC-SH96SG-E)
Heightoftheobstacleis1200orless
1-3. SELECTING OPTIONAL DIFFERENT-DIAMETER JOINTS
Ifthediameterofconnectionpipedoesnotmatchtheportsizeofoutdoorunit,useoptionaldifferent-diameterjointsaccordingtothefollowingtable.
Optionaldifferent-diameterjoints(portsizeofoutdoorunit
→
diameterofconnectionpipe)
MXZ-
4E80VAD
MXZ-
5E100VAD
Liquid/Gas
6.35(1/4)
→
9.52(3/8):PAC-493PI
9.52(3/8)
→
12.7(1/2):MAC-A454JP
9.52(3/8)
→
15.88(5/8):PAC-SG76RJ
12.7(1/2)
→
9.52(3/8):MAC-A455JP
12.7(1/2)
→
15.88(5/8):MAC-A456JP
Refertotheinstallationmanualofindoorunitforthediameterofconnectionpipeofindoorunit.
AUNIT 6.35(1/4)/12.7(1/2)
B-D
UNIT
B-EUNIT 6.35(1/4)/9.52(3/8)
(Unit:mm(inch))
Note:
Whenoperatingtheairconditionerinlowoutsidetemperature,besure
tofollowtheinstructionsdescribedbelow.
• Neverinstalltheoutdoorunitinaplacewhereitsairinlet/outletside
maybeexposeddirectlytowind.
• Topreventexposuretowind,installtheoutdoorunitwithitsairinlet
sidefacingthewall.
•
Topreventexposuretowind,itisrecommendedtoinstallabafeboard
on the air outlet side of the outdoor unit.
Avoidthefollowingplacesforinstallationwhereairconditionertrouble
is liable to occur.
• Whereammablegascouldleak.
• Wherethereismuchmachineoil.
• Whereoilissplashedorwheretheareaislledwithoilysmoke(such
ascookingareasandfactories,inwhichthepropertiesofplasticcould
bechangedanddamaged).
• Saltyplacessuchastheseaside.
• Wheresuldegasisgeneratedsuchasahotspring,sewage,waste
water.
• Wherethereishigh-frequencyorwirelessequipment.
• WherethereisemissionofhighlevelsofVOCs,includingphthalate
compounds,formaldehyde,etc.,whichmaycausechemicalcracking.
WG79A696H02_en.indd 2 2016/04/21 14:46:36