Mitsubishi MXZ-6E120VAD Air Conditioner

Product's Documents

Below are documents related to this product, you can read online or download:
MXZ-6E120VAD photo

Installation Manual

This is the main product document for model MXZ-6E120VAD.

The file format is pdf, 12 pages, you can download this manual here .

background
Split-type Air-Conditioner
MXZ-6E120VAD
English
Installation Manual
For INSTALLER
• This manual only describes the installation of outdoor unit.
When installing the indoor unit, refer to the installation manual of indoor unit.
BH79A274H01_en.indd 1 2016/03/23 10:42:14
background
En-1
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
• Besuretoread“THEFOLLOWINGSHOULDALWAYSBEOBSERVEDFORSAFETY”beforeinstallingtheairconditioner.
• Besuretoobservethewarningsandcautionsspeciedhereastheyincludeimportantitemsrelatedtosafety.
• Afterreadingthismanual,besuretokeepittogetherwiththeOPERATINGINSTRUCTIONSforfuturereference.
• EquipmentcomplyingwithIEC/EN61000-3-12.
1-2. SPECIFICATIONS
Model
Powersupply*1 Wirespecications*2 Pipelengthandheightdifference
*3,*4,*5,*6,*7,*8
Rated
Voltage
Fre-
quency
Breaker
capacity
Power
supply
Indoor/outdoor
connectingwire
Max.pipe
lengthper
indoorunit/for
multi-system
Max. height
difference*9
Max. no. of bends
perindoorunit/
for multi system
Refrigerant
adjustment
A*10
MXZ-6E120VAD 230V 50Hz 32A
3-core
4.0mm
2
4-core
1.0/1.5mm
2
25m/80m 15m 25/80 20g/m
*1 Connecttothepowerswitchwhichhasagapof3mmormorewhenopen
tointerruptthesourcepowerphase.(Whenthepowerswitchisshutoff,it
mustinterruptallphases.)
*2 Usewiresinconformitywithdesign60245IEC57.Usetheindoor/outdoor
connectingwireinconformitywiththewirespecicationsspeciedinthe
installation manual of the indoor unit.
*3 Neverusepipeswiththicknesslessthanspecied.Thepressureresistance
willbeinsufcient.
*4 Useacopperpipeoracopper-alloyseamlesspipe.
*5 Becarefulnottocrushorbendthepipeduringpipebending.
*6 Refrigerantpipebendingradiusmustbe100mmormore.
*7 Insulationmaterial:Heatresistingfoamplastic0.045specicgravity
*8 Besuretousetheinsulationofspeciedthickness.Excessivethickness
maycauseincorrectinstallationoftheindoorunitandinsufcientthickness
maycausedewdrippage.
*
9
If the outdoor unit is installed higher than the indoor unit, max. height
differenceisreducedto10m.
*
10
Ifpipelengthexceeds30m,additionalrefrigerant(R410A)chargeisre-
quired.(Noadditionalchargeisrequiredforpipelengthlessthan30m.)
Additionalrefrigerant=A×(pipelength(m)-30)
Required Tools for Installation
Phillipsscrewdriver
Level
Scale
Utilityknifeorscissors
Torquewrench
Wrench(orspanner)
4mmhexagonalwrench
FlaretoolforR410A
GaugemanifoldforR410A
VacuumpumpforR410A
ChargehoseforR410A
Pipecutterwithreamer
ENGLISH
CONTENTS
1.BEFOREINSTALLATION ............................................................1
2.OUTDOORUNITINSTALLATION ...............................................4
3.FLARINGWORKANDPIPECONNECTION ...............................5
4.PURGINGPROCEDURES,LEAKTEST,ANDTESTRUN .........5
5.PUMPINGDOWN ........................................................................ 7
CAUTION
(Couldleadtoseriousinjuryinparticularenvironmentswhenoperatedincorrectly.)
n Do not install the unit by yourself (user).
Incompleteinstallationcouldcausereorelectricshock,injuryduetotheunit
falling,orleakageofwater.Consultthedealerfromwhomyoupurchased
theunitoraqualiedinstaller.
n Perform the installation securely referring to the installation manual.
Incompleteinstallationcouldcausere,electricshock,injuryduetothe
unitfalling,orleakageofwater.
n When installing the unit, use appropriate protective equipment and
tools for safety.
Failure to do so could cause injury.
n Install the unit securely in a place which can bear the weight of the
unit.
Iftheinstallationlocationcannotbeartheweightoftheunit,theunitcould
fall causing injury.
n Electrical work should be performed by a qualied, experienced electri-
cian, according to the installation manual. Be sure to use an exclusive
circuit. Do not connect other electrical appliances to the circuit.
If thecapacity of the power circuit is insufcient or there is incomplete
electricalwork,itcouldresultinareoranelectricshock.
n Do not damage the wires by applying excessive pressure with parts
or screws.
Damagedwirescouldcausereorelectricshock.
n Be sure to cut off the main power in case of setting up the indoor P.C.
board or wiring works.
Failuretodosocouldcauseelectricshock.
n Use the specied wires to connect the indoor and outdoor units
securely and attach the wires rmly to the terminal block connecting
sections so the stress of the wires is not applied to the sections. Do
not extend the wires, or use intermediate connection.
Incompleteconnectingandsecuringcouldcausere.
n Do not install the unit in a place where inammable gas may leak.
Ifgasleaksandaccumulatesintheareaaroundtheunit,itcouldcausean
explosion.
n Do not use intermediate connection of the power cord or the extension
cord and do not connect many devices to one AC outlet.
Itcouldcauseareoranelectricshockduetodefectivecontact,defective
insulation,exceedingthepermissiblecurrent,etc.
n Be sure to use the parts provided or specied parts for the installation
work.
Theuseofdefectivepartscouldcauseaninjuryorleakageofwaterdue
toare,anelectricshock,theunitfalling,etc.
n When plugging the power supply plug into the outlet, make sure that
there is no dust, clogging, or loose parts in both the outlet and the
plug. Make sure that the power supply plug is pushed completely into
the outlet.
Ifthereisdust,clogging,orloosepartsonthepowersupplyplugorthe
outlet,itcouldcauseelectricshockorre.Ifloosepartsarefoundonthe
powersupplyplug,replaceit.
n Attach the electrical cover to the indoor unit and the service panel
to the outdoor unit securely.
Iftheelectricalcoveroftheindoorunitand/ortheservicepanelofthe
outdoorunitarenotattachedsecurely,itcouldresultinareoranelectric
shockduetodust,water,etc.
n When installing, relocating, or servicing the unit, make sure that no
substance other than the specied refrigerant (R410A) enters the
refrigerant circuit.
Anypresenceofforeignsubstancesuchasaircancauseabnormalpres-
sureriseandmayresultinexplosionorinjury.Theuseofanyrefrigerant
otherthan thatspeciedfor the systemwillcause mechanicalfailure,
systemmalfunction,orunitbreakdown.Intheworstcase,thiscouldlead
toaseriousimpedimenttosecuringproductsafety.
n Do not discharge the refrigerant into the atmosphere. If refrigerant
leaks during installation, ventilate the room.
Ifrefrigerantcomesincontactwithare,harmfulgascouldbegenerated.
n Check that the refrigerant gas does not leak after installation has
been completed.
Ifrefrigerantgasleaksindoors,andcomesintocontactwiththeameofa
fanheater,spaceheater,stove,etc.,harmfulsubstanceswillbegenerated.
n Use appropriate tools and piping materials for installation.
ThepressureofR410Ais1.6timesmorethanR22.Notusingappropriate
toolsormaterialsandincompleteinstallationcouldcausethepipesto
burst or injury.
n When pumping down the refrigerant, stop the compressor before
disconnecting the refrigerant pipes.
Iftherefrigerantpipesaredisconnectedwhilethecompressorisrunning
andthestopvalveisopen,aircouldbedrawninandthepressureinthe
refrigeration cycle could become abnormally high. This could cause the
pipestoburstorinjury.
n When installing the unit, securely connect the refrigerant pipes
before starting the compressor.
Ifthecompressorisstartedbeforetherefrigerantpipesareconnected
andwhenthestopvalveisopen,aircouldbedrawninandthepressure
in the refrigeration cycle could become abnormally high. This could cause
thepipestoburstorinjury.
n Fasten a are nut with a torque wrench as specied in this manual.
Iffastenedtootight,aarenutmaybreakafteralongperiodandcause
refrigerantleakage.
n The unit shall be installed in accordance with national wiring regula-
tions.
n Earth the unit correctly.
Donotconnecttheearthtoagaspipe,waterpipe,lightningrodortel-
ephoneearth.Defectiveearthingcouldcauseelectricshock.
n Be sure to install an earth leakage breaker.
Failuretoinstallanearthleakagebreakermayresultinelectricshockorre.
n Perform the drainage/piping work securely according to the installation
manual.
Ifthereisdefectinthedrainage/pipingwork,watercoulddropfromtheunit,
soakinganddamaginghouseholdgoods.
n Do not touch the air inlet or the aluminum ns of the outdoor unit.
This could cause injury.
n Do not install the outdoor unit where small animals may live.
Ifsmallanimalsenterandtouchtheelectricpartsinsidetheunit,itcould
causeamalfunction,smokeemission,orre.Also,adviseusertokeep
the area around the unit clean.
WARNING
(Couldleadtodeath,seriousinjury,etc.)
1. BEFORE INSTALLATION
BH79A274H01_en.indd 1 2016/03/23 10:42:15
background
En-2
1-3. SELECTING OPTIONAL DIFFERENT-DIAMETER JOINTS
Ifthediameterofconnectionpipedoesnotmatchtheportsizeofoutdoorunit,useoptionaldifferent-diameterjointsaccordingtothefollowingtable.
Portsizeofoutdoorunit Optionaldifferent-diameterjoints(portsizeofoutdoorunit
diameterofconnectionpipe)
MXZ-6E Liquid/Gas
6.35(1/4)
9.52(3/8):PAC-493PI
9.52(3/8)
12.7(1/2):MAC-A454JP
9.52(3/8)
15.88(5/8):PAC-SG76RJ
12.7(1/2)
9.52(3/8):MAC-A455JP
12.7(1/2)
15.88(5/8):MAC-A456JP
Refertotheinstallationmanualofindoorunitforthediameterofconnectionpipeofindoorunit.
AUNIT 6.35(1/4)/12.7(1/2)
B-FUNIT 6.35(1/4)/9.52(3/8)
1-4. SELECTING THE INSTALLATION LOCATION
• Whereitisnotexposedtostrongwind.
• Whereairowisgoodanddustless.
• Whererainordirectsunshinecanbeavoidedasmuchaspossible.
• Whereneighboursarenotannoyedbyoperationsoundorhotair.
• Whererigidwallorsupportisavailabletopreventtheincreaseofopera-
tionsoundorvibration.
• Wherethereisnoriskofcombustiblegasleakage.
• Wheninstallingtheunit,besuretosecuretheunitlegs.
• Whereitisatleast3mawayfromtheantennaofTVsetorradio.Opera-
tionoftheairconditionermayinterferewithradioorTVreceptioninareas
wherereceptionisweak.Anampliermayberequiredfortheaffected
device.
• Installtheunithorizontally.
• Pleaseinstallitinanareanotaffectedbysnowfallorblowingsnow.In
areaswithheavysnow,pleaseinstallacanopy,apedestaland/orsome
bafeboards.
Note:
Itis advisabletomake a pipingloop near outdoorunit so asto reduce
vibrationtransmittedfromthere.
Note:
Whenoperatingtheairconditionerinlowoutsidetemperature,besure
tofollowtheinstructionsdescribedbelow.
• Neverinstalltheoutdoorunitinaplacewhereitsairinlet/outletside
maybeexposeddirectlytowind.
• Topreventexposuretowind,installtheoutdoorunitwithitsairinlet
sidefacingthewall.
•
Topreventexposuretowind,itisrecommendedtoinstallabafeboard
on the air outlet side of the outdoor unit.
Avoidthefollowingplacesforinstallationwhereairconditionertrouble
is liable to occur.
• Whereammablegascouldleak.
• Wherethereismuchmachineoil.
• Saltyplacessuchastheseaside.
• Wheresuldegasisgenerated suchashotspring,sewage,waste
water.
• Wherethereishigh-frequencyorwirelessequipment.
• WherethereisemissionofhighlevelsofVOCs,includingphthalate
compounds,formaldehyde,etc.,whichmaycausechemicalcracking.
(Unit:mm(inch))
3. Obstacles in front (blowing) only
When there is an obstacle in front of
theunitasshowninthegure,open
spaceabove,behind,andonthesides
oftheunitisrequired.
2. Front (blowing) side open
As long as space indicated
in the figure is provided, it
is allowed to install the unit
where obstaclesare behind
and on the sides of the unit.
(Noobstacleabovetheunit)
FREE SPACE REQUIRED AROUND OUTDOOR UNIT
500ormore
200ormore
350ormore100ormore
1. Obstacles above
When there is no obstacle in front and
onthesidesof the unit, itisallowed
toinstalltheunitwhereanobstacleis
abovetheunitonlyifthespaceshown
inthegureisprovided.
100ormore
500ormore
100ormore
Servicespace
350ormore
350ormore
6. Service space
Providespaceforserviceandmaintenanceasshowninthegure.
500ormore
100ormore
• Wheninstallingtheunitinanareathatisenclosedwithwallssuch
asaverandah,besuretohaveenoughspaceasshownbelow.
Inthiscase,theairconditioningcapacityandpowerconsumption
might deteriorate.
• Whenthereisalackofairoworthereisapossibilityofbecoming
shortcycle,installanoutletguideandmakesurethereisenough
spacebehindoftheunit.
• Wheninstallingtwoormoreunits,donotinstalltheunitsinfrontor
behind each other.
100ormore
200ormore
350ormore
500ormore
500ormore
(Unit:mm)
5. Obstacles in front, behind and on side(s)
4. Obstacles in front and behind
The unit can be used by at-
tachinganoptionaloutdoor
blowingguide(PAC-
SH96SG-E)(butbothsides
andtopareopen).
100ormore
500ormore
Blowingguide(PAC-SH96SG-E)
Heightoftheobstacleis1200orless
BH79A274H01_en.indd 2 2016/03/23 10:42:15
background
En-3
1-5. INSTALLATION DIAGRAM
Unitsshouldbeinstalledbylicensedcontractoraccordingtolocalcoderequirements.
After the leak test, apply insulat-
ing material tightly so that there
isnogap.
ACCESSORIES
Checkthefollowingpartsbeforeinstallation.
(1) Drainsocket 1
(2) Draincap 5
PARTS TO BE PROVIDED AT YOUR SITE
(A) Powersupplycord* 1
(B) Indoor/outdoorunitconnectingwire* 1
(C) Extensionpipe 1
(D) Wallholecover 1
(E) Pipingtape 1
(F)
Extension drain hose
(orsoftPVChose,15mminner
diameterorhardPVCpipeVP16)
1
(G) Refrigeration oil
Little
amount
(H) Putty 1
(I) Pipexingband 2to7
(J) Fixingscrewfor(I) 2to7
(K) Wallholesleeve 1
(L)
SoftPVChose,15mminner
diameterorhardPVCpipeVP16
fordrainsocket(1)
1
* Note:
Place indoor/outdoor unit connecting wire (B)and
powersupplycord (A) atleast1maway from the
TVantennawire.
The“Q’ty”for(B)to(K)intheabovetableisquantity
tobeusedperindoorunit.
More than
100mm
Openasarule
Morethan500mm
if the front and both
sidesareopen
Morethan100mm
Morethan200mmifthereare
obstacles to both sides
Openasarule
Morethan500mmiftheback,
bothsidesandtopareopen
Morethan350mm
Outdoor unit installation
Air inlet
Air outlet
Air inlet
950mm
600mm
175
mm
2-U-shapenotchedholes
(BaseboltM10)
330mm
2-12mm×36mm
ovalholes(BaseboltM10)
370mm
417mm
Whenthepipingistobeattachedto
awallcontainingmetals(tinplated)
or metal netting, use a chemically
treated wooden piece20 mm or
thicker between the wall and the
pipingorwrap7to8turnsofinsula-
tionvinyltapearoundthepiping.
To use existing piping, perform
COOL operation for30 minutes
and pump down before removing
theoldairconditioner.Remakeare
accordingtothedimensionfornew
refrigerant.
1-6. DRAIN PIPING FOR OUTDOOR UNIT
1) Performthedrainpipingworkonlywhendrainingfromoneplace.
2) Providedrainpipingbeforeindoorandoutdoorpipingconnection.
3) Attachthedrainsockettooneoftheseveraldrainholes.
Fixthedrainsocketintothedrainholeofthebaseusingthecatchestosecureitin
place.
4) ConnectthesoftPVChoseI.D.15mmasshownintheillustration.
5) Makesuretoprovidedrainpipingwithadownhillgradeforeasydrainow.
6) Gluethedraincapstoclosealltheotherunnecessaryholeswiththeglue(Prepare
intheeld).
Note:
Applythegluesecurely,astheglue(Prepareintheeld)willworkassealtoprevent
waterfromleaking.
Usetheadhesivefortherubberandmetal.
Attention
The outdoorunit is providedwith several holes for drainage at the bottom to make
drainage easier.
Thedrainsocketisusedtoclosetheunnecessaryholesandcentralizethedrainage
whenusingthedraintubeattheinstallationplace.
Donottousethedrainsocketincoldregion.Thedraintubecanbefrozen.
(1)Drainsocket
(L)SoftPVChose
(2)Draincap
BH79A274H01_en.indd 3 2016/03/23 10:42:15
background
En-4
A B C
D E F
A B C
D E F
A B C
E F
A B C
D E F
A B C
D D E F
DRDRDRDRDR
P P P P P
2-1. INSTALLING THE UNIT
Fixherewith
M10bolts.
Makethesetting
depthdeeper.
Makewidthwider.
Anchor leg
25orless
Anchor bolt length
Anchorboltpitch
(Unit:mm)
2-2. CONNECTING WIRES FOR OUTDOOR UNIT
Terminalblock
forpowersupply
• Besuretoxtheunit’slegswithboltswheninstallingit.
• Besuretoinstalltheunitrmlytoensurethatitdoesnotfallbyanearthquakeoragust.
• Refertothegureintherightforconcretefoundation.
• Donotusethedrainsocketandthedraincapsinthecoldregion.
Drainmayfreezeanditmakesthefanstop.
• Removethetapeonthepanelwhenopeningthepackage.(DONOTremovetheLABELSonthepanel.)
1)Removetheservicepanel.
2)Loosenterminalscrew,andconnectindoor/outdoorunitconnectingwire
(B)fromtheindoorunitcorrectlyontheterminalblock.Becarefulnot
tomakemis-wiring.Fixthewiretotheterminalblocksecurelysothat
nopartofitscoreisappeared,andnoexternalforceisconveyedtothe
connectingsectionoftheterminalblock.
3)Firmlytightentheterminalscrewstopreventthemfromloosening.After
tightening,pullthewireslightlytoconrmthattheydonotmove.
4)Perform2)and3)foreachindoorunit.
5)Connectpowersupplycord(A).
6)Fixindoor/outdoorunitconnectingwire(B)andpowersupplycord(A)
withthecableclamps.
7)Closetheservicepanelsecurely.Makesurethat3-2.PIPECONNEC-
TIONiscompleted.
• After making connectionsbetweenbothpowersupplycord(A) and
indoor/outdoorunitconnectingwire(B),besuretoxbothcableand
wirewithcableclamps.
Connectingorder
• Connect theterminal block in
followingorder.
A
B
C
D
E
F
P
DR
Terminalblockforindoor/outdoorunit
Cableclamps
600
370
Servicepanel
Screws
Note:
• Removingthehandleincreasestheeffectivenessofthewiringoperation.
• Besuretoreinstallthehandle.
2. OUTDOOR UNIT INSTALLATION
Terminalblock
forDREDInterface
DREDInterface
Powersupply
35mm
15mm
Leadwire
• Besuretoattacheachscrewtoitscorrespondent
terminalwhensecuringthecordand/orthewireto
theterminalblock.
• Makeearthwirealittlelongerthanothers.
(Morethan35mm)
• Forfutureservicing,giveextralengthtothecon-
nectingwires.
1 2 3 C
<OUTDOORUNIT>
Indoor/outdoorunit
connectingwire
<INDOORUNIT>
Terminalblock
Terminalblock Terminalblock
Terminalblockfor
powersupply
Terminalblock
<INDOORUNIT>
POWERSUPPLY
~/N230V50Hz
ThisunithasdemandresponsecapabilitywhichiscompliantwithAS/NZS4755.3.1.Toactivatethisfunction,youneedtomakeacontractwithremote
agentssuchaselectricsupplycompany,thenthisunitshouldbeconnectedtoDemandresponseenablingdevise(DRED).Forfurtherinformation,
consultyourdealer.Thisunitsupports3DemandResponseModes(DRMs):DRM1,DRM2andDRM3.
CAUTION
•Topreventmalfunctioncausedbynoise,routethecordconnectingthisunittoDREDandthepowersupplycordasparallelaspossible.
•Donotconnectthedemandcontroltransmissioncabletotheterminalblockforpowersupply.
•Donotpull,extremelybendorapplystrongpressureonthewiretopreventfailure.
•DonotscrewDREDtooutdoorunit.
•DonotputDREDinoutdoorunit.
•Secureelectricalwiringaboveclamp.
•DonotgetDREDwirecaughtintheservicepanel.
1:DRM1
2:DRM2
3:DRM3
C:COMMON
AS/NZS4755
terminalblock
BH79A274H01_en.indd 4 2016/03/23 10:42:17
background
En-5
Fig. 1 Fig.2
Fig.3 Fig.4
Fig.5 Fig.6
3-1. FLARING WORK
Pipediameter
(mm)
Nut
(mm)
A(mm) Tighteningtorque
Clutch
typetool
forR410A
Clutch
typetool
forR22
Wing nut
typetool
forR22
N•m kgf•cm
ø6.35(1/4”) 17
0to0.5 1.0to1.5
1.5to2.0
13.7to17.7 140to180
ø9.52(3/8”) 22 34.3to41.2 350to420
ø12.7(1/2”) 26
2.0to2.5
49.0to56.4 500to575
ø15.88(5/8”) 29 73.5to78.4 750to800
TiltedUnevenBurred
Good
No good
Burr
Copperpipe
Sparereamer
Pipecutter
Smooth all
around
Evenlength
all around
Inside is shin-
ingwithoutany
scratches.
Flare nut
Die
Copperpipe
Clutchtype
Flaring tool
Wingnuttype
3-2. PIPE CONNECTION
1)Applyathincoatofrefrigerationoil(G)tothearedendsofthepipes
andthepipeconnectionsoftheoutdoorunit.Donotapplyrefrigeration
oilonscrewthreads.Excessivetighteningtorquewillresultindamage
onthescrew.
2)Alignthecenterofthepipewiththatofthepipeconnectionsoftheoutdoor
unit,thenhandtightenthearenut3to4turns.
3)Tightenthearenutwithatorquewrenchasspeciedinthetable.
• Over-tighteningmaycausedamagetothearenut,resultinginrefriger-
antleakage.
• Besuretowrapinsulationaroundthepiping.Directcontactwiththe
barepipingmayresultinburnsorfrostbite.
3-3. INSULATION AND TAPING
1)Coverpipingjointswithpipecover.
2)Foroutdoorunitside,surelyinsulateeverypipingincludingvalves.
3)Usingpipingtape(E),applytapingstartingfromtheentryofoutdoorunit.
• Stoptheendofpipingtape(E)withtape(withadhesiveagentattached).
• Whenpipinghavetobearrangedthroughaboveceiling,closetorwhere
thetemperatureandhumidityarehigh,windadditionalcommercially
soldinsulationtopreventcondensation.
Copper
pipe
1)Cutthecopperpipecorrectlywithpipecutter.(Fig.1,2)
2)Completelyremoveallburrsfromthecutcrosssectionofpipe.(Fig.3)
• Aimthecopperpipedownwardwhileremovingburrstopreventburrs
fromdroppinginthepipe.
3)Removearenutsattachedtoindoorandoutdoorunits,thenputthem
onpipehavingcompletedburrremoval.(Notpossibletoputthemon
afteraringwork.)
4)Flaringwork(Fig.4,5).Firmlyholdcopperpipeinthedimensionshown
in the table. Select A mm from the table according to the tool selected.
5)Check
• ComparethearedworkwithFig.6.
• Ifareisnotedtobedefective,cutoffthearedsectionanddoaring
workagain.
WARNING
When installing the unit, securely
connect the refrigerant pipes before
starting the compressor.
CAUTION
When there are the ports which are
not used, make sure their nuts are
tightened securely.
4-1. PURGING PROCEDURES AND LEAK TEST
1)Removeserviceportcapofstopvalveonthesideoftheoutdoorunit
gaspipe.(Thestopvalvesarefullyclosedandcoveredincapsintheir
initialstate.)
2)Connectgaugemanifoldvalveandvacuumpumptoserviceportofstop
valveonthegaspipesideoftheoutdoorunit.
3)Runthevacuumpump.(Vacuumizeformorethan15minutes.)
4)Checkthevacuumwithgaugemanifoldvalve,thenclosegaugemanifold
valve,andstopthevacuumpump.
5)Leaveasitisforoneortwominutes.Makesurethepointerofgauge
manifoldvalveremainsinthesameposition.Conrmthatpressuregauge
shows-0.101MPa[Gauge](-760mmHg).
6)Removegaugemanifoldvalvequicklyfromserviceportofstopvalve.
7)Fullyopenallstopvalvesonthegaspipeandtheliquidpipe.Operating
withoutfullyopeninglowerstheperformanceandthiscausestrouble.
8)Referto1-2.,andchargetheprescribedamountofrefrigerantifneeded.
Besuretochargeslowlywithliquidrefrigerant.Otherwise,composition
oftherefrigerantinthesystemmaybechangedandaffectperformance
of the air conditioner.
9)Tightencapofserviceporttoobtaintheinitialstatus.
10
)Leaktest
Stopvalve
forGAS
Gaugemani-
foldvalve(for
R410A)
Compoundpressure
gauge(forR410A)
–0.101MPa
(–760mmHg)
Handle
Low
HandleHigh
Vacuumpump
(forR410A)
Chargehose
(forR410A)
*Close
*Open
Hexagonal
wrench
*4to5turns
Stopvalve
forLIQUID
Pressuregauge
(forR410A)
Precautionswhenus-
ingthecontrolvalve
Whenattachingthecontrolvalve
totheserviceport,valvecoremay
deformorloosenifexcesspres-
sureisapplied.Thismaycause
gasleak.
Serviceport
Chargehose
(forR410A)
Body Close
Open
Controlvalve
A
Whenattachingthecontrolvalveto
theserviceport,makesurethatthe
valvecoreisinclosedposition,and
then tighten partA. Do nottighten
partA orturnthebodywhenvalve
coreisinopenposition.
4. PURGING PROCEDURES, LEAK TEST, AND TEST RUN
Stopvalvecap
(Torque24.4to
30.4N•m,250to
310kgf•cm)
Serviceportcap
(Torque10to12N•m,
100to120kgf•cm)
Serviceportcap
(Torque10to12N•m,
100to120kgf•cm)
Stopvalvecap
(Torque21.5to
27.5N•m,220
to280kgf•cm)
3. FLARING WORK AND PIPE CONNECTION
BH79A274H01_en.indd 5 2016/03/23 10:42:18
background
En-6
4-3. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)
4-4. LOWERING THE OPERATION NOISE OF THE OUTDOOR UNIT
4-2. GAS CHARGE
Performgaschargetounit.
1)Connectgascylindertotheserviceportofstopvalve.
2)Performairpurgeofthepipe(orhose)comingfromrefrigerantgascylinder.
3)Replenishspeciedamountoftherefrigerant,whileoperatingtheairconditioner
for cooling.
Note:
Incaseofaddingrefrigerant,complywiththequantityspeciedfortherefrigerat-
ing cycle.
CAUTION:
Whenchargingtherefrigerantsystemwithadditionalrefrigerant,besuretouse
liquidrefrigerant.Addinggasrefrigerantmaychangethecompositionoftherefriger-
antinthesystemandaffectnormaloperationoftheairconditioner.Also,charge
theliquidrefrigerantslowly,otherwisethecompressorwillbelocked.
Tomaintain the highpressure of thegas cylinder, warm the gas cylinder with
warmwater(under40°C)duringcoldseason.Butneverusenakedreorsteam.
COOL/DRY HEAT
• Descriptionofthefunction:
Withthisfunction, once theoperationmodeis locked toeitherCOOL/DRYmodeor
HEATmode,theairconditioneroperatesinthatmodeonly.
* Changingthesettingisrequiredtoactivatethisfunction.Pleaseexplainaboutthisfunc-
tiontoyourcustomersandaskthemwhethertheywanttouseit.
[How to lock the operation mode]
1)Besuretoturnoffthemainpowerfortheairconditionerbeforemakingthesetting.
2)Setthe“3”ofSW1ontheoutdoorcontrollerboardtoONtoenablethisfunction.
3)TolocktheoperationmodeinCOOL/DRY mode,setthe“4”ofSW1onthe outdoor
controllerboardtoOFF.TolocktheoperationinHEATmode,setthesameswitchto
ON.
4)Turnonthemainpowerfortheairconditioner.
• Descriptionofthefunction:
Withthisfunction,theoperatingnoiseoftheoutdoorunitcanbeloweredbyreducingtheoperationload,forexample,duringnighttimeinCOOLmode.
However,pleasenotethatthecoolingandheatingcapacitymaylowerifthisfunctionisactivated.
* Changingthesettingisrequiredtoactivatethisfunction.Pleaseexplainaboutthisfunctiontoyourcustomersandaskthemwhethertheywanttouseit.
Union
Stopvalve
Liquid
pipe
Indoor
unit
Stopvalvewith
serviceport
Gas
pipe
Refrigerant gas
cylinder
operatingvalve
(forR410A)
Gaugemanifold
valve(forR410A)
Chargehose
(forR410A)
RefrigerantgascylinderforR410Awithsiphon
Electronic scale for refrigerant charging
Refrigerant(liquid)
Outdoor
unit
Union
Union
Union
SW1
ON
1 2 3 4 5 6
SW1
ON
1 2 3 4 5 6
SW1
ON
1 2 3 4 5 6
Lowertheoperatingnoise
[How to lower the operating noise]
1)Besureto turn off themainpowerfortheairconditionerbeforemaking the
setting.
2)Setthe“5”ofSW1ontheoutdoorcontrollerboardtoONtoenablethisfunction.
3)Turnonthemainpowerfortheairconditioner.
LED
SW1
SW871
SW2
Terminalblock
forDREDInterface
BH79A274H01_en.indd 6 2016/03/23 10:42:18
background
En-7
4-5. TEST RUN
• Testrunsoftheindoorunitsshouldbeperformedindividually.Seetheinstallationmanualcomingwiththeindoorunit,andmakesurealltheunitsoperate
properly.
• Ifthetestrunwithalltheunitsisperformedatonce,possibleerroneousconnectionsoftherefrigerantpipesandtheindoor/outdoorunitconnectingwires
cannotbedetected.Thus,besuretoperformthetestrunonebyone.
About the restart protective mechanism
Oncethecompressorstops,therestartpreventivedeviceoperatessothecompressorwillnotoperatefor3minutestoprotecttheairconditioner.
Wiring/piping correction function
Thisunithasawiring/pipingcorrectionfunctionwhichcorrectswiringandpipingcombination.Whenthereispossibilityofincorrectwiringandpipingcombi-
nation,andconrmingthecombinationisdifcult,usethisfunctiontodetectandcorrectthecombinationbyfollowingtheproceduresbelow.
Makesurethatthefollowingisdone.
• Powerissuppliedtotheunit.
• Stopvalvesareopen.
Note:
Duringdetection,theoperationoftheindoorunitiscontrolledbytheoutdoorunit.Duringdetection,theindoorunitautomaticallystopsoperation.Thisisnot
a malfunction.
Procedure
Pressthepiping/wiringcorrectionswitch(SW871)1minuteormoreafterturningonthe
powersupply.
• Correctioncompletesin10to20minutes.Whenthecorrectioniscompleted,itsresult
isshownbyLEDindication.Detailsaredescribedinthefollowingtable.
• Tocancelthisfunctionduringitsoperation,pressthepiping/wiringcorrectionswitch
(SW871)again.
• Whenthecorrectioncompletedwithouterror,donotpressthepiping/wiringcorrection
switch(SW871)again.
When the result was “cannot be corrected”, press thepiping/wiring correction switch
(SW871)againtocancelthisfunction.Then,conrmthewiringandpipingcombinationin
aconventionalmannerbyoperatingtheindoorunitsonebyone.
• Theoperationisdonewhilethepowerissupplied.Makesurenottocontactpartsother
thantheswitch,includingtheP.C.board.Thismaycauseelectricshockorburnbyhot
partsandlivepartsaroundtheswitch.ContactingthelivepartsmaycauseP.C.board
damage.
• TopreventelectroniccontrolP.C.boarddamage,makesuretoperformstaticelimination
beforeoperatingthisfunction.
• Thisfunctiondoesnotoperatewhentheoutsidetemperatureis0°Corbelow.
LED indication during detection:
LED1
(Red)
LED2
(Yellow)
LED3
(Green)
Lighted Lighted Once
Result of piping/wiring correction function
LED1
(Red)
LED2
(Yellow)
LED3
(Green)
Result
Lighted Not lighted Lighted
Completed
(Problemcorrectedor
normal)
Once Once Once
Notcompleted
(Detectionfailed)
Otherindications
Referto“SAFETYPRE-
CAUTIONSWHENLED
BLINKS”locatedbehind
theservicepanel.
4-6. EXPLANATION TO THE USER
• UsingtheOPERATINGINSTRUCTIONS,explaintotheuserhowtousetheairconditioner(howtousetheremotecontroller,howtoremovetheairlters,
howtoremoveorputtheremotecontrollerintheremotecontrollerholder,howtoclean,precautionsforoperation,etc.).
• RecommendtheusertoreadtheOPERATINGINSTRUCTIONScarefully.
Whenrelocatingordisposingoftheairconditioner,pumpdownthesystemfollowingtheprocedurebelowsothatnorefrigerantisreleasedintotheatmosphere.
1)Turnoffthebreaker.
2)Connectthegaugemanifoldvalvetotheserviceportofthestopvalveonthegaspipesideoftheoutdoorunit.
3)Fullyclosethestopvalveontheliquidpipesideoftheoutdoorunit.
4)Turnonthebreaker.
5)StarttheemergencyCOOLoperationonalltheindoorunits.
6)Whenthepressuregaugeshows0–0.05MPa[Gauge](approx.0–0.5kgf/cm
2
),fullyclosethestopvalveonthegaspipesideoftheoutdoorunitand
stoptheoperation.(Refertotheindoorunitinstallationmanualaboutthemethodforstoppingtheoperation.)
* Iftoomuchrefrigeranthasbeenaddedtotheairconditionersystem,thepressuremaynotdropto0–0.05MPa[Gauge](approx.0–0.5kgf/cm
2
),or
theprotectionfunctionmayoperateduetothepressureincreaseinthehigh-pressurerefrigerantcircuit.Ifthisoccurs,usearefrigerantcollectingdevice
tocollectalloftherefrigerantinthesystem,andthenrechargethesystemwiththecorrectamountofrefrigerantaftertheindoorandoutdoorunitshave
been relocated.
7)Turnoffthebreaker.Removethepressuregaugeandtherefrigerantpiping.
When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.
The compressor may burst and cause injury if any foreign substance, such as air, enters the pipes.
WARNING
5. PUMPING DOWN
BH79A274H01_en.indd 7 2016/03/23 10:42:18
background
C
M
Y
CM
MY
CY
CMY
K
blank(A4-tombo-blank).pdf 2014/03/17 15:06:22
background
C
M
Y
CM
MY
CY
CMY
K
blank(A4-tombo-blank).pdf 2014/03/17 15:06:22
background
C
M
Y
CM
MY
CY
CMY
K
blank(A4-tombo-blank).pdf 2014/03/17 15:06:22
background
BH79A274H01
HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
BH79A274H01_cover.indd 1 2016/04/07 19:03:22

Specifications

Mitsubishi MXZ-6E120VAD Questions and Answers

Questions and Answers

Related Products