Split-type Air-Conditioner
MXZ-2E52VAD
MXZ-3E54VAD
MXZ-4E71VAD
English
Installation Manual
For INSTALLER
• This manual only describes the installation of outdoor unit.
When installing the indoor unit, refer to the installation manual of indoor unit.
BN79A289H01_cover.indd 1 2016/04/07 16:27:46
background
En-1
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
• Besuretoread“THEFOLLOWINGSHOULDALWAYSBEOBSERVEDFORSAFETY”beforeinstallingtheairconditioner.
• Besuretoobservethewarningsandcautionsspeciedhereastheyincludeimportantitemsrelatedtosafety.
• Afterreadingthismanual,besuretokeepittogetherwiththeOPERATINGINSTRUCTIONSforfuturereference.
• EquipmentcomplyingwithIEC/EN61000-3-12.
1-2. SPECIFICATIONS
CAUTION
(Couldleadtoseriousinjuryinparticularenvironmentswhenoperatedincorrectly.)
n Do not install the unit by yourself (user).
Incompleteinstallationcouldcausereorelectricshock,injuryduetotheunit
falling,orleakageofwater.Consultthedealerfromwhomyoupurchased
theunitoraqualiedinstaller.
n Perform the installation securely referring to the installation manual.
Incompleteinstallationcouldcause re,electricshock, injuryduetothe
unitfalling,orleakageofwater.
n When installing the unit, use appropriate protective equipment and
tools for safety.
Failuretodosocouldcauseinjury.
n Install the unit securely in a place which can bear the weight of the
unit.
Iftheinstallationlocationcannotbeartheweightoftheunit,theunitcould
fallcausinginjury.
n Electrical work should be performed by a qualied, experienced electri-
cian, according to the installation manual. Be sure to use an exclusive
circuit. Do not connect other electrical appliances to the circuit.
If the capacity of the power circuit is insufcient or there is incomplete
electricalwork,itcouldresultinareoranelectricshock.
n Do not damage the wires by applying excessive pressure with parts
or screws.
Damagedwirescouldcausereorelectricshock.
n Be sure to cut off the main power in case of setting up the indoor P.C.
board or wiring works.
Failuretodosocouldcauseelectricshock.
n Use the specied wires to connect the indoor and outdoor units
securely and attach the wires rmly to the terminal block connecting
sections so the stress of the wires is not applied to the sections. Do
not extend the wires, or use intermediate connection.
Incompleteconnectingandsecuringcouldcausere.
n Do not install the unit in a place where inammable gas may leak.
Ifgasleaksandaccumulatesintheareaaroundtheunit,itcouldcausean
explosion.
n Do not use intermediate connection of the power cord or the extension
cord and do not connect many devices to one AC outlet.
Itcouldcauseareoranelectricshockduetodefectivecontact,defective
insulation,exceedingthepermissiblecurrent,etc.
n Be sure to use the parts provided or specied parts for the installation
work.
Theuseofdefectivepartscouldcauseaninjuryorleakageofwaterdue
toare,anelectricshock,theunitfalling,etc.
n When plugging the power supply plug into the outlet, make sure that
there is no dust, clogging, or loose parts in both the outlet and the
plug. Make sure that the power supply plug is pushed completely into
the outlet.
Ifthereisdust,clogging,orloosepartsonthepowersupplyplugorthe
outlet,itcouldcauseelectricshockorre.Ifloosepartsarefoundonthe
powersupplyplug,replaceit.
n Attach the electrical cover to the indoor unit and the service panel
to the outdoor unit securely.
Iftheelectricalcoveroftheindoorunitand/ortheservicepanelofthe
outdoorunitarenotattachedsecurely,itcouldresultinareoranelectric
shockduetodust,water,etc.
n When installing, relocating, or servicing the unit, make sure that no
substance other than the specied refrigerant (R410A) enters the
refrigerant circuit.
Anypresenceofforeignsubstancesuchasaircancauseabnormalpres-
sureriseandmayresultinexplosionorinjury.Theuseofanyrefrigerant
otherthan that specied for thesystem will cause mechanical failure,
systemmalfunction,orunitbreakdown.Intheworstcase,thiscouldlead
toaseriousimpedimenttosecuringproductsafety.
n Do not discharge the refrigerant into the atmosphere. If refrigerant
leaks during installation, ventilate the room.
Ifrefrigerantcomesincontactwithare,harmfulgascouldbegenerated.
n Check that the refrigerant gas does not leak after installation has
been completed.
Ifrefrigerantgasleaksindoors,andcomesintocontactwiththeameofa
fanheater,spaceheater,stove,etc.,harmfulsubstanceswillbegenerated.
n Use appropriate tools and piping materials for installation.
ThepressureofR410Ais1.6timesmorethanR22.Notusingappropriate
toolsormaterialsandincompleteinstallationcouldcausethe pipesto
burstorinjury.
n When pumping down the refrigerant, stop the compressor before
disconnecting the refrigerant pipes.
Iftherefrigerantpipesaredisconnectedwhilethecompressorisrunning
andthestopvalveisopen,aircouldbedrawninandthepressureinthe
refrigerationcyclecouldbecomeabnormallyhigh.Thiscouldcausethe
pipestoburstorinjury.
n When installing the unit, securely connect the refrigerant pipes
before starting the compressor.
Ifthecompressorisstartedbeforetherefrigerantpipesareconnected
andwhenthestopvalveisopen,aircouldbedrawninandthepressure
intherefrigerationcyclecouldbecomeabnormallyhigh.Thiscouldcause
thepipestoburstorinjury.
n Fasten a are nut with a torque wrench as specied in this manual.
Iffastenedtootight,aarenutmaybreakafteralongperiodandcause
refrigerantleakage.
n The unit shall be installed in accordance with national wiring regula-
tions.
n Earth the unit correctly.
Donotconnecttheearthtoagaspipe,waterpipe,lightningrodortel-
ephoneearth.Defectiveearthingcouldcauseelectricshock.
n Be sure to install an earth leakage breaker.
Failuretoinstallanearthleakagebreakermayresultinelectricshockorre.
n Perform the drainage/piping work securely according to the installation
manual.
Ifthereisdefectinthedrainage/pipingwork,watercoulddropfromtheunit,
soakinganddamaginghouseholdgoods.
n Do not touch the air inlet or the aluminum ns of the outdoor unit.
Thiscouldcauseinjury.
n Do not install the outdoor unit where small animals may live.
Ifsmallanimalsenterandtouchtheelectricpartsinsidetheunit,itcould
causeamalfunction,smokeemission,orre.Also,adviseusertokeep
theareaaroundtheunitclean.
WARNING
(Couldleadtodeath,seriousinjury,etc.)
Required Tools for Installation
Phillipsscrewdriver
Level
Scale
Utilityknifeorscissors
Torquewrench
Wrench(orspanner)
4mmhexagonalwrench
FlaretoolforR410A
GaugemanifoldforR410A
VacuumpumpforR410A
ChargehoseforR410A
Pipecutterwithreamer
ENGLISH
CONTENTS
1.BEFOREINSTALLATION............................................................ 1
2.OUTDOORUNITINSTALLATION...............................................4
3.FLARINGWORKANDPIPECONNECTION............................... 4
4.PURGINGPROCEDURES,LEAKTEST,ANDTESTRUN......... 5
5.PUMPINGDOWN........................................................................ 6
Model
Powersupply*1 Wirespecications*2 Pipelengthandheightdifference
*3,*4,*5,*6,*7,*8
Rated
Voltage
Fre-
quency
Breaker
capacity
Powersupply
Indoor/outdoor
connecting
wire
Max.pipelength
perindoorunit/for
multi-system
Max.height
difference*9
Max.no.ofbends
perindoorunit/
formultisystem
Refrigerant
adjustment
A*10
MXZ-2E52VAD
230V 50Hz
15A
3-core2.5mm
2
4-core
1.0/1.5mm
2
20m/40m
15m
20/40
20g/mMXZ-3E54VAD
25A
25m/50m 25/50
MXZ-4E71VAD 25m/60m 25/60
1. BEFORE INSTALLATION
Note:
WhenconnectingtheMFZ-KJseriesindoorunit(s)tothisoutdoorunit,chargeadditionalrefrigerantaccordingtotheinstructionsinthetablebelow.
No.ofMFZ-KJindoorunits
Pipelength(L)
40morless Morethan40m
1unit 100gadditional(Total2800g) 100g+{(L-40)mx20g/m)}
2units 200gadditional(Total2900g) 200g+{(L-40)mx20g/m)}
3units 300gadditional(Total3000g) 300g+{(L-40)mx20g/m)}
4units 400gadditional(Total3100g) 400g+{(L-40)mx20g/m)}
BN79A289H01_en.indd 1 2016/04/20 14:52:57
background
En-2
3. Obstacles in front (blowing) only
Whenthereisanobstacleinfrontof
theunitasshowninthegure,open
spaceabove,behind,andonthesides
oftheunitisrequired.
2. Front (blowing) side open
As long as space indicated
in the figure is provided, it
is allowed to install the unit
where obstacles are behind
andon the sides of theunit.
(Noobstacleabovetheunit)
1-3. SELECTING OPTIONAL DIFFERENT-DIAMETER JOINTS
Ifthediameterofconnectionpipedoesnotmatchtheportsizeofoutdoorunit,useoptionaldifferent-diameterjointsaccordingtothefollowingtable.
Portsizeofoutdoorunit
Optionaldifferent-diameterjoints
(portsizeofoutdoorunit→diameterofconnectionpipe)
MXZ-2E52VAD MXZ-3E54VAD MXZ-4E71VAD Liquid/Gas
6.35(1/4)
9.52(3/8):PAC-493PI
9.52(3/8)
12.7(1/2):MAC-A454JP
9.52(3/8)
15.88(5/8):PAC-SG76RJ
12.7(1/2)
9.52(3/8):MAC-A455JP
12.7(1/2)
15.88(5/8):MAC-A456JP
Refertotheinstallationmanualofindoorunitforthediameterofconnection
pipeofindoorunit.
AUNIT 6.35(1/4)/12.7(1/2)
A-BUNIT A-CUNIT B-DUNIT 6.35(1/4)/9.52(3/8)
*1 Connecttothepowerswitchwhichhasagapof3mmormorewhenopen
tointerruptthesourcepowerphase.(Whenthepowerswitchisshutoff,it
mustinterruptallphases.)
*2 Usewiresinconformitywithdesign60245IEC57.Usetheindoor/outdoor
connectingwireinconformitywiththewirespecicationsspeciedinthe
installationmanualoftheindoorunit.
*3 Neverusepipeswiththicknesslessthanspecied.Thepressureresistance
willbeinsufcient.
*4 Useacopperpipeoracopper-alloyseamlesspipe.
*5 Becarefulnottocrushorbendthepipeduringpipebending.
*6 Refrigerantpipebendingradiusmustbe100mmormore.
*7 Insulationmaterial:Heatresistingfoamplastic0.045specicgravity
*8 Besuretousetheinsulationofspeciedthickness.Excessivethickness
maycauseincorrectinstallationoftheindoorunitandinsufcientthickness
maycausedewdrippage.
*
9
Iftheoutdoorunitisinstalledhigherthantheindoorunit,max.height
differenceisreducedto10m.
*
10
Ifpipelengthexceeds40m,additionalrefrigerant(R410A)chargeisre-
quired.(Noadditionalchargeisrequiredforpipelengthlessthan40m.)
Additionalrefrigerant=A×(pipelength(m)-40)
FREE SPACE REQUIRED AROUND OUTDOOR UNIT
1-4. SELECTING THE INSTALLATION LOCATION
• Whereitisnotexposedtostrongwind.
• Whereairowisgoodanddustless.
• Whererainordirectsunshinecanbeavoidedasmuchaspossible.
• Whereneighboursarenotannoyedbyoperationsoundorhotair.
• Whererigidwallorsupportisavailabletopreventtheincreaseofopera-
tionsoundorvibration.
• Wherethereisnoriskofcombustiblegasleakage.
• Wheninstallingtheunit,besuretosecuretheunitlegs.
• Whereitisatleast3mawayfromtheantennaofTVsetorradio.Opera-
tionoftheairconditionermayinterferewithradioorTVreceptioninareas
wherereceptionisweak.Anampliermayberequiredfortheaffected
device.
• Installtheunithorizontally.
• Pleaseinstallitinanareanotaffectedbysnowfallorblowingsnow.In
areaswithheavysnow,pleaseinstallacanopy,apedestaland/orsome
bafeboards.
Note:
Itis advisable to make a piping loopnear outdoor unit so as to reduce
vibrationtransmittedfromthere.
Note:
Whenoperatingtheairconditionerinlowoutsidetemperature,besure
tofollowtheinstructionsdescribedbelow.
• Neverinstalltheoutdoorunitinaplacewhereitsairinlet/outletside
maybeexposeddirectlytowind.
• Topreventexposuretowind,installtheoutdoorunitwithitsairinlet
sidefacingthewall.
•
Topreventexposuretowind,itisrecommendedtoinstallabafe
boardontheairoutletsideoftheoutdoorunit.
Avoidthefollowingplacesforinstallationwhereairconditionertrouble
isliabletooccur.
• Whereammablegascouldleak.
• Wherethereismuchmachineoil.
• Whereoilissplashedorwheretheareaislledwithoilysmoke
(suchascookingareasandfactories,inwhichthepropertiesof
plasticcouldbechangedanddamaged).
• Saltyplacessuchastheseaside.
• Wheresuldegasisgeneratedsuchashotspring,sewage,waste
water.
• Wherethereishigh-frequencyorwirelessequipment.
•
WherethereisemissionofhighlevelsofVOCs,includingphthalate
compounds,formaldehyde,etc.,whichmaycausechemicalcracking.
500ormore
200ormore
350ormore
100ormore
1. Obstacles above
Whenthereisnoobstacleinfrontand
onthe sidesof theunit, itis allowed
toinstalltheunitwhereanobstacleis
abovetheunitonlyifthespaceshown
inthegureisprovided.
500ormore
100ormore
(Unit:mm(inch))
4. Obstacles in front and behind
Theunitcanbeusedbyat-
tachinganoptionaloutdoor
blowingguide(MAC-
856SG)(butbothsidesand
topareopen).
100ormore
500ormore
Blowingguide(MAC-856SG)
(Unit:mm)
BN79A289H01_en.indd 2 2016/04/20 14:52:57
background
En-3
Aftertheleaktest,applyinsulating
materialtightlysothatthereis
nogap.
Whenthepipingistobeattached
toawallcontainingmetals(tin
plated)ormetalnetting,usea
chemicallytreatedwoodenpiece
20mmorthickerbetweenthewall
andthepipingorwrap7to8turns
ofinsulationvinyltapearound
thepiping.
Touseexistingpiping,perform
COOLoperationfor30minutes
andpumpdownbeforeremoving
theoldairconditioner.Remake
areaccordingtothedimension
fornewrefrigerant.
Morethan
100mm
Openasarule
Morethan500mm
ifthefrontandboth
sidesareopen
Morethan100mm
Morethan200mmifthereare
obstaclestobothsides
Openasarule
Morethan500mmiftheback,
bothsidesandtopareopen
Morethan350mm
1-5. INSTALLATION DIAGRAM
ACCESSORIES
Checkthefollowingpartsbeforeinstallation.
(1) Drainsocket 1
(2) Draincap 2
PARTS TO BE PROVIDED AT YOUR SITE
(A) Powersupplycord* 1
(B)
Indoor/outdoorunitconnectingwire*
1
(C) Extensionpipe 1
(D) Wallholecover 1
(E) Pipingtape 1
(F)
Extensiondrainhose
(orsoftPVChose,15mminner
diameterorhardPVCpipeVP16)
1
(G) Refrigerationoil
Little
amount
(H) Putty 1
(I) Pipexingband 2to7
(J) Fixingscrewfor(I) 2to7
(K) Wallholesleeve 1
(L)
SoftPVChose,15mminner
diameterorhardPVCpipeVP16
fordrainsocket(1)
1
Note:
*Placeindoor/outdoorunitconnectingwire(B)and
powersupplycord(A)atleast1mawayfromthe
TVantennawire.
The“Q’ty”for(B)to(K)intheabovetableisquantity
tobeusedperindoorunit.
Unitsshouldbeinstalledbylicensedcontractor
accordingtolocalcoderequirements.
Outdoor unit installation
Airinlet
169 500
Airinlet
4-10×21Ovalholes
396
Airoutlet
840
(Unit:mm)
361
330
1-6. DRAIN PIPING FOR OUTDOOR UNIT
Pleaseperformthedrainpipingworkonlywhendrainingfromoneplace.
1)Chooseoneholetodischargedrainandinstallthedrainsocket(1)tothehole.
2)Closetherestoftheholeswiththedraincaps(2).
3)ConnectthesoftPVChose(L)of15mmintheinsidediameteronthemarketwiththedrainsocket(1)andleaddrain.
Note:
Installtheunithorizontally.
Donotusethedrainsocket(1)andthedraincaps(2)inthecoldregions.Drainmayfreezeanditmakesthefanstop.
Theoutdoorunitproducescondensateduringtheheatingoperation.Selecttheinstallationplacetoensuretopreventtheoutdoorunitand/orthegroundsfrom
beingwetbydrainwaterordamagedbyfrozendrainwater.
100ormore
500ormore
100ormore
Servicespace
350ormore
350ormore
6. Service space
Providespaceforserviceandmaintenanceasshowninthegure.
• Wheninstallingtheunitinanareathatisenclosedwithwallssuch
asaverandah,besuretohaveenoughspaceasshownbelow.
Inthiscase,theairconditioningcapacityandpowerconsumption
mightdeteriorate.
• Whenthereisalackofairoworthereisapossibilityofbecoming
shortcycle,installanoutletguideandmakesurethereisenough
spacebehindoftheunit.
• Wheninstallingtwoormoreunits,donotinstalltheunitsinfrontor
behindeachother.
5. Obstacles in front, behind and on side(s)
200ormore
100ormore
350ormore
500ormore
500ormore
Heightoftheobstacleis1200orless
(Unit:mm)
BN79A289H01_en.indd 3 2016/04/20 14:52:58
background
En-4
1 2 3 C
(MXZ-2E)
(MXZ-3E)
(MXZ-4E)
(MXZ-2E)
(MXZ-3E)
(MXZ-4E)
35mm
15mm
Leadwire
• Besuretoattacheachscrewtoitscorrespondent
terminalwhensecuringthecordand/orthewireto
theterminalblock.
• Makeearthwirealittlelongerthanothers.
(Morethan35mm)
• Forfutureservicing,giveextralengthtothecon-
nectingwires.
<OUTDOORUNIT>
Indoor/outdoorunit
connectingwire
<INDOORUNIT>
Terminalblock
Terminalblock Terminalblock
Terminalblockfor
powersupply
Terminalblock
2-1. CONNECTING WIRES FOR OUTDOOR UNIT
1)Removetheservicepanel,toppanel,frontpanel.
2)Loosenterminalscrew,andconnectindoor/outdoorunitconnectingwire(B)from
theindoorunitcorrectlyontheterminalblock.Becarefulnottomakemis-wiring.
Fixthewiretotheterminalblocksecurelysothatnopartofitscoreisappeared,
andnoexternalforceisconveyedtotheconnectingsectionoftheterminalblock.
3)Firmlytightentheterminalscrewstopreventthemfromloosening.Aftertightening,
pullthewireslightlytoconrmthattheydonotmove.
4)Perform2)and3)foreachindoorunit.
5)Connectpowersupplycord(A).
6)ConnectthedemandcontroltransmissioncabletotheterminalblockforDRED
Interface.
7)Fixindoor/outdoorunitconnectingwire(B)andpowersupplycord(A)withthe
cableclamps.
8)Fixthedemandcontroltransmissioncablewiththecablestrap.
9)Closetheservicepanel,toppanel,frontpanelsecurely.Makesurethat3-2.PIPE
CONNECTIONiscompleted.
•
Aftermakingconnectionsbetweenbothpowersupplycord(A)andindoor/outdoor
unitconnectingwire(B),besuretoxbothcableandwirewithcableclamps.
2. OUTDOOR UNIT INSTALLATION
POWERSUPPLY
~/N230V50Hz
ThisunithasdemandresponsecapabilitywhichiscompliantwithAS/NZS4755.3.1.Toactivatethisfunction,youneedtomakeacontractwithremote
agentssuchaselectricsupplycompany,thenthisunitshouldbeconnectedtoDemandresponseenablingdevise(DRED).Forfurtherinformation,
consultyourdealer.Thisunitsupports3DemandResponseModes(DRMs):DRM1,DRM2andDRM3.
CAUTION
•Topreventmalfunctioncausedbynoise,routethecordconnectingthisunittoDREDandthepowersupplycordasparallelaspossible.
•Donotconnectthedemandcontroltransmissioncabletotheterminalblockforpowersupply.
•Donotpull,extremelybendorapplystrongpressureonthewiretopreventfailure.
•DonotscrewDREDtooutdoorunit.
•DonotputDREDinoutdoorunit.
•Secureelectricalwiringaboveclamp.
•DonotgetDREDwirecaughtintheservicepanel.
1:DRM1
2:DRM2
3:DRM3
C:COMMON
AS/NZS4755
terminalblock
Fig.1 Fig.2
Fig.3 Fig.4
Fig.5 Fig.6
3-1. FLARING WORK
Pipediameter
(mm)
Nut
(mm)
A(mm) Tighteningtorque
Clutch
typetool
forR410A
Clutch
typetool
forR22
Wingnut
typetool
forR22
N•m kgf•cm
ø6.35(1/4”) 17
0to0.5 1.0to1.5
1.5to2.0
13.7to17.7 140to180
ø9.52(3/8”) 22 34.3to41.2 350to420
ø12.7(1/2”) 26
2.0to2.5
49.0to56.4 500to575
ø15.88(5/8”) 29 73.5to78.4 750to800
TiltedUnevenBurred
Good
Nogood
Burr
Copperpipe
Sparereamer
Pipecutter
Smoothall
around
Evenlength
allaround
Insideisshin-
ingwithoutany
scratches.
Flarenut
Die
Copperpipe
Clutchtype
Flaringtool
Wingnuttype
Copper
pipe
1)Cutthecopperpipecorrectlywithpipecutter.(Fig.1,2)
2)Completelyremoveallburrsfromthecutcrosssectionofpipe.(Fig.3)
• Aimthecopperpipedownwardwhileremovingburrstopreventburrsfrom
droppinginthepipe.
3)Removearenutsattachedtoindoorandoutdoorunits,thenputthemonpipe
havingcompletedburrremoval.(Notpossibletoputthemonafteraringwork.)
4)Flaringwork(Fig.4,5).Firmlyholdcopperpipeinthedimensionshowninthe
table.SelectAmmfromthetableaccordingtothetoolselected.
5)Check
• ComparethearedworkwithFig.6.
• Ifareisnotedtobedefective,cutoffthearedsectionanddoaringwork
again.
3. FLARING WORK AND PIPE CONNECTION
Terminalblock
forDREDInterface
Frontpanel
Servicepanel
Terminalblock
forpowersupply
Cablestrap
Thetipshouldbe
pointedupwards.
Toppanel
BN79A289H01_en.indd 4 2016/04/20 14:53:00
background
En-5
4-1. PURGING PROCEDURES AND LEAK TEST
4-2. GAS CHARGE
Performgaschargetounit.
1)Connectgascylindertotheserviceportofstopvalve.
2)Performairpurgeofthepipe(orhose)comingfromrefrigerantgascylinder.
3)Replenishspeciedamountoftherefrigerant,whileoperatingtheairconditioner
forcooling.
Note:
Incaseofaddingrefrigerant,complywiththequantityspeciedfortherefrigerat-
ingcycle.
CAUTION:
Whenchargingtherefrigerantsystemwithadditionalrefrigerant,besuretouseliquid
refrigerant.Addinggasrefrigerantmaychangethecompositionoftherefrigerantin
thesystemandaffectnormaloperationoftheairconditioner.Also,chargetheliquid
refrigerantslowly,otherwisethecompressorwillbelocked.
Tomaintainthehighpressureofthegascylinder,warmthegascylinderwithwarm
water(under40°C)duringcoldseason.Butneverusenakedreorsteam.
1)Removeserviceportcapofstopvalveonthesideoftheoutdoorunit
gaspipe.(Thestopvalvesarefullyclosedandcoveredincapsin
theirinitialstate.)
2)Connectgaugemanifoldvalveandvacuumpumptoserviceportof
stopvalveonthegaspipesideoftheoutdoorunit.
3)Runthevacuumpump.(Vacuumizeformorethan15minutes.)
4)Checkthevacuumwithgaugemanifoldvalve,thenclosegauge
manifoldvalve,andstopthevacuumpump.
5)Leaveasitisforoneortwominutes.Makesurethepointerofgauge
manifoldvalveremainsinthesameposition.Conrmthatpressure
gaugeshows-0.101MPa[Gauge](-760mmHg).
6)Removegaugemanifoldvalvequicklyfromserviceportofstopvalve.
7)
Fullyopenallstopvalvesonthegaspipeandtheliquidpipe.Operating
withoutfullyopeninglowerstheperformanceandthiscausestrouble.
8)Referto1-2.,andchargetheprescribedamountofrefrigerantif
needed.Besuretochargeslowlywithliquidrefrigerant.Otherwise,
compositionoftherefrigerantinthesystemmaybechangedand
affectperformanceoftheairconditioner.
9)Tightencapofserviceporttoobtaintheinitialstatus.
10
)Leaktest
Union
Stop valve
Liquid
pipe
Indoor
unit
Stop valve with
service port
Gas
pipe
Outdoor
unit
Union
Union
Union
Model Indoor unit
MXZ-2E
MXZ-3E
MXZ-4E
Refrigerantgas
cylinder
operatingvalve
(forR410A)
Gaugemanifold
valve(forR410A)
Chargehose
(forR410A)
RefrigerantgascylinderforR410Awithsiphon
Electronicscaleforrefrigerantcharging
Refrigerant(liquid)
Stopvalve
forGAS
Stopvalvecap
(Torque19.6to
29.4N•m,200
to300kgf•cm)
Gaugemanifold
valve(forR410A)
Compoundpressure
gauge(forR410A)
–0.101MPa
(–760mmHg)
Handle
Low
HandleHigh
Vacuumpump
(forR410A)
*Close
*Open
Hexagonalwrench
*4to5turns
Stopvalve
forLIQUID
Pressuregauge
(forR410A)
Precautionswhenus-
ingthecontrolvalve
Whenattachingthecontrolvalve
totheserviceport,valvecoremay
deformorloosenifexcesspres-
sureisapplied.Thismaycause
gasleak.
Serviceport
Chargehose
(forR410A)
Body
Close
Open
Control
valve
A
Whenattachingthecontrolvalveto
theserviceport,makesurethatthe
valvecoreisinclosedposition,and
then tighten part A. Do not tighten
partA orturnthe bodywhen valve
coreisinopenposition.
Serviceportcap
(Torque13.7to
17.7N•m,140to
180kgf•cm)
Chargehose
(forR410A)
4-3. REMOVING THE MAINTENANCE PANEL
ThesettingofDipSwitchontheoutdoorcontrollerboardcanbechangedwithout
removingthefrontpanel.
FollowtheproceduresbelowtoremovethemaintenancepanelandsettheDip
Switch.
1)Removescrew(s)whichxthemaintenancepanel.
2)Removethemaintenancepanel,andperformnecessarysettings.
3)Installthemaintenancepanel.
Note:
Makesuretoxthemaintenancepanelsecurely.Incompleteinstallationcould
causemalfunction.
Maintenancepanel
4. PURGING PROCEDURES, LEAK TEST, AND TEST RUN
3-2. PIPE CONNECTION
1)Applyathincoatofrefrigerationoil(G)tothearedendsofthepipesandthepipecon-
nectionsoftheoutdoorunit.Donotapplyrefrigerationoilonscrewthreads.Excessive
tighteningtorquewillresultindamageonthescrew.
2)Alignthecenterofthepipewiththatofthepipeconnectionsoftheoutdoorunit,thenhand
tightenthearenut3to4turns.
3)Tightenthearenutwithatorquewrenchasspeciedinthetable.
•Over-tighteningmaycausedamagetothearenut,resultinginrefrigerantleakage.
•Besuretowrapinsulationaroundthepiping.Directcontactwiththebarepipingmay
resultinburnsorfrostbite.
3-3. INSULATION AND TAPING
1)Coverpipingjointswithpipecover.
2)Foroutdoorunitside,surelyinsulateeverypipingincludingvalves.
3)Usingpipingtape(E),applytapingstartingfromtheentryofoutdoorunit.
• Stoptheendofpipingtape(E)withtape(withadhesiveagentattached).
•
Whenpipinghavetobearrangedthroughaboveceiling,closetorwherethetemperature
andhumidityarehigh,windadditionalcommerciallysoldinsulationtopreventcondensation.
When installing the unit, securely
connect the refrigerant pipes before
starting the compressor.
When there are the ports which are
not used, make sure their nuts are
tightened securely.
WARNING
CAUTION
BN79A289H01_en.indd 5 2016/04/20 14:53:01
background
En-6
4-4. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)
4-5. LOWERING THE OPERATION NOISE OF THE OUTDOOR UNIT
• Descriptionofthefunction:
Withthisfunction,oncetheoperationmodeislockedtoeitherCOOL/DRYmode
orHEATmode,theairconditioneroperatesinthatmodeonly.
* Changingthesettingisrequiredtoactivatethisfunction.Pleaseexplainabout
thisfunctiontoyourcustomersandaskthemwhethertheywanttouseit.
[How to lock the operation mode]
1)Besure toturn offthe mainpower forthe airconditioner beforemaking the
setting.
2)Setthe“3”ofSW1ontheoutdoorcontrollerboardtoONtoenablethisfunction.
3)Tolockthe operationmodeinCOOL/DRYmode,setthe “4”ofSW1onthe
outdoorcontrollerboardtoOFF.TolocktheoperationinHEATmode,setthe
sameswitchtoON.
4)Turnonthemainpowerfortheairconditioner.
• Descriptionofthefunction:
Withthisfunction,theoperatingnoiseoftheoutdoorunitcanbeloweredbyreducingtheoperationload,forexample,duringnighttimeinCOOLmode.
However,pleasenotethatthecoolingandheatingcapacitymaylowerifthisfunctionisactivated.
* Changingthesettingisrequiredtoactivatethisfunction.Pleaseexplainaboutthisfunctiontoyourcustomersandaskthemwhethertheywanttouseit.
Lowertheoperatingnoise
[How to lower the operating noise]
1)Besuretoturnoffthemainpowerfortheairconditionerbeforemakingthesetting.
2)Setthe“5”ofSW1ontheoutdoorcontrollerboardtoONtoenablethisfunction.
3)Turnonthemainpowerfortheairconditioner.
4-6. TEST RUN
• Testrunsoftheindoorunitsshouldbeperformedindividually.Seetheinstallationmanualcomingwiththeindoorunit,andmakesurealltheunitsoperate
properly.
• Ifthetestrunwithalltheunitsisperformedatonce,possibleerroneousconnectionsoftherefrigerantpipesandtheindoor/outdoorunitconnectingwires
cannotbedetected.Thus,besuretoperformthetestrunonebyone.
About the restart protective mechanism
Oncethecompressorstops,therestartpreventivedeviceoperatessothecompressorwillnotoperatefor3minutestoprotecttheairconditioner.
Wiring/piping correction function
Thisunithasawiring/pipingcorrectionfunctionwhichcorrectswiringandpipingcombination.Whenthereispossibilityofincorrectwiringandpipingcombi-
nation,andconrmingthecombinationisdifcult,usethisfunctiontodetectandcorrectthecombinationbyfollowingtheproceduresbelow.
Makesurethatthefollowingisdone.
• Powerissuppliedtotheunit.
• Stopvalvesareopen.
Note:
Duringdetection,theoperationoftheindoorunitiscontrolledbytheoutdoorunit.Duringdetection,theindoorunitautomaticallystopsoperation.Thisisnot
amalfunction.
Whenrelocatingordisposingoftheairconditioner,pumpdownthesystemfollowingtheprocedurebelowsothatnorefrigerantisreleasedintotheatmosphere.
1)Turnoffthebreaker.
2)Connectthegaugemanifoldvalvetotheserviceportofthestopvalveonthegaspipesideoftheoutdoorunit.
3)Fullyclosethestopvalveontheliquidpipesideoftheoutdoorunit.
4)Turnonthebreaker.
5)StarttheemergencyCOOLoperationonalltheindoorunits.
6)Whenthepressuregaugeshows0.05to0MPa[Gauge](approx.0.5to0kgf/cm
2
),fullyclosethestopvalveonthegaspipesideoftheoutdoorunitand
stoptheoperation.(Refertotheindoorunitinstallationmanualaboutthemethodforstoppingtheoperation.)
*Iftoomuchrefrigeranthasbeenaddedtotheairconditionersystem,thepressuremaynotdropto0.05MPa[Gauge](approx.0.5kgf/cm
2
),ortheprotection
functionmayoperateduetothepressureincreaseinthehigh-pressurerefrigerantcircuit.Ifthisoccurs,usearefrigerantcollectingdevicetocollectallof
therefrigerantinthesystem,andthenrechargethesystemwiththecorrectamountofrefrigerantaftertheindoorandoutdoorunitshavebeenrelocated.
7)Turnoffthebreaker.Removethepressuregaugeandtherefrigerantpiping.
4-7. EXPLANATION TO THE USER
• UsingtheOPERATINGINSTRUCTIONS,explaintotheuserhowtousetheairconditioner(howtousetheremotecontroller,howtoremovetheairlters,
howtoremoveorputtheremotecontrollerintheremotecontrollerholder,howtoclean,precautionsforoperation,etc.).
• RecommendtheusertoreadtheOPERATINGINSTRUCTIONScarefully.
Procedure
Pressthepiping/wiringcorrectionswitch(SW871)1minuteormoreafterturningonthe
powersupply.
• Correctioncompletesin10to15minutes.Whenthecorrectioniscompleted,itsresult
isshownbyLEDindication.Detailsaredescribedinthefollowingtable.
• Tocancelthisfunctionduringitsoperation,pressthepiping/wiringcorrectionswitch
(SW871)again.
• Whenthecorrectioncompletedwithouterror,donotpressthepiping/wiringcorrection
switch(SW871)again.
Whentheresultis“Notcompleted”,pressthepiping/wiringcorrectionswitch(SW871)again
tocancelthisfunction.Then,conrmthewiringandpipingcombinationinaconventional
mannerbyoperatingtheindoorunitsonebyone.
• Theoperationisdonewhilethepowerissupplied.Makesurenottocontactpartsother
thantheswitch,includingtheP.C.board.Thismaycauseelectricshockorburnbyhot
partsandlivepartsaroundtheswitch.ContactingthelivepartsmaycauseP.C.board
damage.
• TopreventelectroniccontrolP.C.boarddamage,makesuretoperformstaticelimination
beforeoperatingthisfunction.
• Thisfunctiondoesnotoperatewhentheoutsidetemperatureis0°Corbelow.
LED indication during detection:
LED1
(Red)
LED2
(Yellow)
LED3
(Green)
Lighted Lighted Once
Result of piping/wiring correction function
LED1
(Red)
LED2
(Yellow)
LED3
(Green)
Result
Lighted Notlighted Lighted
Completed
(Problemcorrectedor
normal)
Once Once Once
Notcompleted
(Detectionfailed)
Otherindications
Referto“SAFETYPRE-
CAUTIONSWHENLED
BLINKS”locatedbehind
thetoppanel.
When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.
The compressor may burst and cause injury if any foreign substance, such as air, enters the pipes.
WARNING
5. PUMPING DOWN
HEAT
COOL/DRY
LED
SW1
SW871
SW2
SW1
ON
1 2 3 4 5 6
SW1
ON
1 2 3 4 5 6
BN79A289H01_en.indd 6 2016/04/20 14:53:02
background
BN79A289H01
HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
BN79A289H01_cover.indd 2 2016/04/07 16:27:46

Specifications

Mitsubishi MXZ-4E71VAD Questions and Answers


#1 Are Mitsubishi air conditioners any good?

So, which air conditioner brand do consumers rate best in 2021? Mitsubishi Heavy Industries continues to chill in the number one spot for three years running. It earned five-star reviews for reliability, functionality and features, ease of use, noise while operating, value for money and overall satisfaction.

#2 Is Mitsubishi or Daikin better?

Both have exceptional cooling efficiencies (23 SEER) while Daikin has better heating efficiency (12.5 HSPF) at a lower price. Mitsubishi, on the other hand, is significantly quieter indoors and has a wider operating range down to -15 F. The choice between these two should come down to either climate or use.

Questions and Answers

Related Products