Loading ...
Loading ...
Loading ...
19
Remove the terminal block access cover
on the upper back of the dryer. Install a
UL-listed strain relief into the power cord
through-hole; then thread a UL-listed, 30A,
240V, 4-wire, #10 AWG-minimum copper
conductor power cord through the
strain relief.
1
Transfer the dryer’s ground wire from behind
the green ground screw to the center screw
of the terminal block. Attach the two hot
leads of the power cord to the outer terminal
block screws. Attach the white neutral wire
to the center terminal block screw. Attach the
power cord ground wire to the green ground
screw. TIGHTEN ALL SCREWS SECURELY.
Reinstall the terminal block access cover.
2
UL-Listed
Strain Relief
UL-Listed
4-Wire
Power Cord
Terminal
Block
Ground Screw
Neutral
(White)
Hot
(Black)
Power Cord
Ground Wire
Hot
(Red)
CONNECTING ELECTRIC DRYERS
Four-Wire Connection for Electric Dryers: Power Cord
•A4-wireconnectionisrequiredforallmobile
and manufactured home installations, as well
as all new construction after January 1, 1996.
•AUL-listedstrainreliefisrequired.
•Usea30-amp,240V,UL-listedpowercord
with #10 AWG-minimum copper conductor
and closed loop or forked terminals with
upturned ends.
wWARNING:
•Connectthepowercordtotheterminalblock.Eachcoloredwireshouldbeconnectedto
same color screw. Wire color indicated on manual is connected to the same color screw
in block. Failure to follow these instructions may result in a short or overload.
•Groundingthroughtheneutralconductorisprohibitedfor:(1)newbranch-circuit
installations, (2) mobile homes, (3) recreational vehicles, and (4) areas where local
codes prohibit grounding through the neutral conductor.
Loading ...
Loading ...
Loading ...