www.napoleongrills.com
6
CYLINDER SIZE
20 lb (9.1 kg)
20 in
2
(130 cm
2
) 10 in
2
(65 cm
2
)
30 lb (13.6 kg)
30 in
2
(195 cm
2
) 15 in
2
(100 cm
2
)
MAXIMUM
MAXIMUM
A
B
MINIMUM
CYLINDER FROM GRILL
RECOMMENDED
MAXIMUM
BUILT IN CYLINDER ENCLOSURES: Built in cylinder enclosures which completely enclose the cylinder must
have both of the following:
1. At least one unobstructed venlaon opening on the exposed exterior side of the enclosure located
within 5 in (127mm) of the top of the enclosure. The opening must have a total free area of more than
20 in
2
(130 cm
2
) for a 20 lb (9.1 kg) cylinder and 30 in
2
(195 cm
2
) for a 30 lb (13.6 kg) cylinder.
2. At least one venlaon opening on the exposed, exterior side of the enclosure located 1 in (25.4 mm) or
less from the oor level. The opening must have a total free area of more than 10 in
2
(65 cm
2
) for a 20 lb
(9.1 kg) cylinder and 15 in
2
(100 cm
2
) for a 30 lb (13.6 kg) cylinder. The upper edge must be no more than
5 in (127 mm) above the oor level.
WARNING!
• The cylinder valve(s) must be readily accessible for hand operaon. A door on the enclosure to gain
access to the cylinder valves is acceptable, provided it is non-locking and can be opened without the
use of tools.
• The enclosure for the ULPG-gas cylinder must isolate the cylinder from the burner compartment to
provide shielding from radiaon, a ame barrier, and protecon from foreign material, such as hot
drippings. The enclosure cannot be located directly below the grill.
• There must be a minimum clearance of 2 in (51 mm) between the oor of the ULPG-gas cylinder
enclosure and the ground.
• The enclosure must be designed so that the ULPG-gas cylinder can be connected, disconnected and
the connecons inspected and tested outside the cylinder enclosure. Any connecons that can
be disturbed when installing the cylinder in the enclosure must be accessible for tesng inside the
enclosure.