Recommendedstandardfittings
P,ccesoriosestAndarrecomendados
3-1/4"xlO'to6"=5ft
De3-1/4'xlO"a6"-
5pies
_o°elbow_lOft
_,odode90° =
I0pies
3-1/4"x10"roofcap=24ft.
Oaperuzadecielorasode
3-1/4"x10"=24pies
3-1/4"x10'
90°elbow- 25ft.
Codode90°y3-1/4"x
10"=25pies
3-1/4"xlO"wallc_
:40ft.
_peruzadepared 45° elbow= 5ft
Je3-1/4"x10"= _odode45°=
10pies $pies
t-1/4"x10'flat
dbow=loft.
",odopianode3-1/4"
(10"- 10pies
Recommendedvent length:
Use 3-1/4" X 10" rectangular or 6" round vent.
The total lengthofthe vent system includingstraight
vent, elbow, transitions, wall or roof caps must not
exceed the equivalent of 140 feet of 3-1/4" X 10"
rectangular or 6" diameterround vent.
For best performance, use no more than three 90 degree
elbows.
Tocalculate the length of system you need, add the
equivalent feet for each vent piece used in the system.
Seethe following examples:
3-1/4"x 10"ventsystem:
Longitudrecomendada del conductode salida de aire:
Use un conducto de salida de aire rectangular de 3-1/4" x
10" o redondo de 6".
La Iongitud total del sistema de salida de aire, incluyendo
el conducto de salida de aire recto, el codo, las
transiciones, las caperuzas de pared o cielo raso no
deben exceder el equivalente a 140 pies de conducto
rectangular de salida de aire de 3-1/4" x 10" o conducto
redondo de 6" de di;imetro.
Para mejores resultados, no use m;_sde tres codos de
90°"
Para calcular la Iongitud del sistema que necesita,
agregue la equivalencia en pie para cada pedazo de
conducto usado en el sistema. Vea los siguientes
ejemplos:
Sistemadesalida deaire de 3-1/4" x10":
I-1/4"x 10"vent system
iistemade salidade aire de3-1/4" x 10"
3-1/4"x10"
90° elbow
Codede 90° y 6ft.
3-1/4"x 10" _ 6 pies
wail
rL cap/
IJ_ ' caperezade
i"ventsystem
;istemade salida deaire de 6"
90° elbows
codode90°
transition
tmnsicibn
6 pies
-r-
2 ft. (2 pies)
_t_
1 - 3-1/4" x 10"
90° elbow = 25 ft.
1 - wall cap = 40 ft.
8 feetstraight = 8 ft.
Lengthof
3-1/4"x 10" system =73 ft.
6"ventsystem:
1 - transition = 5 ft.
2 - 90° elbows 20 ft.
1 - walr cap = 40 ft.
8 feet straight = 8 ft.
Lengthof 6" system = 73 ft.
If the existing vent is round, a rectangular-to-round
adapter must be used and a rectangular 3" extension vent
between the damper assembly and adapter must be
installed to prevent damper from sticking.
1 - Codode 90°
y 3-1/4" x 10" = 25 pies
1 - Caperuzade pared = 40 pies
8 pies recto = 8 pies
Longitud de un
sistema de3-1/4" x 10" =73 pies
Sistemade salida deaire de 6"
1 -transici6n = 5 pies
2 - codos de 90° = 20 pies
1 - caperuza de pared = 40 pies
8 pies recto = 8 pies
Longitud de un
sistema de 6" = 73 pies
Si el actual conducto de salida de aire es redondo, debe
usarse un adaptador de rectangular a redondo y un
conducto de extensi6n rectangular de 3" entre el
conjunto de la compuerta y se debe instalar el adaptador
pare evitar que la compuerta se atasque.