User Manual - Page 27

For INF20N50M. Also, The document are for others Rinnai models: INFINITY 32, REU-VRM3237WG, INFINITY 26, REU- VRM2626WG, INFINITY 26I, REU-VRM2632FFUG, INFINITY 20, REU-VRM2024WG, INFINITY 16, REU-VRM1620WG, INFINITY ENVIRO 32, REU-KM3237WD, INFINITY ENVIRO 26, REU-KM2635WD, B16, REU-VR1620WB, B20, REU-VR2024WB, B26, REU-VR2626WB, HD250E, REU-VRM3237WC, HD200E, REU-VRM2632WC, HD200I, REU-VRM2632FFUC, HDC211E, REU-KM3237WDC, HDC211I, REU-KM3237FFUDC

Loading ...
Loading ...
Loading ...
Rinnai Australia 24 Installation Manual
GENERAL INSTALLATION INSTRUCTIONS
HORIZONTAL FLUE TERMINAL CLEARANCES
Extract from AS/NZS 5601
Flue terminal Fan assisted flue appliance only Gas meter Electricity meter or fuse box Mechanical air inlet
Min. Clearances
(mm)
Fan-Assisted
Appliances up to 50 MJ/h input
200
Appliances over 50 MJ/h input
300
b From the ground, above a balcony or other surface * 300
c Front a return wall or external corner * 300
d
From a gas meter (M) (see 5.11.5.9 for vent terminal location of regulator )
(see Table 6.6 for New Zealand requirements)
1000
e
From an electricity meter or fuse box (P) †
500
f From a drain pipe or soil pipe 75
g
Horizontally from any building structure* = or obstruction facing a terminal
500
h
From any other flue terminal , cowl, or combustion air intake †
300
Appliances up to 150 MJ/h input *
300
Appliances over 150 MJ/h input up to 200 MJ/h input *
300
Appliances over 200 MJ/h input up to 250 MJ/h input *
500
Appliances over 250 MJ/h input *
1500
• All fan-assisted flue appliances , in the direction of discharge
1500
k From a mechanical air inlet, including a spa blower 1000
• Space heaters up to 50 MJ/hr input 150
• Other appliances up to 50 MJ/hr input
500
Appliances over 50 MJ/h input and up to 150 MJ/h input
1000
Appliances over 150 MJ/h input
1500
1
Where dimensions c, j or k cannot be achieved an equivalent horizontal distance
measured diagonally from the nearest discharge point of the terminal to the opening
may be deemed by the Technical Regulator to comply.
2
See Clause 6.9.4 for restrictions on a flue terminal under a covered area.
3
See Figure J3 for clearances required from a flue terminal to an LP Gas cylinder.
A flue terminal is considered to be a source of ignition.
4
For appliances not addressed above acceptance should be obtained from the
Technical Regulator.
Ref. Item
a
Below eaves, balconies and other projections:
FIGURE 6.2 (in-part) MINIMUM CLEARANCES REQUIRED FOR FAN-ASSISTED FLUE TERMINALS, ROOM-
SEALED APPLIANCE TERMINALS AND OPENINGS OF OUTDOOR APPLIANCES
* - unless appliance is certified for closer installation
n
j
Horizontally from an openable window, door, non-mechanical air inlet, or any other opening into a
building with the exception of sub-floor ventilation:
Vertically below an openable window, non-mechanical air inlet, or any other opening into a
building with the exception of sub-floor ventilation:
NOTES:
† - Prohibited area below electricity meter or fuse box extends to ground level.
Loading ...
Loading ...
Loading ...