Heat pump unit shall automatically switch from heat pump
operation to electric resistance heat when it is unable to
provide sufficient heat to maintain room temperature or
when the outdoor temperature falls below 25°F.
Unit shall be equipped with a temperature activated valve
to allow condensate water generated during defrost cycles
to drain into the specified drain system.
Unit shall have a concealed switch to allow heat pump
operation to be overridden and heat provided by electric
resistance heaters regardless of outdoor temperatures.
Heat pump unit shall have Reverse Cycle (hot gas) Defrost
system to maximize heat pump operation and minimize
energy consumption.
To minimize energy consumption, units shall have electric
heaters locked out when outdoor temperatures are above
46°F. Heating will be provided by heat pump operation only.
In the event of a compressor failure during heat pump
operation, the unit shall automatically switch to electric
resistance heat to maintain selected room temperature
regardless of outdoor temperatures.
When the heat mode is selected or when the unit is switched
from off to on in heat mode, the unit shall energize electric
heaters to quickly warm the room to wall thermostat set
point. Heat pump operation will resume on subsequent
heating requirements.
Unit shall have an indoor coil temperature sensor to protect
the compressor when the outdoor temperatures are too high
for heat pump operation.
ADDITIONAL SPECIFICATIONS
SERVICE
Submit complete information with bid covering service
availability, to whom service on units will be assigned,
complete address and phone number, including phone
number of emergency service personnel.
STARTUP, ADJUST, DEMONSTRATE
Contractor shall be responsible for the initial starting
of units, adjustments thereto, cleaning, etc., to place the
units in required operating condition. Contractor shall
demonstrate to the owner, or his representative, the
operation of units for both summer and winter functions.
WARRANTY
ONE YEAR - FROM THE DATE OF THE
ORIGINAL PURCHASE
GE Appliances will replace: Any part of the air conditioner
which fails due to a defect in materials or workmanship.
During this limited one-year warranty, GE will provide,
free of charge, all labor and related service costs to replace
the defective part.
FIVE YEARS - FROM THE DATE OF THE
ORIGINAL PURCHASE
GE Appliances will replace: Sealed Refrigerating System,
if any part of the Sealed Refrigerating System (the compressor,
condenser, evaporator, and all connecting tubing) should
fail due to a defect in materials or workmanship. During this
limited five-year warranty, GE will provide, free of charge,
all labor and related service costs to replace the defective part.
SECOND THROUGH FIFTH YEAR - FROM
THE DATE OF THE ORIGINAL PURCHASE
GE Appliances will replace: Fan Motors, Switches,
Thermostat, Heater, Heater Protectors, Compressor
Overload, Solenoids, Circuit Boards, Auxiliary Controls,
Thermistors, Freeze Sentinel, Frost Controls, ICR Pump,
Capacitors, Varistors and Indoor Blower Bearing, if any
of these parts should fail due to a defect in materials or
workmanship. During this additional four-year limited
warranty, the customer will be responsible for any labor
and related service costs.
Ge Appliances Vertical Zoneline Heat Pumps
ADDITIONAL SPECIFICATIONS