Mitsubishi MXZ-4E80VAD Split-type Air-Conditioner

Product's Documents

Below are documents related to this product, you can read online or download:
MXZ-4E80VAD photo

Installation Manual

This is the main product document for model MXZ-4E80VAD. Additionally, the document applies to other Mitsubishi models: MXZ-5E100VAD

The file format is pdf, 12 pages, you can download this manual here .

background
Installation Manual
For INSTALLER
• This manual only describes the installation of outdoor unit.
When installing the indoor unit, refer to the installation manual of indoor unit.
Split-type Air-Conditioner
MXZ-4E80VAD
MXZ-5E100VAD
English
WG79A696H02_en.indd 1 2016/04/21 14:46:35
background
En-1
1. BEFORE INSTALLATION
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
• Besuretoread“THEFOLLOWINGSHOULDALWAYSBEOBSERVEDFORSAFETY”beforeinstallingtheairconditioner.
• Besuretoobservethewarningsandcautionsspeciedhereastheyincludeimportantitemsrelatedtosafety.
• Afterreadingthismanual,besuretokeepittogetherwiththeOPERATINGINSTRUCTIONSforfuturereference.
• EquipmentcomplyingwithIEC/EN61000-3-12.
1-2. SPECIFICATIONS
CAUTION
(Couldleadtoseriousinjuryinparticularenvironmentswhenoperatedincorrectly.)
n Do not install the unit by yourself (user).
Incompleteinstallationcouldcausereorelectricshock,injuryduetotheunit
falling,orleakageofwater.Consultthedealerfromwhomyoupurchased
theunitoraqualiedinstaller.
n Perform the installation securely referring to the installation manual.
Incompleteinstallationcouldcause re,electricshock, injuryduetothe
unitfalling,orleakageofwater.
n When installing the unit, use appropriate protective equipment and
tools for safety.
Failuretodosocouldcauseinjury.
n
Install the unit securely in a place which can bear the weight of the unit.
Iftheinstallationlocationcannotbeartheweightoftheunit,theunitcould
fallcausinginjury.
n
Electrical work should be performed by a qualied, experienced electrician,
according to the installation manual. Be sure to use an exclusive circuit.
Do not connect other electrical appliances to the circuit.
If the capacity of the power circuit is insufcient or there is incomplete
electricalwork,itcouldresultinareoranelectricshock.
n Do not damage the wires by applying excessive pressure with parts
or screws.
Damagedwirescouldcausereorelectricshock.
n Be sure to cut off the main power in case of setting up the indoor P.C.
board or wiring works.
Failuretodosocouldcauseelectricshock.
n Use the specied wires to connect the indoor and outdoor units
securely and attach the wires rmly to the terminal block connecting
sections so the stress of the wires is not applied to the sections.
Do
not extend the wires, or use intermediate connection.
Incompleteconnectingandsecuringcouldcausere.
n Do not install the unit in a place where inammable gas may leak.
Ifgasleaksandaccumulatesintheareaaroundtheunit,itcouldcausean
explosion.
n Do not use intermediate connection of the power cord or the extension
cord and do not connect many devices to one AC outlet.
Itcouldcauseareoranelectricshockduetodefectivecontact,defective
insulation,exceedingthepermissiblecurrent,etc.
n
Be sure to use the parts provided or specied parts for the installation work.
Theuseofdefectivepartscouldcauseaninjuryorleakageofwaterdue
toare,anelectricshock,theunitfalling,etc.
n
When plugging the power supply plug into the outlet, make sure that there
is no dust, clogging, or loose parts in both the outlet and the plug. Make
sure that the power supply plug is pushed completely into the outlet.
Ifthereisdust,clogging,orloosepartsonthepowersupplyplugorthe
outlet,itcouldcauseelectricshockorre.Ifloosepartsarefoundonthe
powersupplyplug,replaceit.
n Attach the electrical cover to the indoor unit and the service panel
to the outdoor unit securely.
Iftheelectricalcoveroftheindoorunitand/ortheservicepanelofthe
outdoorunitarenotattachedsecurely,itcouldresultinareoranelectric
shockduetodust,water,etc.
n When installing, relocating, or servicing the unit, make sure that no
substance other than the specied refrigerant (R410A) enters the
refrigerant circuit.
Anypresenceofforeignsubstancesuchasaircancauseabnormalpres-
sureriseandmayresultinexplosionorinjury.Theuseofanyrefrigerant
otherthan that specied for thesystem will cause mechanical failure,
systemmalfunction,orunitbreakdown.Intheworstcase,thiscouldlead
toaseriousimpedimenttosecuringproductsafety.
n Do not discharge the refrigerant into the atmosphere. If refrigerant
leaks during installation, ventilate the room.
Ifrefrigerantcomesincontactwithare,harmfulgascouldbegenerated.
n Check that the refrigerant gas does not leak after installation has
been completed.
Ifrefrigerantgasleaksindoors,andcomesintocontactwiththeameofa
fanheater,spaceheater,stove,etc.,harmfulsubstanceswillbegenerated.
n Use appropriate tools and piping materials for installation.
ThepressureofR410Ais1.6timesmorethanR22.Notusingappropriatetools
ormaterialsandincompleteinstallationcouldcausethepipestoburstorinjury.
n When pumping down the refrigerant, stop the compressor before
disconnecting the refrigerant pipes.
Iftherefrigerantpipesaredisconnectedwhilethecompressorisrunning
andthestopvalveisopen,aircouldbedrawninandthepressureinthe
refrigeration cycle could become abnormally high. This could cause the
pipestoburstorinjury.
n When installing the unit, securely connect the refrigerant pipes
before starting the compressor.
Ifthecompressorisstartedbeforetherefrigerantpipesareconnected
andwhenthestopvalveisopen,aircouldbedrawninandthepressure
in the refrigeration cycle could become abnormally high. This could cause
thepipestoburstorinjury.
n Fasten a are nut with a torque wrench as specied in this manual.
Iffastenedtootight,aarenutmaybreakafteralongperiodandcause
refrigerantleakage.
n
The unit shall be installed in accordance with national wiring regulations.
n Earth the unit correctly.
Donotconnecttheearthtoagaspipe,waterpipe,lightningrodortel-
ephoneearth.Defectiveearthingcouldcauseelectricshock.
n Be sure to install an earth leakage breaker.
Failuretoinstallanearthleakagebreakermayresultinelectricshockorre.
n
Perform the drainage/piping work securely according to the installation manual.
Ifthereisdefectinthedrainage/pipingwork,watercoulddropfromtheunit,
soakinganddamaginghouseholdgoods.
n Do not touch the air inlet or the aluminum ns of the outdoor unit.
Thiscouldcauseinjury.
n Do not install the outdoor unit where small animals may live.
Ifsmallanimalsenterandtouchtheelectricpartsinsidetheunit,itcould
causeamalfunction,smokeemission,orre.Also,adviseusertokeep
the area around the unit clean.
WARNING
(Couldleadtodeath,seriousinjury,etc.)
*1 Connecttothepowerswitchwhichhasagapof3mmormorewhenopento
interruptthesourcepowerphase.(Whenthepowerswitchisshutoff,itmust
interruptallphases.)
*2 Usewiresinconformitywithdesign60245IEC57. Usetheindoor/outdoor
connecting wire in conformity with the wire specications specied in the
installation manual of the indoor unit.
*3 Neverusepipeswiththicknesslessthanspecied.Thepressureresistance
willbeinsufcient.
*4 Useacopperpipeoracopper-alloyseamlesspipe.
*5 Becarefulnottocrushorbendthepipeduringpipebending.
*6 Refrigerantpipebendingradiusmustbe100mmormore.
*7 Insulationmaterial:Heatresistingfoamplastic0.045specicgravity
*8 Besuretousetheinsulationofspeciedthickness.Excessivethicknessmay
causeincorrectinstallationoftheindoorunitandinsufcientthicknessmay
causedewdrippage.
*
9
If the outdoor unit is installed higher than the indoor unit, max. height dif-
ferenceisreducedto10m.
*
10
Ifpipelengthexceeds30m,additionalrefrigerant(R410A)chargeisrequired.
(for4E80VAD)
Additionalrefrigerant=A×(pipelength(m)-30)
Ifpipelengthexceeds5m,additionalrefrigerant(R410A)chargeisrequired.
(for5E100VAD)
Additionalrefrigerant=A×(pipelength(m)-5)
Required Tools for Installation
Phillipsscrewdriver
Level
Scale
Utilityknifeorscissors
Torquewrench
Wrench(orspanner)
4mmhexagonalwrench
FlaretoolforR410A
GaugemanifoldforR410A
VacuumpumpforR410A
ChargehoseforR410A
Pipecutterwithreamer
ENGLISH
CONTENTS
1.BEFOREINSTALLATION ............................................................1
2.OUTDOORUNITINSTALLATION ...............................................4
3.FLARINGWORKANDPIPECONNECTION ...............................5
4.PURGINGPROCEDURES,LEAKTEST,ANDTESTRUN .........6
5.PUMPINGDOWN ........................................................................ 7
Model
Powersupply*1 Wirespecications*2 Pipelengthandheightdifference
*3,*4,*5,*6,*7,*8
Rated
Voltage
Fre-
quency
Breaker
capacity
Power
supply
Indoor/
outdoor con-
nectingwire
Max.pipelength
perindoorunit/
for multi-system
Max.height
difference
*9
Max.no.ofbends
perindoorunit/
for multi system
Refrigerant
adjustment
A*10
MXZ-4E80VAD
230V 50Hz 25A
3-core
2.5mm
2
4-core
1.0/1.5mm
2
25m/70m
15m
25/70
20g/m
25m/80m 25/80
MXZ-5E100VAD
WG79A696H02_en.indd 1 2016/04/21 14:46:35
background
En-2
3. Obstacles in front (blowing) only
When there is an obstacle in front of
theunitasshowninthegure,open
spaceabove,behind,andonthesides
oftheunitisrequired.
2. Front (blowing) side open
As long as space indicated
in the figure is provided, it
is allowed to install the unit
where obstacles are behind
and on the sides of the unit.
(Noobstacleabovetheunit)
FREE SPACE REQUIRED AROUND OUTDOOR UNIT
1-4. SELECTING THE INSTALLATION LOCATION
• Whereitisnotexposedtostrongwind.
• Whereairowisgoodanddustless.
• Whererainordirectsunshinecanbeavoidedasmuchaspossible.
• Whereneighboursarenotannoyedbyoperationsoundorhotair.
• Whererigidwallorsupportisavailabletopreventtheincreaseofopera-
tionsoundorvibration.
• Wherethereisnoriskofcombustiblegasleakage.
• Wheninstallingtheunit,besuretosecuretheunitlegs.
• Whereitisatleast3mawayfromtheantennaofTVsetorradio.Opera-
tionoftheairconditionermayinterferewithradioorTVreceptioninareas
wherereceptionisweak.Anampliermayberequiredfortheaffected
device.
• Installtheunithorizontally.
• Pleaseinstallitinanareanotaffectedbysnowfallorblowingsnow.In
areaswithheavysnow,pleaseinstallacanopy,apedestaland/orsome
bafeboards.
Note:
Itis advisable to make a piping loopnear outdoor unit so as to reduce
vibrationtransmittedfromthere.
500ormore
200ormore
350ormore
100ormore
1. Obstacles above
When there is no obstacle in front and
onthe sidesof theunit, itis allowed
toinstalltheunitwhereanobstacleis
abovetheunitonlyifthespaceshown
inthegureisprovided.
100ormore
500ormore
100ormore
Servicespace
350ormore
350ormore
6. Service space
Providespaceforserviceandmaintenanceasshowninthegure.
500ormore
100ormore
• Wheninstallingtheunitinanareathatisenclosedwithwallssuch
asaverandah,besuretohaveenoughspaceasshownbelow.
Inthiscase,theairconditioningcapacityandpowerconsumption
might deteriorate.
• Whenthereisalackofairoworthereisapossibilityofbecoming
shortcycle,installanoutletguideandmakesurethereisenough
spacebehindoftheunit.
• Wheninstallingtwoormoreunits,donotinstalltheunitsinfrontor
behind each other.
100ormore
200ormore
350ormore
500ormore
500ormore
(Unit:mm)
5. Obstacles in front, behind and on side(s)
4. Obstacles in front and behind
The unit can be used by at-
tachinganoptionaloutdoor
blowingguide(PAC-
SH96SG-E)(butbothsides
andtopareopen).
100ormore
500ormore
Blowingguide(PAC-SH96SG-E)
Heightoftheobstacleis1200orless
1-3. SELECTING OPTIONAL DIFFERENT-DIAMETER JOINTS
Ifthediameterofconnectionpipedoesnotmatchtheportsizeofoutdoorunit,useoptionaldifferent-diameterjointsaccordingtothefollowingtable.
Optionaldifferent-diameterjoints(portsizeofoutdoorunit
diameterofconnectionpipe)
MXZ-
4E80VAD
MXZ-
5E100VAD
Liquid/Gas
6.35(1/4)
9.52(3/8):PAC-493PI
9.52(3/8)
12.7(1/2):MAC-A454JP
9.52(3/8)
15.88(5/8):PAC-SG76RJ
12.7(1/2)
9.52(3/8):MAC-A455JP
12.7(1/2)
15.88(5/8):MAC-A456JP
Refertotheinstallationmanualofindoorunitforthediameterofconnectionpipeofindoorunit.
AUNIT 6.35(1/4)/12.7(1/2)
B-D
UNIT
B-EUNIT 6.35(1/4)/9.52(3/8)
(Unit:mm(inch))
Note:
Whenoperatingtheairconditionerinlowoutsidetemperature,besure
tofollowtheinstructionsdescribedbelow.
• Neverinstalltheoutdoorunitinaplacewhereitsairinlet/outletside
maybeexposeddirectlytowind.
• Topreventexposuretowind,installtheoutdoorunitwithitsairinlet
sidefacingthewall.
•
Topreventexposuretowind,itisrecommendedtoinstallabafeboard
on the air outlet side of the outdoor unit.
Avoidthefollowingplacesforinstallationwhereairconditionertrouble
is liable to occur.
• Whereammablegascouldleak.
• Wherethereismuchmachineoil.
• Whereoilissplashedorwheretheareaislledwithoilysmoke(such
ascookingareasandfactories,inwhichthepropertiesofplasticcould
bechangedanddamaged).
• Saltyplacessuchastheseaside.
• Wheresuldegasisgeneratedsuchasahotspring,sewage,waste
water.
• Wherethereishigh-frequencyorwirelessequipment.
• WherethereisemissionofhighlevelsofVOCs,includingphthalate
compounds,formaldehyde,etc.,whichmaycausechemicalcracking.
WG79A696H02_en.indd 2 2016/04/21 14:46:36
background
En-3
1-5. INSTALLATION DIAGRAM
Unitsshouldbeinstalledbylicensedcontractoraccordingtolocalcoderequirements.
ACCESSORIES
Checkthefollowingpartsbeforeinstallation.
(1) Drainsocket 1
(2) Draincap 5
PARTS TO BE PROVIDED AT YOUR SITE
(A) Powersupplycord* 1
(B)
Indoor/outdoorunitconnectingwire
* 1
(C) Extensionpipe 1
(D) Wallholecover 1
(E) Pipingtape 1
(F)
Extension drain hose
(orsoftPVChose,15mminner
diameterorhardPVCpipeVP16)
1
(G) Refrigeration oil
Little
amount
(H) Putty 1
(I) Pipexingband 2to7
(J) Fixingscrewfor(I) 2to7
(K) Wallholesleeve 1
(L)
SoftPVChose,15mminner
diameterorhardPVCpipeVP16
fordrainsocket(1)
1
Note:
*Placeindoor/outdoorunitconnectingwire(B)and
powersupplycord(A)atleast1mawayfromthe
TVantennawire.
The“Q’ty”for(B)to(K)intheabovetableisquantity
tobeusedperindoorunit.
Morethan
100mm
Openasarule
Morethan500mm
if the front and both
sidesareopen
Morethan100mm
Morethan200mmifthereare
obstacles to both sides
Openasarule
Morethan500mmiftheback,
bothsidesandtopareopen
Morethan350mm
Outdoor unit installation
Air inlet
Air outlet
Air inlet
950mm
600mm
175
mm
2-U-shapenotchedholes
(BaseboltM10)
330mm
2-12mm×36mm
ovalholes(BaseboltM10)
370mm
417mm
After the leak test, apply insulat-
ing material tightly so that there
isnogap.
Whenthepipingistobeattachedto
awallcontainingmetals(tinplated)
or metal netting, use a chemically
treated wooden piece 20 mm or
thicker between the wall and the
pipingorwrap7to8turnsofinsula-
tionvinyltapearoundthepiping.
To use existing piping, perform
COOL operation for 30 minutes
and pump down before removing
theoldairconditioner.Remakeare
accordingtothedimensionfornew
refrigerant.
1-6. DRAIN PIPING FOR OUTDOOR UNIT
1) Performthedrainpipingworkonlywhendrainingfromoneplace.
2) Providedrainpipingbeforeindoorandoutdoorpipingconnection.
3) Attachthedrainsockettooneoftheseveraldrainholes.
Fixthedrainsocketintothedrainholeofthebaseusingthecatchestosecureit
inplace.
4) ConnectthesoftPVChoseI.D.15mmasshownintheillustration.
5) Makesuretoprovidedrainpipingwithadownhillgradeforeasydrainow.
6) Gluethedraincapstoclosealltheotherunnecessaryholeswiththeglue(Prepare
intheeld).
Note:
Applythegluesecurely,astheglue(Prepareintheeld)willworkassealtoprevent
waterfromleaking.
Usetheadhesivefortherubberandmetal.
Attention
Theoutdoorunitisprovidedwithseveralholesfordrainageatthebottomtomake
drainage easier.
Thedrainsocketisusedtoclosetheunnecessaryholesandcentralizethedrainage
whenusingthedraintubeattheinstallationplace.
Donottousethedrainsocketincoldregion.Thedraintubecanbefrozen.
(1)Drainsocket
(2)Draincap
(L)SoftPVChose
IMPORTANT NOTES
TocomplywiththerequirementsofAustralianstandardAS/NZS3000electricalinstallations
(wiring rules), the electrical wiring required between the indoor and outdoorunits must be
installed by a licenced electrical contractor.
WG79A696H02_en.indd 3 2016/04/21 14:46:36
background
En-4
2-1. INSTALLING THE UNIT
2-2. CONNECTING WIRES FOR OUTDOOR UNIT
• Besuretoxtheunit’slegswithboltswheninstallingit.
• Besuretoinstalltheunitrmlytoensurethatitdoesnotfallbyanearthquakeoragust.
• Refertothegureintherightforconcretefoundation.
• Donotusethedrainsocketandthedraincapsinthecoldregion.
Drainmayfreezeanditmakesthefanstop.
• Removethetapeonthepanelwhenopeningthepackage.(DONOTremovetheLABELSonthepanel.)
1)Removetheservicepanelandthecablecover.
2)Passtheindoor/outdoorunitconnectingwire(B)andpowersupplycord
(A)throughthegrommet.Loosenterminalscrew,andconnectindoor/
outdoorunitconnecting wire(B) fromtheindoor unitcorrectlyon the
terminalblock. Becareful notto makemis-wiring. Fixthe wire tothe
terminalblocksecurelysothatnopartofitscoreisappeared,andno
externalforceisconveyedtotheconnectingsectionoftheterminalblock.
3)Firmlytightentheterminalscrewstopreventthemfromloosening.After
tightening,pullthewireslightlytoconrmthattheydonotmove.
4)Perform2)and3)foreachindoorunit.
5)Connectpowersupplycord(A).
6)Fixindoor/outdoorunitconnectingwire(B)andpowersupplycord(A)
withthecableclamps.Routethecablesorwiressoasnottodeformthe
servicepanel.Otherwise,rainwatermayentertheoutdoorunit.
7)Closetheservicepanelandthecablecoversecurely.Makesurethat
3-2.PIPECONNECTIONiscompleted.
• Aftermaking connectionsbetween bothpower supplycord (A)and
indoor/outdoorunitconnectingwire(B),besuretoxbothcableand
wirewithcableclamps.
Connectingorder
• Connecttheterminalblockinfollowingorder.
Fixherewith
M10bolts.
Makethesetting
depthdeeper.
Makewidthwider.
Anchor leg
30orless
Anchor bolt length Anchorboltpitch
(Unit:mm)
5E100VAD
Terminalblock
forpowersupply
DRDR DR DR
Powersupply
Terminalblockfor
indoor/outdoorunit
600
370
2. OUTDOOR UNIT INSTALLATION
Servicepanel
Screws
Cable
cover
Cableclamp
MXZ-5E100VAD A
B
C
D
E
P
DR
MXZ-4E80VAD A
B
C
D
P
DR
TerminalblockforDREDinterface
Wire-to-wireconnector
WG79A696H02_en.indd 4 2016/04/21 14:46:38
background
En-5
Fig. 1 Fig.2
Fig.3 Fig.4
Fig.5 Fig.6
3-1. FLARING WORK
Pipediameter
(mm)
Nut
(mm)
A(mm) Tighteningtorque
Clutch
typetool
forR410A
Clutch
typetool
forR22
Wing nut
typetool
forR22
N•m kgf•cm
ø6.35(1/4”) 17
0to0.5 1.0to1.5
1.5to2.0
13.7to17.7 140to180
ø9.52(3/8”) 22 34.3to41.2 350to420
ø12.7(1/2”) 26
2.0to2.5
49.0to56.4 500to575
ø15.88(5/8”) 29 73.5to78.4 750to800
TiltedUnevenBurred
Good
No good
Burr
Copperpipe
Sparereamer
Pipecutter
Smooth all
around
Evenlength
all around
Inside is shin-
ingwithoutany
scratches.
Flare nut
Die
Copperpipe
Clutchtype
Flaring tool
Wingnuttype
3-2. PIPE CONNECTION
1)Applyathincoatofrefrigerationoil(G)tothearedendsofthepipesand
thepipeconnectionsoftheoutdoorunit.Donotapplyrefrigerationoilon
screwthreads.Excessivetighteningtorquewillresultindamageonthe
screw.
2)Alignthecenterofthepipewiththatofthepipeconnectionsoftheoutdoor
unit,thenhandtightenthearenut3to4turns.
3)Tightenthearenutwithatorquewrenchasspeciedinthetable.
•Over-tighteningmaycausedamagetothearenut,resultinginrefriger-
antleakage.
•Besuretowrapinsulationaroundthepiping.Directcontactwiththebare
pipingmayresultinburnsorfrostbite.
3-3. INSULATION AND TAPING
1)Coverpipingjointswithpipecover.
2)Foroutdoorunitside,surelyinsulateeverypipingincludingvalves.
3)Usingpipingtape(E),applytapingstartingfromtheentryofoutdoorunit.
• Stoptheendofpipingtape(E)withtape(withadhesiveagentattached).
• Whenpipinghavetobearrangedthroughaboveceiling,closetorwhere
thetemperatureandhumidityarehigh,windadditionalcommerciallysold
insulationtopreventcondensation.
Copper
pipe
1)Cutthecopperpipecorrectlywithpipecutter.(Fig.1,2)
2)Completelyremoveallburrsfromthecutcrosssectionofpipe.(Fig.3)
• Aimthecopperpipedownwardwhileremovingburrstopreventburrs
fromdroppinginthepipe.
3)Removearenutsattachedtoindoorandoutdoorunits,thenputthem
onpipehavingcompletedburrremoval.(Notpossibletoputthemon
afteraringwork.)
4)Flaringwork(Fig.4,5).Firmlyholdcopperpipeinthedimensionshown
in the table. Select A mm from the table according to the tool selected.
5)Check
• ComparethearedworkwithFig.6.
• Ifareisnotedtobedefective,cutoffthearedsectionanddoaring
workagain.
WARNING
When installing the unit, securely
connect the refrigerant pipes before
starting the compressor.
CAUTION
When there are the ports which are
not used, make sure their nuts are
tightened securely.
3. FLARING WORK AND PIPE CONNECTION
• Besuretoattacheachscrewtoitscorrespondentterminalwhensecuringthecordand/orthewiretotheterminalblock.
• Makeearthwirealittlelongerthanothers.(Morethan35mm)
• Forfutureservicing,giveextralengthtotheconnectingwires.
1 2 3 C
<OUTDOORUNIT>
Indoor/outdoorunit
connectingwire
<INDOORUNIT>
Terminalblock
POWERSUPPLY
~/N230V50Hz
Terminalblock Terminalblock
Terminalblockfor
powersupply
Terminalblock
ThisunithasdemandresponsecapabilitywhichiscompliantwithAS/NZS4755.3.1.Toactivatethisfunction,youneedtomakeacontractwithremote
agentssuchaselectricsupplycompany,thenthisunitshouldbeconnectedtoDemandresponseenablingdevise(DRED).Forfurtherinformation,
consultyourdealer.Thisunitsupports3DemandResponseModes(DRMs):DRM1,DRM2andDRM3.
CAUTION
•Topreventmalfunctioncausedbynoise,routethecordconnectingthisunittoDREDandthepowersupplycordasparallelaspossible.
•Donotconnectthedemandcontroltransmissioncabletotheterminalblockforpowersupply.
•Donotpull,extremelybendorapplystrongpressureonthewiretopreventfailure.
•DonotscrewDREDtooutdoorunit.
•DonotputDREDinoutdoorunit.
•Secureelectricalwiringaboveclamp.
•DonotgetDREDwirecaughtintheservicepanel.
1:DRM1
2:DRM2
3:DRM3
C:COMMON
AS/NZS4755
terminalblock
35mm
15mm
Leadwire
Model
INDOOR/
OUTDOORUNIT
MXZ-5E100VAD
A
E
MXZ-4E80VAD
A
D
WG79A696H02_en.indd 5 2016/04/21 14:46:39
background
En-6
4-1. PURGING PROCEDURES AND LEAK TEST
4-2. GAS CHARGE
Performgaschargetounit.
1)Connectgascylindertotheserviceportofstopvalve.
2)Performairpurgeofthepipe(orhose)comingfromrefrigerantgascylinder.
3)Replenishspeciedamountoftherefrigerant,whileoperatingtheairconditioner
for cooling.
Note:
Incaseofaddingrefrigerant,complywiththequantityspeciedfortherefrigerat-
ing cycle.
CAUTION:
Whenchargingtherefrigerantsystemwithadditionalrefrigerant,besuretouse
liquidrefrigerant.Addinggasrefrigerantmaychangethecompositionoftherefriger-
antinthesystemandaffectnormaloperationoftheairconditioner.Also,charge
theliquidrefrigerantslowly,otherwisethecompressorwillbelocked.
Tomaintain the high pressure of the gas cylinder,warm the gas cylinder with
warmwater(under40°C)duringcoldseason.Butneverusenakedreorsteam.
1)Removeserviceportcapofstopvalveonthesideoftheoutdoorunit
gaspipe.(Thestopvalvesarefullyclosedandcoveredincapsintheir
initialstate.)
2)Connectgaugemanifoldvalveandvacuumpumptoserviceportofstop
valveonthegaspipesideoftheoutdoorunit.
3)Runthevacuumpump.(Vacuumizeformorethan15minutes.)
4)Checkthevacuumwithgaugemanifoldvalve,thenclosegaugemanifold
valve,andstopthevacuumpump.
5)Leaveasitisforoneortwominutes.Makesurethepointerofgauge
manifoldvalveremainsinthesameposition.Conrmthatpressuregauge
shows-0.101MPa[Gauge](-760mmHg).
6)Removegaugemanifoldvalvequicklyfromserviceportofstopvalve.
7)Fullyopenallstopvalvesonthegaspipeandtheliquidpipe.Operating
withoutfullyopeninglowerstheperformanceandthiscausestrouble.
8)Referto1-2.,andchargetheprescribedamountofrefrigerantifneeded.
Besuretochargeslowlywithliquidrefrigerant.Otherwise,composition
oftherefrigerantinthesystemmaybechangedandaffectperformance
of the air conditioner.
9)Tightencapofserviceporttoobtaintheinitialstatus.
10
)Leaktest
Stopvalve
forGAS
Gaugemani-
foldvalve(for
R410A)
Compoundpressure
gauge(forR410A)
–0.101MPa
(–760mmHg)
Handle
Low
HandleHigh
Vacuumpump
(forR410A)
Chargehose
(forR410A)
*Close
*Open
Hexagonal
wrench
*4to5turns
Stopvalve
forLIQUID
Pressuregauge
(forR410A)
Precautionswhenus-
ingthecontrolvalve
Whenattachingthecontrolvalve
totheserviceport,valvecoremay
deformorloosenifexcesspres-
sureisapplied.Thismaycause
gasleak.
Serviceport
Chargehose
(forR410A)
Body Close
Open
Controlvalve
A
Whenattachingthecontrolvalveto
theserviceport,makesurethatthe
valvecoreisinclosedposition,and
then tighten part A. Do not tighten
partA orturnthebodywhen valve
coreisinopenposition.
Union
Stopvalve
Liquid
pipe
Indoor
unit
Stopvalvewith
serviceport
Gas
pipe
Refrigerant gas
cylinder
operatingvalve
(forR410A)
Gaugemanifold
valve(forR410A)
Chargehose
(forR410A)
RefrigerantgascylinderforR410Awithsiphon
Electronic scale for refrigerant charging
Refrigerant(liquid)
Outdoor
unit
Union
Union
Union
4. PURGING PROCEDURES, LEAK TEST, AND TEST RUN
Serviceportcap
(Torque13.7to
17.7N•m,140to
180kgf•cm)
Stopvalvecap
(Torque19.6to
29.4N•m,200
to300kgf•cm)
Model Indoor unit
MXZ-5E100VAD
A
E
MXZ-4E80VAD
A
D
4-3. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)
COOL/DRY HEAT
• Descriptionofthefunction:
Withthisfunction,oncetheoperationmodeislockedtoeitherCOOL/DRYmode
orHEATmode,theairconditioneroperatesinthatmodeonly.
* Changingthesettingisrequiredtoactivatethisfunction.Pleaseexplainabout
thisfunctiontoyourcustomersandaskthemwhethertheywanttouseit.
[How to lock the operation mode]
1)Besure toturn offthe mainpower forthe airconditioner beforemaking the
setting.
2)Setthe“3”ofSW1ontheoutdoorcontrollerboardtoONtoenablethisfunction.
3)Tolockthe operationmodein COOL/DRYmode,setthe “4”ofSW1 onthe
outdoorcontrollerboardtoOFF.TolocktheoperationinHEATmode,setthe
sameswitchtoON.
4)Turnonthemainpowerfortheairconditioner.
SW1
ON
1 2 3 4 5 6
SW1
ON
1 2 3 4 5 6
LED
SW1
SW871
SW2
WG79A696H02_en.indd 6 2016/04/21 14:46:40
background
En-7
Whenrelocatingordisposingoftheairconditioner,pumpdownthesystemfollowingtheprocedurebelowsothatnorefrigerantisreleasedintotheatmosphere.
1)Turnoffthebreaker.
2)Connectthegaugemanifoldvalvetotheserviceportofthestopvalveonthegaspipesideoftheoutdoorunit.
3)Fullyclosethestopvalveontheliquidpipesideoftheoutdoorunit.
4)Turnonthebreaker.
5)StarttheemergencyCOOLoperationonalltheindoorunits.
6)Whenthepressuregaugeshows0–0.05MPa[Gauge](approx.0–0.5kgf/cm
2
),fullyclosethestopvalveonthegaspipesideoftheoutdoorunitand
stoptheoperation.(Refertotheindoorunitinstallationmanualaboutthemethodforstoppingtheoperation.)
* Iftoomuchrefrigeranthasbeenaddedtotheairconditionersystem,thepressuremaynotdropto0–0.05MPa[Gauge](approx.0–0.5kgf/cm
2
),or
theprotectionfunctionmayoperateduetothepressureincreaseinthehigh-pressurerefrigerantcircuit.Ifthisoccurs,usearefrigerantcollectingdevice
tocollectalloftherefrigerantinthesystem,andthenrechargethesystemwiththecorrectamountofrefrigerantaftertheindoorandoutdoorunitshave
been relocated.
7)Turnoffthebreaker.Removethepressuregaugeandtherefrigerantpiping.
When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.
The compressor may burst and cause injury if any foreign substance, such as air, enters the pipes.
WARNING
5. PUMPING DOWN
4-5. TEST RUN
• Testrunsoftheindoorunitsshouldbeperformedindividually.Seetheinstallationmanualcomingwiththeindoorunit,andmakesurealltheunitsoperate
properly.
• Ifthetestrunwithalltheunitsisperformedatonce,possibleerroneousconnectionsoftherefrigerantpipesandtheindoor/outdoorunitconnectingwires
cannotbedetected.Thus,besuretoperformthetestrunonebyone.
About the restart protective mechanism
Oncethecompressorstops,therestartpreventivedeviceoperatessothecompressorwillnotoperatefor3minutestoprotecttheairconditioner.
Wiring/piping correction function
Thisunithasawiring/pipingcorrectionfunctionwhichcorrectswiringandpipingcombination.Whenthereispossibilityofincorrectwiringandpipingcombi-
nation,andconrmingthecombinationisdifcult,usethisfunctiontodetectandcorrectthecombinationbyfollowingtheproceduresbelow.
Makesurethatthefollowingisdone.
• Powerissuppliedtotheunit.
• Stopvalvesareopen.
Note:
Duringdetection,theoperationoftheindoorunitiscontrolledbytheoutdoorunit.Duringdetection,theindoorunitautomaticallystopsoperation.Thisisnot
a malfunction.
Procedure
Pressthepiping/wiringcorrectionswitch(SW871)1minuteormoreafterturningonthe
powersupply.
• Correctioncompletesin10to20minutes.Whenthecorrectioniscompleted,itsresult
isshownbyLEDindication.Detailsaredescribedinthefollowingtable.
• Tocancelthisfunctionduringitsoperation,pressthepiping/wiringcorrectionswitch
(SW871)again.
• Whenthecorrectioncompletedwithouterror,donotpressthepiping/wiringcorrection
switch(SW871)again.
Whentheresultis“Notcompleted”,pressthepiping/wiringcorrectionswitch(SW871)again
tocancelthisfunction.Then,conrmthewiringandpipingcombinationinaconventional
mannerbyoperatingtheindoorunitsonebyone.
• Theoperationisdonewhilethepowerissupplied.Makesurenottocontactpartsother
thantheswitch,includingtheP.C.board.Thismaycauseelectricshockorburnbyhot
partsandlivepartsaroundtheswitch.ContactingthelivepartsmaycauseP.C.board
damage.
• TopreventelectroniccontrolP.C.boarddamage,makesuretoperformstaticelimination
beforeoperatingthisfunction.
• Thisfunctiondoesnotoperatewhentheoutsidetemperatureis0°Corbelow.
LED indication during detection:
LED1
(Red)
LED2
(Yellow)
LED3
(Green)
Lighted Lighted Once
Result of piping/wiring correction function
LED1
(Red)
LED2
(Yellow)
LED3
(Green)
Result
Lighted Not lighted Lighted
Completed
(Problemcorrectedor
normal)
Once Once Once
Notcompleted
(Detectionfailed)
Otherindications
Referto“SAFETYPRE-
CAUTIONSWHENLED
BLINKS”locatedbehind
theservicepanel.
4-6. EXPLANATION TO THE USER
• UsingtheOPERATINGINSTRUCTIONS,explaintotheuserhowtousetheairconditioner(howtousetheremotecontroller,howtoremovetheairlters,
howtoremoveorputtheremotecontrollerintheremotecontrollerholder,howtoclean,precautionsforoperation,etc.).
• RecommendtheusertoreadtheOPERATINGINSTRUCTIONScarefully.
4-4. LOWERING THE OPERATION NOISE OF THE OUTDOOR UNIT
• Descriptionofthefunction:
Withthisfunction,theoperatingnoiseoftheoutdoorunitcanbeloweredbyreducingtheoperationload,forexample,duringnighttimeinCOOLmode.
However,pleasenotethatthecoolingandheatingcapacitymaylowerifthisfunctionisactivated.
* Changingthesettingisrequiredtoactivatethisfunction.Pleaseexplainaboutthisfunctiontoyourcustomersandaskthemwhethertheywanttouseit.
SW1
ON
1 2 3 4 5 6
Lowertheoperatingnoise
[How to lower the operating noise]
1)Besure toturn offthe mainpower forthe airconditioner beforemaking the
setting.
2)Setthe“5”ofSW1ontheoutdoorcontrollerboardtoONtoenablethisfunction.
3)Turnonthemainpowerfortheairconditioner.
WG79A696H02_en.indd 7 2016/04/21 14:46:40
background
blank(A4-tombo-blank).pdf 2014/05/23 11:00:46
background
blank(A4-tombo-blank).pdf 2014/05/23 11:00:46
background
blank(A4-tombo-blank).pdf 2014/05/23 11:00:46
background
WG79A696H02
HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
WG79A696H02_en_cover.indd 2 2016/04/21 14:50:16

Specifications

Mitsubishi MXZ-4E80VAD Questions and Answers

Questions and Answers

Related Products