LG ARUM241DTE5 Air Conditioners

Product's Documents

Below are documents related to this product, you can read online or download:
ARUM241DTE5 photo

User Manual

This is the main product document for model ARUM241DTE5.

The file format is pdf, 60 pages, you can download this manual here .

background
INSTALLATION MANUAL
AIR
CONDITIONER
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring standards
by authorized personnel only.
Please retain this installation manual for future reference after reading it thoroughly.
For Heat Pump / Heat Recovery system
Original instruction
MFL68980308
Rev.01_110718
www.lghvac.com
www.lg.com
Copyright © 2016 - 2018 LG Electronics Inc. All Rights Reserved.
ENGLISH
FRANÇAIS
ESPAÑOL
1,MFL68980308,영영 2018. 11. 13. 영영 3:22 Page 1
background
2
ENGLISH
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption
when you use the air conditioner. You can use your air conditioner
more efficiently by referring to the instructions below:
IMPORTANT SAFETY
INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE
APPLIANCE.
Always comply with the following precautions to avoid dangerous
situations and ensure peak performance of your product.
WARNING
It can result in serious injury or death when the directions are ignored.
CAUTION
It can result in minor injury or product damage when the directions are
ignored.
WARNING
• Installation or repairs made by unqualified persons can result in
hazards to you and others. Installation of all field wiring and
components MUST conform with local building codes or, in the
absence of local codes, with the National Electrical Code 70 and the
National Building Construction and Safety Code or Canadian
Electrical code and National Building Code of Canada.
• The information contained in the manual is intended for use by a
qualified service technician familiar with safety procedures and
equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can
result in equipment malfunction, property damage, personal injury
and/or death.
Installation
• Have all electric work done by a licensed electrician according to
"Electric Facility Engineering Standard" and "Interior Wire Regulations"
and the instructions given in this manual and always use a special
circuit.
- If the power source capacity is inadequate or electric work is
performed improperly, electric shock or fire may result.
• Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage, electric
shock, or fire.
• Always ground the product.
- There is risk of fire or electric shock.
• Always intstall a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• For re-installation of the installed product, always contact a dealer or an
Authorized Service Center.
- There is risk of fire, electric shock, explosion, or injury.
• Do not install, remove, or re-install the unit by yourself (customer).
- There is risk of fire, electric shock, explosion, or injury.
• Do not store or use flammable gas or combustibles near the air
conditioner.
- There is risk of fire or failure of product.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Prepare for strong wind or earthquake and install the unit at the
specified place.
- Improper installation may cause the unit to topple and result in injury.
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Use a vacuum pump or Inert(nitrogen) gas when doing leakage test or
air purge. Do not compress air or Oxygen and do not use Flammable
gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
• When installing and moving the air conditioner to another site, do not
charge it with a different refrigerant from the refrigerant specified on the
unit.
- If a different refrigerant or air is mixed with the original refrigerant, the
refrigerant cycle may malfunction and the unit may be damaged.
• Do not reconstruct to change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is
shorted and operated forcibly, or parts other than those specified by
LGE are used, fire or explosion may result.
• Ventilate before operating air conditioner when gas leaked out.
- It may cause explosion, fire, and burn.
• Securely install the cover of control box and the panel.
- If the cover and panel are not installed securely, dust or water may
enter the outdoor unit and fire or electric shock may result.
• If the air conditioner is installed in a small room, measures must be
taken to prevent the refrigerant concentration from exceeding the safety
limit when the refrigerant leaks.
- Consult the dealer regarding the appropriate measures to prevent the
safety limit from being exceeded. Should the refrigerant leak and cause
the safety limit to be exceeded, harzards due to lack of oxygen in the
room could result.
Operation
• Do not damage or use an unspecified power cord.
- There is risk of fire, electric shock, explosion, or injury.
• Use a dedicated outlet for this appliance.
- There is risk of fire or electrical shock.
• Be cautious that water could not enter the product.
- There is risk of fire, electric shock, or product damage.
• Do not touch the power switch with wet hands.
- There is risk of fire, electric shock, explosion, or injury.
• When the product is soaked (flooded or submerged), contact an
Authorized Service Center.
- There is risk of fire or electric shock.
• Be cautious not to touch the sharp edges when installing.
- It may cause injury.
• Take care to ensure that nobody could step on or fall onto the outdoor
unit.
- This could result in personal injury and product damage.
• Do not open the inlet grille of the product during operation. (Do not
touch the electrostatic filter, if the unit is so equipped.)
- There is risk of physical injury, electric shock, or product failure.
!
!
!
• Do not cool excessively indoors. This may be harmful for your health
and may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air
conditioner.
• Keep doors or windows closed tightly while you are operating the air
conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate
indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period
of time.
• Open windows regularly for ventilation as the indoor air quality may
deteriorate if the air conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected
in the air filter may block the air flow or weaken the cooling /
dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of
purchase or for warranty purposes. Write the model number and the
serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
1,MFL68980308,영영 2018. 11. 13. 영영 3:22 Page 2
background
3
CAUTION
Installation
• Always check for gas (refrigerant) leakage after installation or repair of
product.
- Low refrigerant levels may cause failure of product.
• Do not install the product where the noise or hot air from the outdoor
unit could damage the neighborhoods.
- It may cause a problem for your neighbors.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may
result.
• Use power cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.
• Do not use the product for special purposes, such as preserving foods,
works of art, etc. It is a consumer air conditioner, not a precision
refrigeration system.
- There is risk of damage or loss of property.
• Keep the unit away from children. The heat exchanger is very sharp.
- It can cause the injury, such as cutting the finger. Also the damaged fin
may result in degradation of capacity.
• When installting the unit in a hospital, communication station, or similar
place, provide sufficient protection against noise.
- The inverter equipment, private power generator, high-frequency
medical equipment, or radio communication equipment may cause the
air conditioner to operate erroneously, or fail to operate. On the other
hand, the air conditioner may affect such equipment by creating noise
that disturbs medical treatment or image broadcasting.
• Do not install the product where it is exposed to sea wind (salt spray)
directly.
- It may cause corrosion on the product. Corrosion, particularly on the
condenser and evaporator fins, could cause product malfunction or
inefficient operation.
Operation
• Do not use the air conditioner in special environments.
- Oil, steam, sulfuric smoke, etc. can significantly reduce the
performance of the air conditioner or damage its parts.
• Do not block the inlet or outlet.
- It may cause failure of appliance or accident.
• Make the connections securely so that the outside force of the cable
may not be applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a
fire.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing
property damage, product failure, or personal injury.
• Install and insulate the drain hose to ensure that water is drained away
properly based on the installation manual.
- A bad connection may cause water leakage.
• Be very careful about product transportation.
- Only one person should not carry the product if it weighs more than
20 kg (44 lbs).
- Some products use PP bands for packaging. Do not use any PP bands
for a means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, suspending it at the specified
positions on the unit base. Also support the outdoor unit at four points
so that it cannot slip sideways.
• Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or wooden parts, may
cause stabs or other injuries.
- Tear apart and throw away plastic packaging bags so that children may
not play with them. If children play with a plastic bag which was not
torn apart, they face the risk of suffocation.
• Turn on the power at least 6 hours before starting operation.
- Starting operation immediately after turning on the main power switch
can result in severe damage to internal parts. Keep the power switch
turned on during the operational season.
• Do not touch any of the refrigerant piping during and after operation.
- It can cause a burn or frostbite.
• Do not operate the air conditioner with the panels or guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
• Do not directly turn off the main power switch after stopping operation.
- Wait at least 5 minutes before turning off the main power switch.
Otherwise it may result in water leakage or other problems.
• Auto-addressing should be done in condition of connecting the power of
all indoor and outdoour units. Auto-addressing should also be done in
case of changing the indoor unit PCB.
• Use a firm stool or ladder when cleaning or maintaining the air
conditioner.
- Be careful and avoid personal injury.
• Do not insert hands or other objects through the air inlet or outlet while
the air conditioner is plugged in.
- There are sharp and moving parts that could cause personal injury.
!
ENGLISH
1,MFL68980308,영영 2018. 11. 13. 영영 3:22 Page 3
background
4
ENGLISH
52 High Efficiency Mode (Cooling Operation) (Fn 10)
52 Auto Dust Removal Mode (Fn 11)
53 Compressor Max. Frequency Limit (Fn 12)
53 ODU Fan Max. RPM Limit (Fn 13)
53 SLC (Smart Load Control) (Fn 14)
53 Humidity Reference Control (Fn 16)
54 Central Control Connection at Indoor Unit side (Fn 19)
54 Compressor Input Current Limit Mode (Fn 20)
54 Overall Defrost Operating in Low temperature (Heating) (Fn 22)
54 Base pan Heater operation (Fn 23)
55 Comfort Cooling operation (Id 10)
56 Self-Diagnosis Function
58 CAUTION FOR REFRIGERANT LEAK
58 Introduction
58 Checking procedure of limiting concentration
59 INSTALLATION GUIDE AT THE SEASIDE
60 Model Designation
2 TIPS FOR SAVING ENERGY
2 IMPORTANT SAFETY INSTRUCTIONS
5 INSTALLATION PROCESS
5 OUTDOOR UNITS INFORMATION
5 ALTERNATIVE REFRIGERANT R410A
5 SELECT THE BEST LOCATION
7 INSTALLATION SPACE
7 Individual Installation
7 LIFTING METHOD
8 INSTALLATION
8 The location of the Anchor bolts
8 Foundation for Installation
8 Preparation of Piping
10 Plumbing materials and storage methods
11 REFRIGERANT PIPING INSTALLATION
11 Precautions on Pipe connection / Valve operation
11 Connection of Outdoor units
12 Installation procedure for HR unit
12 Installation of Outdoor Unit, HR Unit, Indoor Unit Refrigerant
Pipe
12 Type of HR Unit
13 Installation of Zoning Control
14 Caution
14 Precautions on Pipe connection / Valve operation
15 Connection of Outdoor units
15 Caution
16 PIPE CONNECTIONS BETWEEN INDOOR
AND OUTDOOR UNIT
16 Preparation Work
17 Pipe Drawing Out during Single / Series connection
17 Refrigerant piping system
19 Preparation Work
20 Pipe Drawing Out during Single / Series connection
20 Refrigerant piping system
21 Series Outdoor Units (2 Units ~ 3 Units)
21 Pipe Connection Method between outdoor unit/indoor unit
25 Refrigerant charging
25 Branch pipe Fitting
29 Distribution Method
29 Vacuum Mode
30 Leak Test and Vacuum drying
31 Thermal insulation of refrigerant piping
32 ELECTRICAL WIRING
32 Caution
33 Control box and connecting position of wiring
33 Communication and Power Cables
34 Wiring of main power supply and equipment capacity
34 Field Wiring
38 Checking the setting of outdoor units
40 Switch for setup of HR Unit
44 Automatic Addressing
45 The Procedure of Automatic Addressing
46 Flow chart of auto pipe detection Process
47 Flow chart of manual addressing for pipe detection
47 Example of manual valve addressing (Non-Zoning setting)
48 Example of manual valve addressing (Zoning setting)
48 Method of checking the pipe detection result at HR unit
48 Identification of Manual Valve ID (Address)
48 Method of checking the pipe detection result at outdoor unit
48 Setting method of Master indoor unit in zoning
49 Group Number setting
50 Cool & Heat selector (Fn 1)
50 High Static Pressure Compensation mode (Fn 2)
50 Night Low Noise Function (Fn 3)
51 Overall HEX defrost mode (Fn 4)
51 Setting the ODU address (Fn 5)
51 Snow removal & rapid defrost (Fn 6)
52 Target pressure adjusting (Fn 8)
52 Low Ambient Kit (Fn 9)
TABLE OF CONTENTS
1,MFL68980308,영영 2018. 11. 13. 영영 3:22 Page 4
background
• The wall thickness of the piping should comply with the relevant
local and national regulations for the designed pressure 3.8 MPa
[551.1 psi]
• Since R410A is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state.
If the refrigerant is charged in its gaseous state, its composition
changes and the system will not work properly.
• Do not place the refrigerant container under the direct rays of
the sun to prevent it from exploding.
• For high-pressure refrigerant, any unapproved pipe must not be
used.
• Do not heat pipes more than necessary to prevent them from
softening.
• Be careful not to install wrongly to minimize economic loss
because it is expensive in comparison with R22.
CAUTION
!
5
ENGLISH
SELECT THE BEST LOCATION
Select space for installing outdoor unit, which will meet the following
conditions:
• No direct thermal radiation from other heat sources
• No possibility of annoying neighbors due to noise of unit
• No exposition to strong wind
• With strength which bears weight of unit
• Note that drain flows out of unit when heating
• Because of the possibility of fire, do not install unit to the space
where generation, inflow, stagnation, and leakage of combustible gas
is expected.
ALTERNATIVE REFRIGERANT R410A
The refrigerant R410A has the property of higher operating pressure in
comparison with R22.
Therefore, all materials have the characteristics of higher resisting
pressure than R22 ones and this characteristic should also be
considered during the installation.
R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone
depletion potential (ODP) of R410A is 0.
Notes : * We can guarantee the operation only within 130 %
combination.
Combination Ratio(50~130 %)
Outdoor Number Connection Capacity
Single outdoor units
130 %Double outdoor units
Triple outdoor units
OUTDOOR UNITS INFORMATION
The foundation must be level even
Outdoor unit foundation work
Avoid short circuits and ensure
sufficient space is allowed for service
Installation of outdoor unit
Refer to automatic addressing flowchart
Automatic addressing of indoor unit
In the final check for 24 hours at 3.8 MPa (38.7 kgf/cm
2
)[551.1 psi]
there must be no drop in pressure.
Airtight test
Multiple core cable must not be used.
(suitable cable should be selected)
Electrical work
(connection circuits and drive circuits)
Make sure no gaps are left where
the insulating materials are joined
Heat insulation work
Make sure airflow is sufficient
Duct work
Adjust to downward gradient
Drain pipe work
Special attention to dryness,
cleanness and tightness
Refrigerant piping work
Check model name to
make sure the fitting
is made correctly
Installation of indoor unit
Take account of gradient
of drain piping
Sleeve and insert work
Make connection clearly between outdoor, indoor,
remote controller and option.
Preparation of contract drawings
Indicate clearly who will be responsible for switch setting.
Determination of division work
The vacuum pump used must have a capacity of reaching at least
5 torr, more than 1 hour
Vacuum drying
Recharge correctly as calculated in this manual. and record the
amount of added refrigerant
Additional charge of refrigerant
Make sure there are no gaps left between the facing materials
used on the ceiling
Fit facing panels
Run each indoor unit in turn to make sure the pipe work
has been fitted correctly
Test run adjustment
Explain the use of the system as clearly as possible to your customer and
make sure all relevant documentation is in order
Transfer to customer with explanation
Preheat the crank case with the electrical heater for more than 6 hours.
INSTALLATION PROCESS
CAUTION
!
• The above list indicates the order in which the individual work
operations are normally carried out but this order may be varied
where local conditions warrants such change.
• The thickness of the piping should comply with the relevant local
and national regulations for the designed pressure 3.8 MPa
(551.1 psi).
• Since R410A is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state.(If the refrigerant is
charged in its gaseous state, its composition changes and the
system will not work properly.)
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:22 Page 5
background
6
ENGLISH
Select installation location of the HR unit suitable for following
conditions
- Avoid a place where rain may enter since the HR unit is for indoor.
- Sufficient service space must be obtained.
- Refrigerant pipe must not exceed limited length.
- Avoid a place subject to a strong radiation heat from other heat
source.
- Avoid a place where oil spattering, vapor spray or high frequency
electric noise is expected.
- Install the unit at a place in which it is not affected by operation noise.
(Installation within cell such as meeting room etc. may disturb
business due to noise.)
- Place where refrigerant piping, drain piping and electrical wiring
works are easy.
2 Series
• Avoid unit installation in a place where acidic solution and spray
(sulfur) are often used.
• Do not use unit under any special environment where oil, steam and
sulfuric gas exist.
• It is recommended to fence round the outdoor unit in order to
prevent any person or animal from accessing the outdoor unit.
• If installation site is area of heavy snowfall, then the following
directions should be observed.
- Make the foundation as high as possible.
- Fit a snow protection hood.
Select installation location considering following conditions to avoid
bad condition when additionally performing defrost operation.
- Install the outdoor unit at a place well ventilated and having a lot of
sunshine in case of installing the product at a place With a high
humidity in winter (near beach, coast, lake, etc.)
(Ex : Rooftop where there is always sunshine.)
3 Series
Unit: mm(inch)
No. Part Name
Description
PRHR042A
PRHR032A
PRHR083A
PRHR063A
PRHR043A
PRHR033A
PRHR022A
PRHR023A
1
Low pressure Gas
pipe connection port
Ø 28.58 (1-1/8)
Brazing connection
Ø 22.2 (7/8) Brazing
connection
2
High pressure Gas
pipe connection port
Ø 22.2 (7/8) Brazing
connection
Ø 19.05 (3/4) Brazing
connection
3
Liquid pipe
connection port
Ø 15.88 (5/8) Brazing
connection
(PRHR042A)
Ø 9.52 (3/8) Brazing
connection
Ø 12.7 (1/2) Brazing
connection
(PRHR032A)
4
Indoor unit Gas pipe
connection port
Ø 15.88 (5/8) Brazing
connection
Ø 15.88 (5/8) Brazing
connection
5
Indoor unit Liquid
pipe connection port
Ø 9.52 (3/8) Brazing
connection
Ø 9.52 (3/8) Brazing
connection
6 Control box - -
7 Hanger metal M10 or M8 M10 or M8
NOTE
!
• Be sure to install the inspection door at the control box side.
• If reducers are used, servicing space must be increased equal to
reducer's dimension.
For Heat Recovery Installation
54
6
419 (16-1/2)
61
(2-13/32)
137
(5-13/32)
124 (4-7/8)
128 (5-1/32)
30
(1-3/16)
60
(2-3/8)
More than
300 (11-13/16)
(Servicing space)
More than
450 (17-23/32)
(Servicing space)
More than 100 (3-15/16)
More than 100 (3-15/16)
(Servicing space)
(Servicing space)
More than 100 (3-15/16)
(Servicing space)
More than 100 (3-15/16)
More than 100 (3-15/16)
(Servicing space)
(Servicing space)
More than
300 (11-13/16)
More than
300 (11-13/16)
(Servicing space) (Servicing space)
More than 100 (3-15/16)
(Servicing space)
453 (17-27/32)
174
(6-27/32)
174
(6-27/32)
182
(7-5/32)
218 (8-19/32)
Inspection door
(servicing space)
481 (18-15/16)
1
2
3
7
450 (17-23/32)
450 (17-23/32)
345 (13-19/32)
345 (13-19/32)
345 (13-19/32)
300(11-13/16)
300(11-13/16) more
300(11-13/16)
254(10)
more
(Servicing space) (Servicing space)
(Servicing space)
(Servicing space)
500(19-11/16)
7
311(12-1/4)
6(1/4) more (Serviceing space)
6(1/4) more (Serviceing space)
126(4-31/32)
147(5-23/32)
6
54
19(3/4)
55(2-5/32)
389(15-5/16)
92
(3-5/8)
176(6-15/16)
Inspection door
(servicing space)
500(19-11/16)
254(10)
1
2
3
150(5-29/32) 486(19-1/8) 150(5-29/32)
165(6-1/2)
218(8-19/32)
300(11-13/16) more
300(11-13/16) more
300(11-13/16)
254(10)
more
(Servicing space) (Servicing space)
(Servicing space)
(Servicing space)
7
311(12-1/4)
809(31-27/32)
793(31-7/32)
160
(6-5/16)
160
(6-5/16)
218(8-19/32)
165
(6-1/2)
1
2
3
19(3/4)
55(2-5/32)
389(15-5/16)
92(3-5/8)
176(6-15/16)
147(5-23/32)
126(4-31/32)
5
4
6
254(10)
Inspection door
(servicing space)
800(31-1/2)
6(1/4) more (Serviceing space)
6(1/4) more (Serviceing space)
1,MFL68980308,영영 2018. 11. 13. 영영 3:22 Page 6
background
Limitati
ons on
the
height
of the
wall
(Refer
to 4
side
walls)
h2
h1
1500 (59)
Inlet
side
A
B
50500
(19-11/16’’)(19-11/16’’)
500
(19-11/16’’)
Front
side
500
(19-11/16)
240
(9-1/2’’)
or more
50 (2) or more
45° or
more
• The height of the wall on the front side must
be 1500 mm (59 inch) or less.
• The height of the wall on the inlet side must
be 500 mm (19-11/16’’) or less.
• There is no limit to the wall on Inlet side.
• If the height of the walls on the front and Inlet
side are higher than the limit, there must be
additional space on the front and the side.
- Additional Space on the front side by 1/2 of
h1
- Additional Space on the inlet side by 1/2 of
h2
- h1 = A(Actual height) - 1500 (59 inch)
- h2 = B(Actual height) - 500 (19-11/16’’)
7
ENGLISH
During the installation of the unit, consider service, inlet, and outlet
acquire the minimum space as shown in the figures below.
Seasonal wind and cautions in winter
• Sufficient measures are required in a snow areas or severe cold
areas in winter so that product can be operated well.
• Get ready for seasonal wind or snow in winter even in other areas.
• Install a suction and discharge duct not to let in snow or rain.
• Install the outdoor unit in such a way that it should not come in
contact with snow directly.
If snow piles up and freezes on the air suction hole, the system may
malfunction. If it is installed at snowy area, attach the hood to the
system.
• Install the outdoor unit at the higher installation console by 50 cm
(19.7 inch) than the average snowfall (annual average snowfall) if it is
installed at the area with much snowfall.
• Where snow accumulated on the upper part of the Outdoor Unit by
more than 10 cm (3.9 inch), always remove snow for operation.
- The height of H frame must be more than 2 times the snowfall
and its width shall not exceed the width of the product. (If width
of the frame is wider than that of the product, snow may
accumulate)
- Don't install the suction hole and discharge hole of the Outdoor
Unit facing the seasonal wind.
• When carrying the suspended, unit pass the ropes under the unit and
use the two suspension points each at the front and rear.
• Always lift the unit with ropes attached at four points so that impact
is not applied to the unit.
• Attach the ropes to the unit at an angle of 40° or less.
Locking points for
transportation ropes
Forklift Carrying Guide
Forklift Carrying Hole
LIFTING METHOD
Individual Installation
INSTALLATION SPACE
Category
Installation Space
Case 1
(10 mm(13/32 inch)Side
Space49 mm(13/14 inch))
Case 2
(Side Space
49 mm(13/14 inch))
4 sides
are
walls
A10 (13/32)
B300 (11-13/16)
C10 (13/32)
D500 (19-11/16)
A50 (1-31/32)
B100 (3-15/16)
C50 (1-31/32)
D500(19-11/16)
A10 (13/32)
B300 (11-13/16)
C10 (13/32)
D500 (19-11/16)
E20 (25/32)
A50 (1-31/32)
B100 (3-15/16)
C50 (1-31/32)
D500 (19-11/16)
E100 (3-15/16)
A10 (13/32)
B500 (19-11/16)
C10 (13/32)
D500 (19-11/16)
E20 (25/32)
F900 (35-7/16)
A50 (1-31/32)
B100 (3-15/16)
C50 (1-31/32)
D500 (19-11/16)
E100 (3-15/16)
F500 (19-11/16)
A10 (13/32)
B300 (11-13/16)
C10 (13/32)
D300 (11-13/16)
E20 (25/32)
F500 (19-11/16)
A50 (1-31/32)
B100 (3-15/16)
C50 (1-31/32)
D100 (3-15/16)
E100 (3-15/16)
F500 (19-11/16)
Rear
to
Rear
A10 (13/32)
B500 (19-11/16)
C10 (13/32)
D500 (19-11/16)
F900 (35-7/16)
A50 (1-31/32)
B500 (19-11/16)
C50 (1-31/32)
D500 (19-11/16)
F600 (23-5/8)
A10 (13/32)
B500 (19-11/16)
C10 (13/32)
D500 (19-11/16)
E20 (25/32)
F1200 (47-1/4)
A50 (1-31/32)
B500 (19-11/16)
C50 (1-31/32)
D500 (19-11/16)
E100 (3-15/16)
F900 (35-7/16)
A10 (13/32)
B500 (19-11/16)
C10 (13/32)
D500 (19-11/16)
E20 (25/32)
F1800 (70-7/8)
A50 (1-31/32)
B500 (19-11/16)
C50 (1-31/32)
D500 (19-11/16)
E100 (3-15/16)
F1200 (47-1/4)
Only 2
sides
are
walls
A10 (13/32)
B300 (11-13/16)
A10 (13/32)
B300 (11-13/16)
E20 (25/32)
DF
E
G
500
(19-11/16)
DHHF
E
G
500
(19-11/16)
DHF
E
I
G
500
(19-11/16)
DHF
E
I
G
500
(19-11/16)
DF
E
I
G
500
(19-11/16)
DHF
E
I
G
500
(19-11/16)
DHHF
E
I
G
500
(19-11/16)
D
E
500
(19-11/16)
DHH
E
500
(19-11/16)
Front
Front
Front Front
Front Front
Front
Front
Front
Front Front
Front Front
Front Front Front
Front
Front
Front
Front Front
No limit for the
height of wall
No limit for the height of wall
Front
Be very careful while carrying the product.
• Do not have only one person carry product if it is more than
20 kg (44 lbs).
• PP bands are used to pack some products. Do not use them as
a mean for transportation because they are dangerous.
• Do not touch heat exchanger fins with your bare hands.
Otherwise you may get a cut in your hands.
• Tear plastic packaging bag and scrap it so that children cannot
play with it. Otherwise plastic packaging bag may suffocate
children to death.
• When carrying in Outdoor Unit, be sure to support it at four
points. Carrying in and lifting with 3-point
support may make Outdoor Unit unstable, resulting in a fall.
• Use 2 belts of at least 8 m (26.2 ft) long.
• Place extra cloth or boards in the locations where the casing
comes in contact with the sling to prevent damage.
Hoist the unit making sure it is being lifted at its center of gravity.
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:22 Page 7
background
8
ENGLISH
• Install at places where it can endure the weight and vibration/noise
of the outdoor unit.
• The outdoor unit support blocks at the bottom shall have width of at
least 100 mm (3-15/16 inch) under the Unit’s legs before being fixed.
• The outdoor unit support blocks should have minimum height of 200
mm (7-7/8 inch).
• Anchor bolts must be inserted at least 75 mm (2-15/16 inch).
At least 100 mm
(3-15/16 inch)
At least 100 mm
(3-15/16 inch)
At least 100 mm
(3-15/16 inch)
At least 100 mm
(3-15/16 inch)
At least 100 mm
(3-15/16 inch)
At least 100 mm
(3-15/16 inch)
Outdoor units
should not be
supported only by
the corner supports.
Center of the Unit
Center of the Unit
Chassis A [mm (inch)] B [mm (inch)]
UXA 930 (36-5/8) 748 (29-9/20)
UXB 1 240 (47-1/4) 1 040 (40-15/16)
• Fix the unit tightly with bolts as shown below so that unit will not fall
down due to earthquake or gust.
• Use the H-beam support as a base support
• Noise and vibration may occur from the floor or wall since vibration is
transferred through the installation part depending on installation
status. Thus, use anti-vibration materials (cushion pad) fully (The base
pad shall be more than 200 mm (7-7/8 inch)).
At least
200(7-7/8)
760 (29-29/32)
731 (28-25/32)
65
(2-9/16)
65
(2-9/16)
Unit : mm (inch)
At least
65 (2-9/16)
At least
65 (2-9/16)
Unit : mm (inch)
200(7-7/8)
75(2-15/16)
75(2-15/16)
200(7-7/8)
100(3-15/16)
The corner part must be fixed firmly. Otherwise, the support for the
installation may be bent.
Get and use M10 Anchor bolt.
Put Cushion Pad between the outdoor unit and ground support for
the vibration protection in wide area.
Space for pipes and wiring (Pipes and wirings for bottom side)
H-beam support
Concrete support
WARNING
• Install where it can sufficiently support the weight of the
outdoor unit.
If the support strength is not enough, the outdoor unit may drop
and hurt people.
• Install where the outdoor unit may not fall in strong wind or
earthquake.
If there is a fault in the supporting conditions, the outdoor unit
may fall and hurt people.
• Please take extra cautions on the supporting strength of the
ground, water outlet treatment(treatment of the water flowing
out of the outdoor unit in operation), and the passages of the
pipe and wiring, when making the ground support.
• Do not use tube or pipe for water outlet in the Base panel. Use
drainage instead for water outlet. The tube or pipe may freeze
and the water may not be drained.
!
Main cause of gas leakage is defect in flaring work. Carry out correct
flaring work in the following procedure.
Cut the pipes and the cable
- Use the accessory piping kit or the pipes purchased locally.
- Measure the distance between the indoor and the outdoor unit.
- Cut the pipes a little longer than measured distance.
- Cut the cable 1.5 m (4.92 ft) longer than the pipe length.
Preparation of Piping
Copper
tube
90°
Slanted Uneven Rough
Foundation for Installation
The location of the Anchor bolts
INSTALLATION
• Be sure to remove the Pallet(Wood Support) of the bottom side
of the outdoor unit Base panel before fixing the bolt. It may
cause the unstable state of the outdoor settlement, and may
cause freezing of the heat exchanger resulting in abnormal
operations.
• Be sure to remove the Pallet(Wood Support) of the bottom side
of the outdoor unit before welding. Not removing Pallet(Wood
Support) causes hazard of fire during welding.
CAUTION
!
Pallet(Wood Support)
- Remove before Installation
1,MFL68980308,영영 2018. 11. 13. 영영 3:22 Page 8
background
9
ENGLISH
Flaring work
- Carry out flaring work using flaring tool as shown below.
Firmly hold copper tube in a bar(or die) as indicated dimension in the
table above.
Check
- Compare the flared work with figure below.
- If flare is noted to be defective, cut off the flared section and do
flaring work again.
Burrs removal
- Completely remove all burrs from the cut cross section of pipe/tube.
- Put the end of the copper tube/pipe to downward direction as you
remove burrs in order to avoid to let burrs drop in the tubing.
Bar
Copper pipe
"A"
<Wing nut type> <Clutch type>
Inclined
Inside is shining without scratches.
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Flare shape and flare nut tightening torque
Opening shutoff valve
Precautions when connecting pipes
- See the following table for flare part machining dimensions.
- When connecting the flare nuts, apply refrigerant oil to the inside and
outside of the flares and turn them three or four times at first. (Use
ester oil or ether oil.)
-
See the following table for tightening torque.(Applying too much torque may
cause the flares to crack.)
- After all the piping has been connected, use nitrogen to perform a
gas leak check.
1 Remove the cap and turn the valve counter clockwise with the
hexagon wrench.
2 Turn it until the shaft stops.
Do not apply excessive force to the shutoff valve. Doing so may
break the valve body, as the valve is not a backseat type. Always
use the special tool.
3 Make sure to tighten the cap securely.
Pipe size
[mm (inch)]
Tightening Torque
N
.
m (lbs
.
ft)
A [mm (inch)] Flare shape
Ø 9.52 (3/8) 38±4 (28±3.0) 12.8 (0.5)~13.2 (0.52)
90°
±2
4
±
2
A
R=0.4~0.8
Ø 12.7 (1/2) 55±6 (41±4.4) 16.2 (0.64)~16.6 (0.65)
Ø 15.88 (5/8) 75±7 (55±5.2) 19.3 (0.76)~19.7(0.78)
Insulation of shutoff valve
1 Use the heat insulation material for the refrigerant piping which has
an excellent heat-resistance (over 120 °C [248 °F]).
2 Precautions in high humidity circumstance:
This air conditioner has been tested according to the "ISO
Conditions with Mist" and confirmed that there is not any default.
However, if it is operated for a long time in high humid atmosphere
(dew point temperature: More than 23 °C [73.4 °F]), water drops
are liable to fall. In this case, add heat insulation material according
to the following procedure:
- Heat insulation material to be prepared:
EPDM (Ethylene Propylene Diene Methylene)-over 120 °C
[248 °F] the heat-resistance temperature.
- Add the insulation over 10 mm [0.39 inch] thickness at high
humidity environment.
Indoor unit
Thermal insulator
(accessory)
Fastening band
(accessory)
Refrigerant piping
Closing shutoff valve
1 Remove the cap and turn the valve clockwise with the hexagon
wrench.
2 Securely tighten the valve until the shaft contacts the main body seal.
3 Make sure to tighten the cap securely.
* For the tightening torque, refer to the table on the below.
Tightening torque
Shut
off
valve
size
(mm
(inch))
Tightening torque N
.
m (lbs
.
ft) (Turn clockwise to close)
Shaft
(valve body)
Cap
(Valve lid)
Service
port
Flare nut
Gas line
piping
attached
to unit
Closed Opened
Hexagonal
wrench
Ø 6.35
(1/4)
6.0±0.6
(4.4±0.4)
5.0±0.0
(3.7±0.4)
4 mm
(0.16 inch)
17.6±2.0
(13.0±1.5)
12.7±2
(9.4±1.5)
16±2
(12±1.5)
-
Ø 9.52
(3/8)
38±4
(28±3.0)
Ø 12.7
(1/2)
10.0±1.0
(7.4±0.7)
20.0±2.0
(14.8±1.5)
55±6
(41±4.4)
Ø 15.88
(5/8)
12.0±1.2
(8.9±0.9)
5 mm
(0.24 inch)
25.0±2.5
(18.4±1.8)
75±7
(55±5.1)
Ø 19.05
(3/4)
14.0±1.4
(10.3±1.0)
110±10
(81.1±7.4)
Ø 22.2
(7/8)
30.0±3.0
(22.1±2.2)
8 mm
(0.31 inch)
-
Ø 25.4
(1)
25±3
(18.5±2.2)
Pipe diameter
Inch (mm)
A inch (mm)
Wing nut type Clutch type
Ø 1/4 (Ø 6.35)
0.04~0.07 (1.1~1.8) 0~0.02 (0~0.5)
Ø 3/8 (Ø 9.52)
Ø 1/2 (Ø 12.7)
Ø 5/8 (Ø 15.88)
• Always use a charge hose for service port connection.
After tightening the cap, check that no refrigerant leaks are present
.
• When loosening a flare nut, always use two wrenches in
combination, When connecting the piping,
always use a spanner and torque wrench
in combination to tighten the flare nut.
• When connecting a flare nut, coat the
flare(inner and outer faces) with oil for
R410A(PVE) and hand tighten the nut
3 to 4 turns as the initial tightening.
CAUTION
!
Union
1,MFL68980308,영영 2018. 11. 13. 영영 3:22 Page 9
background
10
ENGLISH
Refrigerant piping on three principles
Drying Cleanliness Airtight
Should be no
moisture inside
No dust inside.
There is no refrigerant
leakage
Items
Moisture
Dust
Leakage
Cause failure
- Significant
hydrolysis of
refrigerant oil
- Degradation of
refrigerant oil
- Poor insula’tion of
the compressor
- Do not cold and
warm
- Clogging of EEV,
Capillary
- Degradation of
refrigerant oil
- Poor insulation of
the compressor
- Do not cold and
warm
- Clogging of EEV,
Capillary
- Gas shortages
- Degradation of
refrigerant oil
- Poor insulation of
the compressor
- Do not cold and
warm
Countermeasure
- No moisture in the
pipe
- Until the
connection is
completed, the
plumbing pipe
entrance should be
strictly controlled.
- Stop plumbing at
rainy day.
- Pipe entrance
should be taken
side or bottom.
- When removal burr
after cutting pipe,
pipe entrance
should be taken
down.
- Pipe entrance
should be fitted
cap when pass
through the walls.
- No dust in the
pipe.
- Until the
connection is
completed, the
plumbing pipe
entrance should be
strictly controlled.
- Pipe entrance
should be taken
side or bottom.
- When removal burr
after cutting pipe,
pipe entrance
should be taken
down.
- Pipe entrance
should be fitted
cap when pass
through the walls.
- Airtightness test
should be.
- Brazing operations
to comply with
standards.
- Flare to comply
with standards.
- Flange connections
to comply with
standards.
Nitrogen substitution method
Welding, as when heating without nitrogen substitution a large
amount of the oxide film is formed on the internal piping.
The oxide film is a caused by clogging EEV, Capillary, oil hole of
accumulator and suction hole of oil pump in compressor.
It prevents normal operation of the compressor.
In order to avoid this problem, Welding should be done after replacing
air by nitrogen gas.
When welding plumbing pipe, the work is required.
Regulator
Nitrogen gas
Pressure 0.02 MPa
(2.9 psi) less
Auxiliary valve
Taping
(Should not
contain air)
Welding Point
Note) should not block the outlet side.
When the internal pressure in pipe is abo
ve the atmospheric pressure, pinhole is
occurred and it is a leakage cause.
Oxide scale
Nitrogen
Plumbing materials and storage methods
Pipe must be able to obtain the specified thickness and should be
used with low impurities.
Also when handling storage, pipe must be careful to prevent a
fracture, deformity and wound.
Should not be mixed with contaminations such as dust, moisture.
• Always use the nitrogen.(not use oxygen, carbon dioxide, and a
Chevron gas): Please use the following nitrogen pressure 0.02 MPa
(2.9 psi) Oxygen - Promotes oxidative degradation of refrigerant oil.
Because it is flammable, it is strictly prohibited to use Carbon
dioxide - Degrade the drying characteristics of gas Chevron Gas -
Toxic gas occurs when exposed to direct flame.
Always use a pressure reducing valve.
Please do not use commercially available antioxidant.
The residual material seems to be the oxide scale is observed. In
fact, due to the organic acids generated by oxidation of the
alcohol contained in the anti-oxidants, ants nest corrosion
occurs. (causes of organic acid alcohol + copper + water +
temperature)
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:22 Page 10
background
11
ENGLISH
Service Port
Low Pressure Gas pipe
Liquid pipe
High Pressure Gas pipe
WARNING
• Always careful not to leak the refrigerant during welding.
• The refrigerant generates poisonous gas harmful to human body
if combusted.
• Do not perform welding in a closed space.
• Be sure to close the cap of the service port to prevent gas
leakage after the work.
!
For Heat Recovery System Installation
ABC
IDU side connection pipe
ODU to ODU connection pipe (1st branch)
ODU to ODU connection pipe (2nd branch)
2, 3 Outdoor Units
(Master)
AB
(Slave1)
C
(Slave2)
For more information, refer accessory installation manual.
Y branch
A
B
To outdoor unit
To branch piping or indoor unit
A
B
Viewed from point A
in direction of arrow
Within +/- 10
Facing
upwards
Facing
downwards
Connection of Outdoor units
When installing ODU series, refer below picture.
Precautions on Pipe connection / Valve operation
Pipe connection is done by connecting from the end of the pipe to the
branching pipes, and the refrigerant pipe coming out of the outdoor
unit is divided at the end to connect to each indoor unit. Flare
connection for the indoor unit, and welding connection for the outdoor
pipe and the branching parts. (Including HR Unit)
- Use hexagonal wrench to open/close the valve.
REFRIGERANT PIPING INSTALLATION
Unit : mm(inch)
Outdoor Units Model Pipe
2 Unit
ARCNB21
Low Pressure Gas Pipe
I.D.22.2
(7/8)
O.D.28.58
(1-1/8)
416(16-3/8)
I.D.28.58(1-1/8)
I.D.31.8(1-1/4)
I.D.41.3
(1-5/8)
130(5-1/8)
I.D.22.2
(7/8)
O.D.28.58
(1-1/8)
I.D.34.9
(1-3/8)
I.D.28.58(1-1/8)
I.D.28.58
(1-1/8)
111
(4-3/8)
I.D.38.1
(1-1/2)
O.D.34.9
(1-3/8)
I.D.34.9(1-3/8)
I.D.22.2(7/8)
408(16-1/16)
I.D.34.9
(1-3/8)
Liquid Pipe
I.D.19.05(3/4)
I.D.15.88(5/8)
I.D.19.05(3/4)
I.D.12.7
(1/2)
I.D.9.52
(3/8)
83
(3-9/32)
I.D.22.2
(7/8)
70(2-3/4)
O.D.19.05
(3/4)
I.D.12.7(1/2) I.D.15.88(5/8)
O.D.12.7(1/2)
I.D.9.52(3/8)
O.D.15.88(5/8)
I.D.19.05(3/4)
I.D.15.88(5/8)
O.D.15.88(5/8)
331(13-1/32)
314(12-3/8)
High Pressure Gas Pipe
I.D.15.88(5/8)O.D.22.2
(7/8)
I.D.19.05
(3/4)
I.D.28.58(1-1/8)
I.D.31.8
(1-1/4)
O.D.28.58
(1-1/8)
1.D.22.2(7/8)
I.D.19.05(3/4)
I.D.28.58(1-1/8)
111
(4-3/8)
I.D.34.9
(1-3/8)
I.D.28.58
(1-1/8)
I.D.22.2(7/8)
416(16-3/8)
408(16-1/16)
3 Unit
ARCNB31
Low Pressure Gas Pipe
O.D.34.9
(1-3/8)
I.D.28.58
(1-1/8)
I.D.41.3
(1-5/8)
O.D.34.9
(1-3/8)
I.D.41.3(1-5/8)
I.D.53.98
(2-1/8)
I.D.44.5
(1-3/4)
O.D.41.3
(1-5/8)
I.D.22.2
(7/8)
I.D.34.9(1-3/8)O.D.28.58
(1-1/8)
I.D.28.58(1-1/8)
I.D.34.9
(1-3/8)
341(13-7/16)
125
(4-29/32)
111
(4-3/8)
298(11-23/32)
Liquid Pipe
O.D.19.05(3/4)
I.D.22.2(7/8)
O.D.19.05
(3/4)
I.D.22.2
(7/8)
I.D.28.58
(1-1/8)
I.D.15.88
(5/8)
I.D.19.05
(3/4)
83
(3-9/32)
I.D.12.7(1/2)
O.D.15.88(5/8) I.D.19.05(3/4)
I.D.19.05(3/4)
I.D.12.7(1/2)
O.D.19.05
(3/4)
I.D.22.2(7/8)
I.D.15.88(5/8)
334(13.5/32)
281(11-1/16)
High Pressure Gas Pipe
I.D.22.2
(7/8)
I.D.28.58(1-1/8)
I.D.31.8(1-1/4)
I.D.41.3
(1-5/8)
I.D.53.98
(2-1/8)
I.D.44.5
(1-3/4)
O.D.41.3
(1-5/8)
130(5-1/8)
I.D.38.1
(1-1/2)
O.D.34.9
(1-3/8)
I.D.34.9(1-3/8)
I.D.28.58(1-1/8)
111
(4-3/8)
I.D.34.9
(1-3/8)
O.D.28.58
(1-1/8)
I.D.22.2
(7/8)
I.D.28.58
(1-1/8)
I.D.22.2(7/8)
O.D.28.58
(1-1/8)
416(16-3/8)
408(16-1/16)
I.D.34.9
(1-3/8)
Please block the pipe knock outs of the front and side panels after
installing the pipes.
(Animals or foreign objects may be brought in to damage wires.)
CAUTION
!
Y-branches between the outside units must be installed horizontally.
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:22 Page 11
background
12
ENGLISH
Gas pipe
Gas pipe
Liquid pipe
Liquid pipe
HR Unit
High
Pressure
Gas Pipe
Liquid pipe
Low Pressure
Gas Pipe
1
2
3
4
Pipe
connection
from left
side
Pipe
connection
from right
side
Parallel
pipe
connection
1
st
HR Unit 2
nd
HR Unit
1 2 3 4
B8
(96k) (28k)
BG
1 2 3 4
B8
(76k)(21k)
BH
Gas pipe Ø 15.88 (5/8)
Liquid pipe Ø 9.52 (3/8)
Brazing Type
1
2
3
4
Remove caps on
The brazing part.
Liquid pipe
Low pressure gas pipe
High pressure gas pipe
WARNING
Before brazing work, remove gas in the HR Unit by cutting the
three pipes in the small circles on the figure.
If not, it may cause injuries.
Remove the caps before connecting pipes.
!
Joint Method of HR Unit
(Big Duct : ARNU763B8-, ARNU963B8-)
Joint Method is required when the big duct chassis is installed. In Joint
Method, two neighboring outlets of one HR unit are linked by Y branch
pipe and connected to one indoor unit.
2 Series
Type of HR Unit
Select an HR unit according to the number of the indoor units to be
installed. HR units are classified into 3 types by the number of
connectable indoor units.
Ex) Installation of 6 indoor units
Consists of HR unit for 4 branches and HR unit for 2 branches.
2 Series
3 Series
Installation of Outdoor Unit, HR Unit, Indoor Unit
Refrigerant Pipe
3 pipes are connected to the HR unit from the outdoor unit, classified
into liquid pipe, low pressure gas pipe and high pressure gas pipe
depending on status of refrigerant passing through the pipe.
You must connect 3 pipes from outdoor unit to HR unit.
For connection between indoor unit and HR unit, you must connect
both liquid pipe and gas pipe from the HR unit to the indoor unit. In this
case, connect them to the indoor unit starting from No.1 connection
port of the HR unit (the port number is displayed on ports of the HR
unit). Use auxiliary flare as annexed parts in connection to the indoor
unit.
Installation procedure for HR unit
1 Using an insert-hole-in- anchor, hang the hanging bolt.
2 Install a hexagon nut and a flat washer (locally-procured)to the
hanging bolt as shown in the figure in the bottom, and fit the main
unit to hang on the hanger metal.
3
After checking with a level that the unit is level, tighten the hexagon nut.
* The tilt of the unit should be within ± 5° in front/back and
left/right.
4 This unit should be installed suspended from ceiling and side A
should always be facing up.
5 Insulate not used pipes completely as shown in the figure.
Six-sided Nut
(M10 or M8)
Hanger metal
Hanger metal
Hanger metal
Flat washer
Flat washer
Flat washer
(M10)
Hanging bolt
Hanging bolt
Hanging bolt
(M10 or M8)
A
Insulation
PRHR022A
(2 branches)
PRHR032A
(3 branches)
PRHR042A
(4 branches)
PRHR023A
(2 branches)
PRHR033A
(3 branches)
PRHR063A
(6 branches)
PRHR083A
(8 branches)
PRHR043A
(4 branches)
Whenever connecting the indoor units with the HR unit, install the
indoor units in numerical order from No.1.
Ex) In case of installing 3 indoor units : No. 1, 2, 3 (O), No. 1, 2, 4 (X),
No.1, 3, 4 (X), No.2, 3, 4 (X).
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:22 Page 12
background
13
ENGLISH
HR unit
PRHR022A
PRHR023A
PRHR032A
PRHR033A
PRHR042A
PRHR043A
PRHR063A
PRHR083A
Low pressure
gas pipe
Ø 22.2 (7/8) Ø 28.58 (1-1/8) Ø 28.58 (1-1/8)
High pressure
gas pipe
Ø 19.05 (3/4) Ø 22.2 (7/8) Ø 22.2 (7/8)
Liquid pipe Ø 9.52 (3/8) Ø 12.7 (1/2) Ø 15.88 (5/8)
Installation of Zoning Control
Some indoor unit can be connected to one port of HR unit.
HR unit HR unit
sealing
Changeover under control Auto changeover Changeover under control
Zoning control group 1 Zoning control group 2
(Max. 8 Indoor Units)
(Max. 8 Indoor Units)
1
st
2 HR Unit
nd
HR Unit
4 3 2 1
BG
(38k) (92k)
B8
(48k)
BH
(72k)
B8
4 3 2 1
3 Series
NOTE
!
• A connection to un-neighboring pipes is forbidden.
Do not link more than 2 outlets.
• The B8 unit, which has the largest capacity, must be connected
to the 1st and 2nd outlets of the 1st HR unit. Other B8 units can
be connected to any two neighboring outlets within one HR unit.
1
st
HR Unit 2
nd
HR Unit
2
nd
HR Unit 1
st
HR Unit
4 3 2 1
B8
4 3 2 1
4 3 2 1
B8
4 3 2 1
2
nd
HR Unit 1
st
HR Unit
4 3 2 1
B8
(92k) (38k)
BG
4 3 2 1
B8
(72k)(34k)
BH
WARNING
• A branch pipe of HR unit allows up to 14.1 kW (48 kBtu/h) based
on cooling capacity of the indoor unit.
(up to 14.1 kW (48 kBtu/h) for max installation)
• The maximum total capacity of indoor units connected to a
PRHR042A HR unit is 56.4 kW (192 kBtu/h).
• The maximum number of indoor units connected to a PRHR042A
unit are 32 indoor units. (The Maximum indoor units per a branch
pipe of HR unit are 8 indoor units)
• There is not operate “Auto-changeover” & “Mode override”
function in the zoning group.
• When there are operating indoor units on cooling(heating) mode,
another indoor units aren’t changed on heating(cooling) mode in
the zoning group.
!
[Reducers for indoor unit and HR unit]
Unit : mm (inch)
Models
High pressure
Gas pipe
Low pressure
Liquid pipe
Indoor unit
reducer
HR unit
reducer
PRHR022A
PRHR023A
OD22.2(7/8)
Ø 19.05(3/4)
Ø 15.88(5/8)
OD15.88(5/8)
Ø 12.7(1/2)
Ø 6.35(1/4)OD9.52(3/8)
Ø 6.35(1/4)OD9.52(3/8)
OD19.05(3/4)
Ø 15.88(5/8)
OD12.7(1/2) Ø 9.52(3/8)
Ø 12.7(1/2)
OD22.2(7/8) Ø 19.05(3/4)
Ø 15.88(5/8)
OD15.88(5/8) Ø 12.7(1/2)
PRHR032A
PRHR042A
PRHR033A
PRHR043A
PRHR063A
PRHR083A
OD19.05(3/4)
Ø 15.88(5/8)
OD28.58(1-1/8)
Ø 22.2(7/8)
Ø 19.05(3/4)
OD15.88(5/8) Ø 12.7(1/2) Ø 9.52(3/8)
OD15.88(5/8)
Ø 12.7(1/2)
1,MFL68980308,영영 2018. 11. 13. 영영 3:22 Page 13
background
14
ENGLISH
Caution
1 Use the following materials for refrigerant piping.
- Material: Seamless phosphorous deoxidized copper pipe
- Wall thickness : Comply with the relevant local and national
regulations for the designed pressure 3.8 MPa
(551 psi). We recommend the following table as
the minimum wall thickness.
Outer diameter
[mm(inch)]
6.35
(1/4)
9.52
(3/8)
12.7
(1/2)
15.88
(5/8)
19.05
(3/4)
22.2
(7/8)
25.4
(1)
28.58
(1-1/8)
31.8
(1-1/4)
34.9
(1-3/8)
38.1
(1-1/2)
41.3
(1-5/8)
44.45
(1-3/4)
53.98
(2-1/8)
Minimum
thickness
[mm(inch)]
0.8
(0.03)
0.8
(0.03)
0.8
(0.03)
0.99
(0.04)
0.99
(0.04)
0.99
(0.04)
0.99
(0.04)
0.99
(0.04)
1.1
(0.04)
1.21
(0.05)
1.35
(0.05)
1.43
(0.06)
1.55
(0.06)
2.1
(0.08)
6 If the diameters of the branch piping of the designated refrigerant
piping differs, use a pipe cutter to cut the connecting section and
then use an adapter for connecting different diameters to connect
the piping.
7 Always observe the restrictions on the refrigerant piping (such as
rated length, difference in height, and piping diameter).
Failure to do so can result in equipment failure or a decline in
heating/cooling performance.
8 A second branch cannot be made after a header.
(These are shown by .)
9 The Multi V will stop due to an abnormality like excessive or
insufficient refrigerant. At such a time, always properly charge the
unit. When servicing, always check the notes concerning both the
piping length and the amount of additional refrigerant.
10 Never perform a pump down. This will not only damage the
compressor but also deteriorate the performance.
11 Never use refrigerant to perform an air purge. Always evacuate air
by using a vacuum pump.
To Outdoor Unit
Sealed Piping
A
A
B
12 Always insulate the piping properly. Insufficient insulation will
result in a decline in heating/cooling performance, drip of
condensate and other such problems.
13 When connecting the refrigerant piping, make sure the service
valves of the Outdoor Unit is completely closed (the factory
setting) and do not operate it until the refrigerant piping for the
Outdoor and Indoor Units has been connected, a refrigerant
leakage test has been performed and the evacuation process has
been completed.
14 Always use a non-oxidizing brazing material for brazing the parts
and do not use flux. If not, oxidized film can cause clogging or
damage to the compressor unit and flux can harm the copper
piping or refrigerant oil.
A
B
WARNING
When installing and moving the air conditioner to another site, be
sure to make recharge refrigerant after perfect evacuation.
• If a different refrigerant or air is mixed with the original
refrigerant, the refrigerant cycle may malfunction and the unit
may be damaged.
• After selecting diameter of the refrigerant pipe to suit total
capacity of the indoor unit connected after branching, use an
appropriate branch pipe set according to the pipe diameter of the
indoor unit and the installation pipe drawing.
!
2 Commercially available piping often contains dust and other
materials. Always blow it clean with a dry inert gas.
3 Use care to prevent dust, water or other contaminants from
entering the piping during installation.
4 Reduce the number of bending portions as much as possible, and
make bending radius as big as possible.
5 Always use the branch piping set shown below, which are sold
separately.
Y branch
Header
4 branches 7 branches 10 branches
ARBLB01621, ARBLB03321,
ARBLB07121, ARBLB14521,
ARBLB23220
ARBL054 ARBL057 ARBL1010
ARBL104 ARBL107 ARBL2010
Service Port
Not used(keep closed)
Liquid pipe
Gas pipe
WARNING
• Always careful not to leak the refrigerant during welding.
• The refrigerant generates poisonous gas harmful to human body
if combusted.
• Do not perform welding in a closed space.
• Be sure to close the cap of the service port to prevent gas
leakage after the work.
!
For Heat Pump System Installation
Precautions on Pipe connection / Valve operation
Pipe connection is done by connecting from the end of the pipe to the
branching pipes, and the refrigerant pipe coming out of the outdoor
unit is divided at the end to connect to each indoor unit. Flare
connection for the indoor unit, and welding connection for the outdoor
pipe and the branching parts.
- Use hexagonal wrench to open/close the valve.
h In case of the heat pump system installation, be sure to maintain to
close no use pipe like below picture.
1,MFL68980308,영영 2018. 11. 13. 영영 3:22 Page 14
background
15
ENGLISH
ABC
IDU side connection pipe
ODU to ODU connection pipe (1st branch)
ODU to ODU connection pipe (2nd branch)
(Master)
AB
(Slave1)
C
(Slave2)
Caution
1 Use the following materials for refrigerant piping.
- Material: Seamless phosphorous deoxidized copper pipe
- Wall thickness : Comply with the relevant local and national
regulations for the designed pressure 3.8 MPa
(551 psi). We recommend the following table as
the minimum wall thickness.
Outer diameter
[mm(inch)]
6.35
(1/4)
9.52
(3/8)
12.7
(1/2)
15.88
(5/8)
19.05
(3/4)
22.2
(7/8)
25.4
(1)
28.58
(1-1/8)
31.8
(1-1/4)
34.9
(1-3/8)
38.1
(1-1/2)
41.3
(1-5/8)
44.45
(1-3/4)
53.98
(2-1/8)
Minimum
thickness
[mm(inch)]
0.8
(0.03)
0.8
(0.03)
0.8
(0.03)
0.99
(0.04)
0.99
(0.04)
0.99
(0.04)
0.99
(0.04)
0.99
(0.04)
1.1
(0.04)
1.21
(0.05)
1.35
(0.05)
1.43
(0.06)
1.55
(0.06)
2.1
(0.08)
2 Commercially available piping often contains dust and other
materials. Always blow it clean with a dry inert gas.
3 Use care to prevent dust, water or other contaminants from
entering the piping during installation.
4 Reduce the number of bending portions as much as possible, and
make bending radius as big as possible.
5 Always use the branch piping set shown below, which are sold
separately.
2, 3 Outdoor Units
For more information, refer accessory installation manual.
Y branch
A
B
To outdoor unit
To branch piping or indoor unit
A
B
Facing
upwards
Facing
downwards
Viewed from point A
in direction of arrow
Within +/- 10
Outdoor Units Model Pipe
2 Unit
ARCNN21
Liquid Pipe
O.D.15.88(5/8)
I.D.15.88(5/8)
I.D.19.05(3/4)
I.D.22.2(7/8)
O.D.15.88(5/8) I.D.19.05(3/4)
I.D.12.7(1/2) I.D.15.88(5/8)
O.D.12.7(1/2) I.D.9.52(3/8)
I.D.12.7
(1/2)
I.D.9.52
(3/8)
83
(3-9/32)
O.D.19.05(3/4)
70(2-3/4)
I.D.15.88(5/8)
331(13-1/32)
314(12-3/8)
I.D.19.05(3/4)
Gas Pipe
I.D.22.2
(7/8)
I.D.28.58(1-1/8)
I.D.31.8(1-1/4)
I.D.28.58
(1-1/8)
I.D.34.9(1-3/8)
I.D.41.3
(1-5/8)
130(5-1/8)
I.D.38.1
(1-1/2)
I.D.22.2
(7/8)
O.D.28.58
(1-1/8)
I.D.34.9(1-3/8)
111
(4-3/8)
O.D.34.9(1-3/8)
I.D.28.58(1-1/8)
I.D.22.2(7/8)
O.D.28.58
(1-1/8)
416(16-3/8)
408(16-1/16)
I.D.34.9
(1-3/8)
3 Unit
ARCNN31
Liquid Pipe
O.D.19.05(3/4)
I.D.15.88(5/8)
I.D.22.2
(7/8)
O.D.19.05(3/4)
I.D.22.2(7/8)
I.D.15.88(5/8) I.D.12.7(1/2)
I.D.28.58(1-1/8)
O.D.15.88(5/8) I.D.19.05(3/4)
I.D.19.05
(3/4)
I.D.19.05
(3/4)
334(13-5/32)
281(11-1/16)
I.D.12.7(1/2)
O.D.19.05(3/4) I.D.22.2(7/8)
83
(3-9/32)
Gas Pipe
O.D.34.9(1-3/8) I.D.28.58(1-1/8)
I.D.41.3(1-5/8) O.D.34.9(1-3/8)
I.D.41.3(1-5/8)
I.D.53.98(2-1/8) O.D.41.3(1-5/8)
I.D.22.2(7/8)
O.D.28.58(1-1/8)
I.D.34.9(1-3/8)
I.D.28.58(1-1/8)
I.D.34.9
(1-3/8)
111
(4-3/8)
I.D.44.5(1-3/4)
341(13-7/16)
125(4-29/32)
298(11-23/32)
Y branch
Header
4 branches 7 branches 10 branches
ARBLN01621, ARBLN03321,
ARBLN07121, ARBLN14521,
ARBLN23220
ARBL054 ARBL057 ARBL1010
ARBL104 ARBL107 ARBL2010
6 If the diameters of the branch piping of the designated refrigerant
piping differs, use a pipe cutter to cut the connecting section and
then use an adapter for connecting different diameters to connect
the piping.
7 Always observe the restrictions on the refrigerant piping (such as
rated length, difference in height, and piping diameter).
Failure to do so can result in equipment failure or a decline in
heating/cooling performance.
8 A second branch cannot be made after a header. (These are shown
by .)
Connection of Outdoor units
When installing ODU series, refer below picture.
Please block the pipe knock outs of the front and side panels after
installing the pipes.
(Animals or foreign objects may be brought in to damage wires.)
CAUTION
!
Y-branches between the outside units must be installed
horizontally.
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 15
background
16
ENGLISH
To Outdoor Unit
Sealed Piping
A
A
B
9 The Multi V will stop due to an abnormality like excessive or
insufficient refrigerant. At such a time, always properly charge the
unit. When servicing, always check the notes concerning both the
piping length and the amount of additional refrigerant.
10 Never perform a pump down. This will not only damage the
compressor but also deteriorate the performance.
11 Never use refrigerant to perform an air purge. Always evacuate air
by using a vacuum pump.
12 Always insulate the piping properly. Insufficient insulation will
result in a decline in heating/cooling performance, drip of
condensate and other such problems.
13 When connecting the refrigerant piping, make sure the service
valves of the Outdoor Unit is completely closed (the factory
setting) and do not operate it until the refrigerant piping for the
Outdoor and Indoor Units has been connected, a refrigerant
leakage test has been performed and the evacuation process has
been completed.
14 Always use a non-oxidizing brazing material for brazing the parts
and do not use flux. If not, oxidized film can cause clogging or
damage to the compressor unit and flux can harm the copper
piping or refrigerant oil.
A
B
WARNING
When installing and moving the air conditioner to another site, be
sure to make recharge refrigerant after perfect evacuation.
• If a different refrigerant or air is mixed with the original
refrigerant, the refrigerant cycle may malfunction and the unit
may be damaged.
• After selecting diameter of the refrigerant pipe to suit total
capacity of the indoor unit connected after branching, use an
appropriate branch pipe set according to the pipe diameter of the
indoor unit and the installation pipe drawing.
!
- Pipe connections can be done on the front side or on the side
according to the installation environments.
- Be sure to let 0.2 kgf/cm
2
(2.8 psi) Nitrogen flow in the pipe when
welding.
- If Nitrogen was not flown during welding, many oxidized membranes
may form inside the pipe and disturb the normal operations of valves
and condensers.
Left Side
Pipe Draw
Out
Front Pipe Draw Out
Right
Side Pipe
Draw Out
Refrigerant Pipe
Regulator
Nitrogen
Taping
Valve
Nitrogen
Nitrogen
Direction
Direction
Nitrogen
Direction
Knock Out for
Liquid pipe
Knock Out for low
pressure gas pipe
Knock Out for high
pressure gas pipe
Knock Out for
communication cable
Removal area for pipes
bottom side connections.
Knock Out for
power supply cable
Preparation Work
- Use Knock Outs of Base Pan of the outdoor unit for Left/Right or
Bottom pipe drawing outs.
PIPE CONNECTIONS BETWEEN
INDOOR AND OUTDOOR UNIT
For Heat Recovery System Installation
• Do not give damage to the pipe/base during the Knock Out
work.
• Proceed to pipe work after removing burr after Knock Out work.
Perform sleeve work to prevent damage to the wire when
connecting wires using Knock Outs.
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 16
background
17
ENGLISH
Method of drawing out pipes on the bottom side
- Drawing out common pipe through side panel
Remove leakage prevention cap
• Remove the leakage prevention cap attached to the outdoor unit
service valve before pipe work.
• Proceed the leakage prevention cap removal as follows:
- Verify whether the liquid/gas pipes are locked.
- Extract remaining refrigerant or air inside using the service port.
- Remove the leakage prevention cap
h In case of heat pump installation, please weld with the proper Low
pressure Gas pipe included with product.
Refrigerant piping system
3 Outdoor Units
Example : 12 Indoor Units connected
: Outdoor Unit
: Y branch
: Indoor Unit
: Connection branch pipe between Outdoor units : ARCNB31
: Connection branch pipe between Outdoor units : ARCNB21
: Header
: HR Unit
- Case 1 ("a")
: Maximum height is 30 m (98.4 ft) if you install with Y branch.
- Case 2 ("b")
: Maximum height is 5 m(16 ft) in serial connection of HR units.
A1
H1
D
1
2
D
D
D
3
4
E
F
A
C1
B
C2
C3
*
B1
B2
A2
A3
a
b
c
d
e
g
j
k
x
l
m
n
sealing
f
i
H
h
"a"
"b"
E
H2
H4
G
H3
Master
Slave 1
Slave 2
ODU Capacity
Master ≥ Slave1 ≥ Slave 2
D
5
D
6
D
7
D
8
D
10
D
9
D
11
D
12
Pipe Drawing Out during Single / Series connection
Method of drawing out pipes on the front side
- Proceed with the pipe work as shown in the below figure for front
side pipe drawing out.
Refrigerant pipe diameter from branch to branch (B,C,D)
WARNING
* : Serial connection of HR units : Capacity sum of indoor units
192.4 kBtu/hr
• Refer to the HR unit PCB part for the valve group control setting.
• It is recommended that difference in pipe lengths between an HR
unit and indoor units, for example
difference in length of a, b, c, and d, be minimized. The larger
difference in pipe lengths, the more different performance
between indoor units.
• Piping length from outdoor branch to outdoor unit 10 m (33 ft),
equivalent length : max 13 m (43 ft)
* If the large capacity indoor units (Over 5 HP; using over Ø 15.88
(5/8) / Ø 9.52 (3/8) are installed, it should be used the Valve Group
setting
!
High Pressure Gas pipe
Liquid pipe
Low Pressure Gas pipe
131(5-5/32)
69(2-23/32)
126(4-31/32)
High Pressure
Gas pipe
Liquid pipe
Low Pressure Gas pipe
Service Port
Liquid pipe
Low Pressure
Gas pipe
High Pressure
Gas pipe
Leakage
Prevention Cap
Liquid pipe Low Pressure Gas pipe
High Pressure Gas pipe
Remove Knock Out for the bottom side of Liquid / Gas pipe
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 17
background
18
ENGLISH
- * : Assume equivalent pipe length of Y branch to be 0.5 m (1.64 ft),
that of header to be 1m (3.3 ft), calculation purpose
- It is recommended that indoor unit is installed at lower position than
the header.
- ** : To apply conditional application.
Refrigerant pipe diameter from branch to branch (B,C)
Downward indoor
unit total capacity
[kW(Btu/h)]
Liquid pipe
[mm(inch)]
Gas pipe [mm(inch)]
Low pressure High pressure
5.6(19 100)
Ø 6.35(1/4) Ø 12.7(1/2) Ø 9.52(3/8)
< 16.0(54 600) Ø 9.52(3/8) Ø 15.88(5/8) Ø 12.7(1/2)
< 22.4(76 400) Ø 9.52(3/8) Ø 19.05(3/4) Ø 15.88(5/8)
< 33.6(114 700) Ø 9.52(3/8) Ø 22.2(7/8) Ø 19.05(3/4)
< 50.4(229 000) Ø 12.7(1/2) Ø 28.58(1 1/8) Ø 22.2(7/8)
< 61.6(210 600) Ø 15.88(5/8) Ø 28.58(1 1/8) Ø 22.2(7/8)
< 72.8(210 600) Ø 15.88(5/8) Ø 34.9(1 3/8) Ø 28.58(1 1/8)
< 100.8(344 000) Ø 19.05(3/4) Ø 34.9(1 3/8) Ø 28.58(1 1/8)
< 173.6(592 500) Ø 19.05(3/4) Ø 41.3(1 5/8) Ø 34.9(1 3/8)
Total pipe length = A + B + C1 + C2 + C3 + a + b + c + d
+ e + f + g + i + j + k + l + m + n ≤ 1 000 m (3 280 ft)
L
Longest pipe length * Equivalent pipe length
A+B+C3+D+k 150 m (200 m**) [(492 ft(656 ft**)] A+B+C3+D+k 175 m (225 m**) [(574 ft(738 ft**)]
l
Longest pipe length after 1st branch
B+C3+D+k 40 m(90 m**) [131 ft (295 ft)]
H
Difference in height(Outdoor Unit Indoor Unit)
H 110 m (361 ft)
h
Difference in height (Indoor Unit Indoor Unit)
h 40 m (131 ft)
h1
Difference in height (Outdoor Unit Outdoor Unit)
h1 5 m (16.4 ft)
"a", "b"
Difference in height(HR unit HR unit)
a 15 m (49 ft), b 5 m (16 ft)
WARNING
When the equivalent length between a outdoor and the farthest
indoor unit is 90 m (295 ft) or more, main pipe(A) must be increased
one grade.
!
Refrigerant pipe diameter from outdoor unit to first
branch. (A)
Y branch, Header and HR unit connection pattern
* If available on site, select pipe size according to upper table.
Otherwise it doesn’t need to be increased.
Pattern 1
HR1
48k 48k
1 2
HR2
48k 48k
3 4
B
• Impossible installation : Head branch pipe HR unit
Pattern 2
HR1
1
234567
7k 7k 7k 7k 7k 24k 24k
• Impossible installation : HR unit Head branch
pipe Y and Head branch pipe.
B
A
ODU
Capacity
(HP(ton))
Standard Pipe Diameter
Pipe diameter when pipe length is
90 m (295 ft) or when height differential
(ODUIDU) is > 50 m (164 ft)
Liquid Pipe
mm (inch)
Low
Pressure
Vapor Pipe
[mm(inch)]
High
Pressure
Vapor Pipe
[mm(inch)]
Liquid Pipe
mm (inch)
Low
Pressure
Vapor Pipe
[mm(inch)]
High
Pressure
Vapor Pipe
[mm(inch)]
8(6)
Ø 9.52
(3/8)
Ø 19.05
(3/4)
Ø 15.88
(5/8)
Ø 12.7
(1/2)
Not
increased
Not
increased
10(8)
Ø 9.52
(3/8)
Ø 22.2
(7/8)
Ø 19.05
(3/4)
Ø 12.7
(1/2)
Not
increased
Not
increased
12(10)
Ø 12.7
(1/2)
Ø 28.58
(1-1/8)
Ø 19.05
(3/4)
Ø 15.88
(5/8)
Not
increased
Not
increased
14(12)
Ø 12.7
(1/2)
Ø 28.58
(1-1/8)
Ø 22.2
(7/8)
Ø 15.88
(5/8)
Not
increased
Not
increased
18(14)
Ø 15.88
(5/8)
Ø 28.58
(1-1/8)
Ø 22.2
(7/8)
Ø 19.05
(3/4)
Not
increased
Not
increased
20~22
(16~18)
Ø 15.88
(5/8)
Ø 28.58
(1-1/8)
Ø 28.58
(1-1/8)
Ø 19.05
(3/4)
Not
increased
Not
increased
24(20)
Ø 15.88
(5/8)
Ø 34.9
(1-3/8)
Ø 28.58
(1-1/8)
Ø 19.05
(3/4)
Not
increased
Not
increased
26~34
(22~28)
Ø 19.05
(3/4)
Ø 34.9
(1-3/8)
Ø 28.58
(1-1/8)
Ø 22.2
(7/8)
Not
increased
Not
increased
36~50
(30~42)
Ø 19.05
(3/4)
Ø 41.3
(1-5/8)
Ø 28.58
(1-1/8)
Ø 22.2
(7/8)
Not
increased
Not
increased
(**) Conditional Application (In case of D12 is the farthest in door)
Below condition must be satisfied for 40~90 m (131~295 ft) piping length
after first branch.
1
Diameter of pipes between first branch and the last branch should be
increased by one step, except if the pipe diameter B, C3 is same as
diameter A (main pipe diameter)
Ø 6.35 (1/4), Ø 9.52 (3/8), Ø 12.7 (1/2), Ø 15.88 (5/8), Ø 19.05 (3/4),
Ø 22.2 (7/8), Ø 25.4* (1), Ø 28.58 (1-1/8), Ø 31.8* (1-1/4), Ø 34.9 (1-3/8),
Ø 38.1* (1-1/2)
* : If available on site, it use this size. Otherwise it can’t be increased.
2
While calculating total refrigerant piping length, pipe B, C3 length should
be calculated twice.
A + B x 2 + C3 x 2 + C1 + C2 + a + b + c + d + e + f + g + i + j + k + l
+ m + n 1 000 m (3 281 ft)
3
Length of pipe from each indoor unit to the closest HR unit
(a, b, c, d, e, f, g, i, j, k, l, m, n) 40 m (131 ft)
4
[Length of pipe from outdoor unit to the farthest indoor unit D12
(B+C3+K)
- [Length of pipe from outdoor unit to the closest indoor unit D1 (C1+a)]
40 m (131 ft)
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 18
background
19
ENGLISH
Pattern 3
HR1
48k 48k 48k 48k
1 2 3 4
• The maximum total capacity of indoor
units is 56.4 kW(192 kBtu/h).
Pattern 4
12k 12k 12k 12k
1 2 3 4
• The maximum total capacity of a branch
pipe of HR unit is 14.1 kW(48 kBtu/h).
HR1
B
Pattern 5
HR1
48k 48k
A
1 2
HR2
48k 48k
3 4
HR1
24k 24k 24k
12k 12k
B
Pattern 6
A
A
A
12 345
Pattern 8
A
A
• * : Maximum indoor units per a branch are 8 indoor units
HR1
48k 48k
1 2
HR2
*
B
12k 12k 12k 12k
3 4 5 6
24k
7
24k
8
Pattern 7
HR1
A
48k 48k
1 2
• * : Serial connection of HR units : Capacity sum of indoor units ≤ 56.4 kW (192 kBtu/h)
HR2
48k 48k
3 4
HR3
48k 48k
5 6
*
• Pipe installation from outdoor units to HR units
: 3 pipes(Low pressure Gas pipe, High pressure Gas pipe, Liquid pipe)
• Pipe installation from HR units to indoor units
: 2 pipes(Gas pipe, Liquid pipe)
B
A
1
HR1
Outdoor
Unit
Indoor Unit Y Branch pipe
Low pressure Gas pipe
High pressure Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Head Branch pipe
Indoor
Unit
Keep the 40 m (131 ft) distance from the first branch to the farthest
indoor.
5 m(16 ft)
15 m(49 ft)
1) under 40 m (131 ft)
Keep the sum of indoor capacity under 56.4 kW(192 kBtu/h).
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
1) under 40 m (131 ft)
Y branch
Keep the sum of indoor capacity under 56.4 kW(192 kBtu/h).
For Heat Pump System Installation
Preparation Work
- Use Knock Outs of Base Pan of the outdoor unit for Left/Right or
Bottom pipe drawing outs.
Knock Out for
Liquid pipe
Knock Out for low
pressure gas pipe
Knock Out for high
pressure gas pipe
Knock Out for
communication cable
Removal area for pipes
bottom side connections.
Knock Out for
power supply cable
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 19
background
20
ENGLISH
Piping length from outdoor branch to outdoor unit 10 m(33 ft),
equivalent length : max 13 m(43 ft) (for 14 Ton or more)
Additional Application
To satisfy below condition to make 40 m(131 ft) ~ 90 m(295 ft) of
pipe length after first branch.
• Diameter of pipes between first branch and the last branch
should be increased by one step, except pipe diameter B,C,D is
same as Diameter A
Ø 1/4(6.35 mm) Ø 3/8(9.52 mm) Ø 1/2(12.7 mm)
Ø 5/8(15.88 mm) Ø 3/4(19.05 mm) Ø 7/8(22.2 mm)
Ø 1(25.4)*, Ø 1-1/8(28.58 mm) Ø 1-1/4(31.8 mm)*,
Ø 1-3/8(34.9 mm) Ø 1-1/2(38.1 mm)* Ø 1-5/8(41.3 mm)
* : It is not necessary to size up.
h If the step up size is not available, you can not select the next
higher size available.
While calculating whole refrigerant pipe length, pipe B,C,D length
should be calculated twice.
A+Bx2+Cx2+Dx2+a+b+c+d+e 1 000 m(3 281 ft)
• Length of pipe from each indoor unit to the closest branch
(a,b,c,d,e) 40 m(131 ft)
• [Length of pipe from outdoor unit to the farthest indoor unit 5
(A+B+C+D+e)]
- [Length of pipe from outdoor unit to the closest indoor unit 1
(A+a)] 40 m(131 ft)
Method of drawing out pipes on the bottom side
- Drawing out common pipe through side panel
Remove leakage prevention cap
• Remove the leakage prevention cap attached to the outdoor unit
service valve before pipe work.
• Proceed the leakage prevention cap removal as follows:
- Verify whether all the pipes are locked.
- Extract remaining refrigerant or air inside using the service port.
- Remove the leakage prevention cap
h In case of heat pump system installation, please weld with the
proper accessory pipe included with product.
Combination of Y
branch/header Method
Header Method
: Outdoor Unit
: 1st branch (Y branch)
: Y branch
: Indoor Unit
: Header
: Sealed piping
: Outdoor Unit
: Indoor Units
: Sealed piping
: Header
l 40 m [131 ft] (90 m [295 ft])
h 40 m(131 ft)
H 110 m [361 ft]
L 150 m [492 ft] (200 m [656 ft])
l 40 m [131 ft]
h 40 m [131 ft]
H 110 m [361 ft]
L 200 m [656 ft]
D
h * : See Table 4
Y branch method
: Outdoor Unit
: 1st branch (Y branch)
: Indoor Units
l 40 m [131 ft] (90 m [295 ft])
h 40 m [131 ft]
H 110 m [361 ft]
L 150 m [492 ft] (200 m [656 ft])
Indoor
Unit
Refrigerant piping system
1 Outdoor Units
h * : See Table 4
Pipe Drawing Out during Single / Series connection
Method of drawing out pipes on the front side
- Proceed with the pipe work as shown in the below figure for front
side pipe drawing out.
Service Port
Liquid pipe
Gas pipe
Leakage
Prevention Cap
Not used
(keep closed)
Liquid pipe
Gas pipe
High Pressure
Gas pipe
Liquid pipe
131(5-5/32)
126(4-31/32)
Liquid pipe
Not used(keep closed)
High Pressure Gas pipe
Remove Knock Out for the pipes
• Do not give damage to the pipe/base during the Knock Out
work.
• Proceed to pipe work after removing burr after Knock Out work.
Perform sleeve work to prevent damage to the wire when
connecting wires using Knock Outs.
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 20
background
21
ENGLISH
: Outdoor Unit
: 1st branch (Y branch)
: Indoor Units
: Connection branch
pipe between Outdoor
units: ARCNN31
: Connection branch
pipe between Outdoor
units: ARCNN21
Y branch method
10 m
(323 ft)
or less
L150 m(492 ft) (200 m(656 ft) : Conditional application)
ODU Capacity
Master ≥ Slave1 ≥ Slave 2
l
40 m(131 ft) (90 m(295 ft) : Conditional application)
H 361 ft(110 m)
40 m(131 ft)
Slave2
Slave1
Master
h * : See Table 4
Combination of Y branch/
header Method
: Outdoor Unit
: 1st branch(Y branch)
: Y branch
: Indoor Unit
: Connection branch pipe
between Outdoor units:
ARCNN31
: Connection branch pipe
between Outdoor units:
ARCNN21
: Header
: Sealed piping
H 110 m(361 ft)
Master
Slave2
Slave1
F
E
F
E
ODU Capacity
Master ≥ Slave1 ≥ Slave2
40 m(131 ft)
h1
10 m
(33 ft)
or less
L 150 m(492 ft)(200 m(656 ft) : Conditional application)
40 m(131 ft)(90 m(295 ft) : Conditional application)
h * : See Table 4
Pipe Connection Method between outdoor
unit/indoor unit
Header Method
: Outdoor Unit
: Header branch
: Indoor Units
: Sealed piping
: Connection branch pipe
between Outdoor units:
ARCNN31
: Connection branch pipe
between Outdoor units:
ARCNN21
10 m
(33 ft)
or less
H 110 m(361 ft)
40 m(131 ft)
L 200 m(656 ft)
40 m(131 ft)
Master
Slave2
Slave1
ODU Capacity
Master ≥ Slave1 ≥ Slave2
h See Table 2
A : Refrigerant pipe diameter from outdoor unit to first branch
E : Refrigerant pipe diameter for outdoor unit capacity
(Slave 1+ Slave 2+ Slave 3)
F : Refrigerant pipe diameter for outdoor unit capacity
(Slave 2+ Slave 3)
G : Refrigerant pipe diameter for outdoor unit capacity(Slave 3)
L1
L2
L3
H1
E F
Slave2
Slave1
Master
l 40m (131ft)
h 40 m (131 ft)
Indoor
Unit
1st branch
Refrigerant pipe diameter from outdoor unit to first branch
Level Difference
(Outdoor unit Outdoor unit)
5 m [16.4 ft]
Max length from first branch to
each outdoor unit (L1, L2, L3)
Less than 10 m [32.8 ft]
(equivalent length of piping 13 m
[42.7 ft])
h * : See Table 4
WARNING
Increased Pipe Diameter(table 2)
- When pipe length is 90 m [295 ft] or more from ODU to 1st branch
- When level difference is 50 m [164 ft] or more
!
Y branch
Method
Combination of Y
branch/header
Method
Header
Method
Max pipe
length
Outdoor Unit
Indoor Unit
Longest
pipe length(L)
A+B+C+D+e
150 m [492 ft]
(200 m [656 ft] :
Conditional
application)*
A+B+b 150 m
[492 ft]
A+C+e 150 m
[492 ft]
(200 m [656 ft] :
Conditional
application)*
A+f 200 m
[656 ft]
Equivalent
pipe length
175 m [574 ft]
(225 m [738 ft] :
Conditional
application)*
175 m [574 ft]
(225 m [738 ft] :
Conditional
application)*
225 m
[738 ft]
Total pipe
length
1 000 m
[3 281 ft]
1 000 m [3 281 ft]
1 000 m
[3 281 ft]
Max
difference
in height
Outdoor Unit
Indoor Unit
Difference
in height(H)
110 m [361 ft] 110 m [361 ft]
110 m
[361 ft]
Indoor Unit
Indoor Unit
Difference
in height(h)
40 m [131 ft] 40 m [131 ft]
40 m
[131 ft]
Longest
pipe length
after
1st branch
Pipe length(l)
40 m [131 ft]
(90 m [295 ft] :
Conditional
application)*
40 m [131 ft]
(90 m [295 ft] :
Conditional
application)*
40 m
[131 ft]
(Table 1) Limit Pipe length
Series Outdoor Units (2 Units ~ 3 Units)
Piping length from outdoor branch to outdoor unit 10 m(33 ft),
equivalent length : max 13 m(43 ft) (for 14 Ton or more)
Additional Application
To satisfy below condition to make 40 m(131 ft) ~ 90 m(295 ft) of
pipe length after first branch.
• Diameter of pipes between first branch and the last branch
should be increased by one step, except pipe diameter B,C,D is
same as Diameter A
Ø 1/4(6.35 mm) Ø 3/8(9.52 mm) Ø 1/2(12.7 mm)
Ø 5/8(15.88 mm) Ø 3/4(19.05 mm) Ø 7/8(22.2 mm)
Ø 1(25.4)*, Ø 1-1/8(28.58 mm) Ø 1-1/4(31.8 mm)*,
Ø 1-3/8(34.9 mm) Ø 1-1/2(38.1 mm)* Ø 1-5/8(41.3 mm)
* : It is not necessary to size up.
h If the step up size is not available, you can not select the next
higher size available.
While calculating whole refrigerant pipe length, pipe B,C,D length
should be calculated twice.
A+Bx2+Cx2+Dx2+a+b+c+d+e 1 000 m(3 281 ft)
• Length of pipe from each indoor unit to the closest branch
(a,b,c,d,e) 40 m(131 ft)
• [Length of pipe from outdoor unit to the farthest indoor unit 5
(A+B+C+D+e)]
- [Length of pipe from outdoor unit to the closest indoor unit 1
(A+a)] 40 m(131 ft)
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 21
background
22
ENGLISH
(Table 2) Refrigerant pipe diameter from outdoor unit to first branch. (A)
ODU
capacity
(HP(ton))
Pipe diameter when pipe
Length is <90 m (295 ft)
(Standard)
Pipe diameter when pipe
length (ODU IDU)
is 90 m (295 ft)
Pipe diameter when height
differential (ODU IDU)
is >50 m (164 ft)
Liquid pipe
[mm(inch)]
Vapor pipe
[mm(inch)]
Liquid pipe
[mm(inch)]
Vapor pipe
[mm(inch)]
Liquid pipe
[mm(inch)]
Vapor pipe
[mm(inch)]
Outdoor unit Connection
WARNING
• In case of pipe diameter B connected after first branch is bigger
than the main pipe diameter A, B should be of the same size with A.
Ex) In case indoor unit combination ratio ratio 130 % is connected to
24 HP(70 kW) outdoor unit.
1) Outdoor unit main pipe diameter A : Ø 34.9(1-3/8, gas pipe),
Ø 15.88(5/8, liquid pipe)
2) Pipe diameter B after first branch according to 130 % indoor
unit combination(91 kW) : Ø 34.9(1-3/8, gas pipe),
Ø 19.05(3/4, liquid pipe)
Therefore, pipe diameter B connected after first branch
would be Ø 34.9(1-3/8, gas pipe) / Ø 15.88(5/8, liquid pipe)
which is same with main pipe diameter.
[Example]
Instead of using indoor unit total capacity, use outdoor unit model
name in order to choose main pipe diameter by downward.
Do not let the connection pipe from branch to branch exceed the
main pipe diameter chosen by outdoor unit model name.
EX) Where connecting the indoor units to the 24 HP(70 kW) outdoor
unit to 130 % of its system capacity (91 kW) and branching
7 kBtu/h(2.2 kW) indoor unit at the 1st branch
Main pipe diameter (24 HP outdoor unit) outdoor unit): Ø 28.58
(1-1/8, Gas pipe) Ø 15.88(5/8, Liquid pipe)
Pipe diameter between 1st and 2nd branch (88.5 kW indoor
units) : Ø 34.9(1-3/8, Gas pipe) Ø 19.05(3/4, Liquid pipe) in
conformity with downward indoor units.
Since the main pipe diameter of 24 HP(20 Ton) outdoor unit is
Ø 28.58(1-1/8, Gas pipe) and Ø 15.88(5/8, Liquid pipe), Ø 28.58(1-
1/8, Gas pipe) and Ø 15.88(5/8, Liquid pipe) is used as the main
pipe and the connection pipe between 1st and 2nd branch.
!
Indoor Unit Connection
Indoor Unit connecting pipe from branch (a,b,c,d,e,f)
Indoor Unit capacity
[kW(Btu/h)]
Liquid pipe
[mm(inch)]
Gas pipe [mm(inch)]
5.6(19 100)
Ø 6.35(1/4) Ø 12.7(1/2)
< 16.0(54 600) Ø 9.52(3/8) Ø 15.88(5/8)
< 22.4(76 400) Ø 9.52(3/8) Ø 19.05(3/4)
(Table 3) Refrigerant pipe diameter from first branch to last branch (B,C,D)
Downward indoor unit
total capacity [kW(Btu/h)]
Liquid pipe
[mm(inch)]
Gas pipe
[mm(inch)]
5.6(19 100)
Ø 6.35(1/4) Ø 12.7(1/2)
< 16.0(54 600) Ø 9.52(3/8) Ø 15.88(5/8)
22.4(76 400)
Ø 9.52(3/8) Ø 19.05(3/4)
< 33.6(114 700) Ø 9.52(3/8) Ø 22.2(7/8)
< 50.4(172 000) Ø 12.7(1/2) Ø 28.58(1-1/8)
< 67.2(229 400) Ø 15.88(5/8) Ø 28.58(1-1/8)
< 72.8(248 500) Ø 15.88(5/8) Ø 34.9(1-3/8)
< 100.8(344 000) Ø 19.05(3/4) Ø 34.9(1-3/8)
< 173.6(592 500) Ø 19.05(3/4) Ø 41.3(1-5/8)
(Table 4) Conditional Application
WARNING
• In case of pipe diameter B connected after first branch is bigger than
the main pipe diameter A, B should be of the same size with A.
Ex) In case indoor unit combination ratio 120 % is connected to
24 HP(67.2 kW) outdoor unit.
1) Outdoor unit main pipe diameter A : Ø 34.9(Gas pipe),
Ø 15.88(liquid pipe)
2) Pipe diameter B after first branch according to 120 % indoor
unit ombination(80.6 kW) : Ø 34.9(gas pipe), Ø 19.05(liquid pipe)
Therefore, pipe diameter B connected after first branch would
be Ø 34.9(gas pipe) / Ø 15.88(liquid pipe) which is same with
main pipe diameter.
!
Condition Example
1
Diameter of pipes
between first branch
and the last branch
should be increased by
one step, except pipe
diameter B,C,D is same
as Diameter A
40 m [131 ft] <
B+C+D+e
90 m [295 ft]
B, C, D
Change a diameter
2
While calculating whole
refrigerant pipe length,
pipe B,C,D length
should be calculated
twice.
A+Bx2+Cx2+Dx2
+a+b+c+d+e
1 000 m [3 281 ft]
3
Length of pipe from
each indoor unit to the
closest branch
a,b,c,d,e
40 m [131 ft]
4
Length of pipe from
outdoor unit to the
farthest indoor unit 5
(A+B+C+D+e)] -
[Length of pipe outdoor
unit to the closest
indoor unit 1 (A+a)]
40 m [131 ft]
(A+B+C+D+e)-(A+a)
40 m [131 ft]
• To satisfy below condition to make 40 m ~ 90 m of pipe length after first branch.
Ø 6.35(1/4) Ø 9.52(3/8), Ø 9.52(3/8)
Ø 12.7(1/2), Ø 12.7(1/2) Ø 15.88(5/8),
Ø 15.88(5/8) Ø 19.05(3/4),
Ø 19.05(3/4) Ø 22.2(7/8), Ø 22.2(7/8)
Ø 25.4(1), Ø 25.4(1) Ø 28.58(1-1/8),
Ø 28.58(1-1/8) Ø 31.8(1-1/4),
Ø 31.8(1-1/4) Ø 34.9(1-3/8),
Ø 34.9(1-3/8) Ø 38.1(1-1/2)
l
h 40 m [131 ft]
H 110 m [361 ft]
L
Indoor
Unit
8(6) Ø 9.52(3/8) Ø 19.05(3/4) Ø 12.7(1/2) Ø 22.2(7/8) Ø 12.7(1/2) Not increased
10(8) Ø 9.52(3/8) Ø 22.2(7/8) Ø 12.7(1/2) Ø 28.58(1-1/8) Ø 12.7(1/2) Not increased
12(10)~14(12)
Ø 12.7(1/2) Ø 28.58(1-1/8) Ø 15.88(5/8) Not increased Ø 15.88(5/8) Not increased
18(14)~22(18)
Ø 15.88(5/8) Ø 28.58(1-1/8) Ø 19.05(3/4) Ø 31.8(1-1/4) Ø 19.05(3/4) Not increased
24(20) Ø 15.88(5/8) Ø 34.9(1-3/8) Ø 19.05(3/4) Not increased Ø 19.05(3/4) Not increased
26~34(22~28)
Ø 19.05(3/4) Ø 34.9(1-3/8) Ø 22.2(7/8) Ø 38.1(1-1/2) Ø 22.2(7/8) Not increased
36~50(30~42)
Ø 19.05(3/4) Ø 41.3(1-5/8) Ø 22.2(7/8) Not increased Ø 22.2(7/8) Not increased
• Bending radius should be
at least twice the
diameter of the pipe.
• Bend pipe after 500 mm
[19.7 inch] or more from
branch(or header).
Do not bend U type.
It may affect performance
or result in noise.
If U type bending is
required the R should be
more than 200 mm
[7.9 inch].
CAUTION
!
500 mm [19.7 inch]
or more
500 mm [19.7 inch]
or more
R
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 22
background
23
ENGLISH
Pipe Connection Method/Precautions for
Series connections between Outdoor units
- Separate Y branch joints are needed for series connections between
outdoor units.
- Y-branches between the outside units must be installed horizontally.
- Please refer to the below connection examples to install pipe
connections between outdoor units.
Pipe connection between outdoor
units (General Case)
The maximum pipe
length after the first
branching between the
outdoor units is 10 m
[32.8 ft] or less
Oil Trap
Pipes between outdoor units
are 2 m [6.6 ft] or less
2 m [6.6 ft] or less
- If the distance between the outdoor units becomes more than 2 m
[6.6 ft], apply Oil Traps between the gas pipes.
- If the outdoor unit is located lower than the main pipe, apply Oil Trap.
Examples of Wrong Pipe Connections
- If outside units are located at different level, oil trap must be installed
after each Y branch.
- Oil trap should be located at same level of Y branch. (Heat Pump :
High Pressure Vapor / Heat Recovery : High Pressure Vapor & Low
Pressure Vapor)
Pipes between outdoor units
are 2 m [6.6 ft] or longer
Oil Trap
Oil Trap Oil Trap
2 m [6.6 ft] or less
2 m [6.6 ft] or less 2 m [6.6 ft] or less
0.2 m [0.66 ft]
2 m [6.6 ft] or longer
2 m [6.6 ft] or longer
2 m [6.6 ft] or longer
Level
Level
Oil Trap
Level Level
Oil Trap
Toward indoor unit
Toward indoor unit
Pipe inclination (2° or more)
Toward indoor unit
Toward indoor unit
Toward indoor unit
Toward indoor unit
(Example 1)
(Example 2)
(Example 3)
- Apply Oil Trap as shown below when the length of the pipe between
the outdoor units is more than 2 m [6.6 ft]. Otherwise, the unit may
not operate properly.
(Example 1)
Toward indoor unit
≤ 2 m [6.6 ft]
Toward indoor unit
≤ 2 m [6.6 ft]
≥ 2 m [6.6 ft]
≥ 0.2 m [0.66 ft]
Oil Trap
(Example 2)
- If pipe is higher than outside unit, oil trap must be installed after each
Y branch.
- Oil trap should be located at same level of Y branch. (Heat Pump :
High Pressure Vapor / Heat Recovery : High Pressure Vapor & Low
Pressure Vapor)
- The pipes between the outdoor units must maintain horizontal
levelness or give an inclination to prevent a back flow toward the
slave outdoor unit. Otherwise, the unit may not operate properly.
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 23
background
24
ENGLISH
h
h
≥ 0.2 m [0.66 ft]
Toward indoor unit
Toward indoor unit
Oil Trap
(Example 3)
Amount refrigerant of Indoor units
Example) 4Way Ceiling Cassette 14.5 kW(48 kBtu/hr) -1 EA,
Ceiling concealed Duct 7.3 kW(24 kBtu/hr)-2 EA,
Wall Mounted 2.3 kW(7 kBtu/hr)-4 EA
CF = [0.64 kg (1.411 lbs)×1 EA] + [0.26 kg (0.573 lbs)×
2 EA] + [0.26 kg (0.529 lbs)×4 EA]
= 2.12 kg (4.67 lbs)
WARNING
• Regulation for refrigerant leakage
: the amount of refrigerant leakage should satisfy the following
equation for human safety.
If the above equation can not be satisfied, then follow the
following steps.
• Selection of air conditioning system: select one of the next
- Installation of effective opening part
- Reconfirmation of Outdoor Unit capacity and piping length
- Reduction of the amount of refrigerant
- Installation of 2 or more security device (alarm for gas leakage)
• Change Indoor Unit type
:
installation position should be over 2 m (6.6 ft) from the floor (Wall
mounted type Cassette type)
• Adoption of ventilation system
: choose ordinary ventilation system or building ventilation
system
• Limitation in piping work
: Prepare for earthquake and thermal stress
!
Volume of the room at which Indoor Unit of
the least capacity is installed
Total amount of refrigerant in the system
0.44 kg/m
3
(0.028 lbs/ft
3
)
h
Toward indoor unit
(Example 2)
Attach the additional refrigerant table of IDU.
The amount of Refrigerant
The calculation of the additional charge should take into account the
length of pipe and CF(correction Factor) value of indoor unit.
Include only for
Heat Recovery
system
Total liquid pipe : Ø 25.4 mm (1.0 inch)
Additional charge[kg(lbs)]
Total liquid pipe : Ø 22.2 mm (7/8 inch)
Total liquid pipe : Ø 19.05 mm (3/4 inch)
Total liquid pipe : Ø 15.88 mm (5/8 inch)
Total liquid pipe : Ø 12.7 mm (1/2 inch)
Total liquid pipe : Ø 9.52 mm (3/8 inch)
Total liquid pipe : Ø 6.35 mm (1/4 inch)
Number of installed HR units
CF value of indoor unit
=
+
+
+
+
+
+
+
× 0.480 kg/m (0.323 lbs/ft)
× 0.354 kg/m (0.238 lbs/ft)
× 0.266 kg/m (0.179 lbs/ft)
× 0.173 kg/m (0.116 lbs/ft)
× 0.118 kg/m (0.079 lbs/ft)
× 0.061 kg/m (0.041 lbs/ft)
× 0.022 kg/m (0.015 lbs/ft)
× 0.5 kg (1.1 lbs)
6 & 8 Branches
Model : 1.0 kg/EA
(2.2 lbs/EA)
- When connecting the pipes between the outdoor units, the
accumulation of oil in the slave outdoor unit should be avoided.
Otherwise, the unit may not operate properly.
(Example 1)
Toward indoor unit
Toward indoor unit
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 24
background
25
ENGLISH
For Heat Recovery System Installation
Manifold Gauge
Low pressure side Handle
High pressure side Handle
For Heat Pump System Installation
Manifold Gauge
Low Pressure Side Handle
High Pressure Side Handle
WARNING
• Pipe to be vacuumed : gas pipe, liquid pipe
• If the refrigerant amount is not exact, it may not operate
properly.
• If additionally bottled refrigerant amount is over 10 %,
condenser burst or insufficient indoor unit performance may be
caused.
• Low pressure gas pipe should be sealed with a cap in piping
accessories during refrigerant charging.
!
Y branch
A
B
Facing
upwards
Facing
downwards
Within ±3° Within ±3°
Viewed from point A
in direction of arrow
Horizontal
plane
Within +/- 10°
A
Insulator
(included with kit)
Liquid and gas
pipe joints
Insulator for
field piping
Tape
(field supply)
To Branch Piping or Indoor Unit
To Outdoor Unit
• Ensure that the branch pipes are attached horizontally or vertically.
(see the diagram below.)
• There is no limitation on the joint mounting configuration.
• If the diameter of the refrigerant piping selected by the procedures
described is different from the size of the joint, the connecting
section should be cut with a pipe cutter.
• Branch pipe should be insulated with the insulator in each kit.
Branch pipe Fitting
• When the number of indoor units to be connected to the branch
pipes is less than the number of branch pipes available for
connection then cap pipes should be fitted to the surplus branches.
Pinched pipe
B
Header
A
B
C
To Outdoor Unit
To Indoor Unit
• The indoor unit having larger
capacity must be installed closer
to than smaller one.
• If the diameter of the refrigerant
piping selected by the
procedures described is
different from the size of the
joint, the connecting section
should be cut with a pipe cutter.
Pipe cutter
• When the number of pipes to be
connected is smaller than the
number of header branches,
install a cap to the unconnected
branches.
• Fit branch pipe lie in a horizontal plane.
Horizontal plane
View from point B in the direction of the arrow
Refrigerant charging
Liquid Pipe
Low Pressure
Gas Pipe
High Pressure
Gas Pipe
Liquid Pipe
Not used
Gas Pipe
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 25
background
26
ENGLISH
For Heat Recovery System Installation
• Header should be insulated with the insulator in each kit.
• Joints between branch and pipe should be sealed with the tape
included in each kit.
• Any cap pipe should be insulated using the insulator provided with
each kit and then taped as described above.
Insulate the header using
the insulation
material attached to the
branch pipe kit
as shown in the figure.
Insulator
Insulator of field pipe
Tape
Tape
Cap pipe
Insulator for cap pipe
Y branch pipe
[Unit : mm(inch)]
Models Pipe
ARBLB01621
Low-Pressure Vapor Pipe
I.D12.7(1/2)
I.D15.88(5/8)
I.D12.7(1/2)
I.D15.88(5/8)
I.D19.05(3/4)
O.D15.88(5/8)
I.D15.88(5/8)
Liquid pipe
I.D12.7(1/2)
O.D9.52(3/8)
I.D9.52(3/8)
I.D6.35(1/4)
I.D9.52(3/8)
I.D6.35(1/4)
I.D. 9.52(3/8)
I.D6.35(1/4)
High-Pressure Vapor Pipe
I.D9.52
(3/8)
I.D9.52
(3/8)
I.D6.35(
1/4)
I.D12.7(1/2)
I.D12.7(1/2)
I.D12.7(1/2)
I.D15.88(5/8)
I.D15.88(5/8)
Models Pipe
ARBLB03321
Low-Pressure Vapor Pipe
O.D19.05(3/4)
I.D 22.2(7/8)
I.D 22.2(7/8)
O.D19.05(3/4)
I.D25.4(1)
I.D28.58(1-1/8)
I.D19.05(3/4)
I.D22.2(7/8)
I.D15.88(5/8)
I.D19.05(3/4)
I.D12.7(1/2)
I.D12.7(1/2)
I.D15.88(5/8)
I.D19.05(3/4)
I.D25.4(1)
O.D19.05(3/4)
Liquid pipe
I.D9.52(3/8)
I.D12.7(1/2)
I.D9.52(3/8)
I.D6.35(1/4)
I.D12.7(1/2)
I.D9.52(3/8)
I.D12.7(1/2)
I.D6.35(1/4)
High-Pressure Vapor Pipe
I.D19.05(3/4)
I.D19.05(3/4)
O.D19.05(3/4)
I.D9.52
(3/8)
I.D6.35(
1/4)
I.D22.2(7/8)
I.D12.7(1/2)
I.D12.7(1/2)
I.D15.88(5/8)
I.D15.88(5/8)
ARBLB07121
Low-Pressure Vapor Pipe
I.D28.58(1-1/8)
I.D31.8(1-1/4)
I.D34.9(1-3/8)
O.D31.8(1-1/4)
I.D28.58(1-1/8)
I.D31.8(1-1/4)
O.D22.2(7/8)
I.D22.2(7/8)
O.D19.05(3/4)
I.D28.58(1-1/8)
I.D19.05(3/4)
I.D15.88(5/8)
I.D12.7(1/2)
I.D15.88(5/8)
I.D22.2(7/8)
I.D19.05(3/4)
Liquid pipe
I.D12.7(1/2)
I.D15.88(5/8)
I.D19.05(3/4)
I.D15.88(5/8)
I.D19.05(3/4)
I.D12.7(1/2)
I.D12.7(1/2)
I.D19.05(3/4)
I.D15.88(5/8)
I.D9.52(3/8)
O.D12.7(1/2)
I.D6.35(1/4)
I.D9.52(3/8)
O.D12.7(1/2)
High-Pressure Vapor Pipe
I.D28.58(1-1/8)
I.D28.58(1-1/8)
O.D19.05(3/4)
O.D19.05(3/4)
I.D19.05(3/4)
I.D19.05(3/4)
I.D19.05(3/4)
I.D25.4(1)
I.D9.52
(3/8)
I.D22.2(7/8)
I.D12.7(1/2)
I.D12.7(1/2)
I.D12.7(1/2)
I.D15.88(5/8)
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 26
background
27
ENGLISH
For Heat Pump System Installation
Models Pipe
ARBLN01621
Gas pipe
I.D19.05(3/4)
O.D15.88(5/8)
I.D12.7(1/2)
I.D15.88(5/8)
I.D15.88(5/8)
I.D15.88(5/8)
I.D12.7(1/2)
I.D12.7(1/2)
292(11-1/2)
281(11-1/16)
74
(2-29/32)
70(2-3/4)
1
1
Liquid pipe
I.D12.7(1/2)
292(11-1/2)
281(11-1/16)
74
(2-29/32)
70(2-3/4)
I.D6.35(1/4)
I.D6.35(1/4)
I.D6.35(1/4)
1
1
I.D9.52(3/8)
I.D9.52(3/8)
I.D9.52(3/8)
O.D9.52(3/8)
Models Pipe
ARBLN03321
Gas pipe
413(16-1/4)
390(15-11/32)
I.D19.05(3/4)
I.D19.05(3/4)
I.D19.05(3/4)
I.D12.7(1/2)
I.D12.7
(1/2)
70(2-3/4)
I.D15.88(5/8)
I.D15.88(5/8)
I.D25.4(1)
I.D25.4(1)
O.D25.4(1)
80(3-5/32)
110(4-11/32)
83
(3-9/32)
1
2
3
3
O.D19.05(3/4)
O.D19.05(3/4)
1 2
I.D22.2(7/8)
I.D22.2(7/8)
I.D22.2(7/8)
I.D28.58(1-1/8)
Liquid pipe
I.D12.7(1/2)
I.D12.7(1/2)
I.D12.7(1/2)
74
(2-29/32)
332(13-1/16)
321(12-5/8)
I.D6.35(1/4)
I.D6.35(1/4)
I.D9.52(3/8)
I.D9.52(3/8)
I.D9.52(3/8)
ARBLN07121
Gas pipe
I.D12.7
(1/2)
376(14-13/16)
404(15-29/32)
120(4-23/32) 120(4-23/32)
90(3-17/32)
I.D15.88(5/8)
I.D15.88(5/8)
2
3
1
2
1 3
I.D19.05(3/4)
I.D19.05(3/4)
O.D19.05(3/4)
96
(3-25/32)
I.D22.2(7/8)
I.D22.2(7/8)
O.D22.2(7/8)
I.D34.9(1-3/8)
I.D28.58(1-1/8)
I.D28.58(1-1/8)
I.D28.58(1-1/8)
O.D31.8(1-1/4)
I.D31.8(1-1/4)
I.D31.8(1-1/4)
Liquid pipe
I.D15.88(5/8)
I.D15.88(5/8)
I.D15.88(5/8)
I.D12.7(1/2)
I.D12.7(1/2)
I.D12.7(1/2)
O.D12.7(1/2)
O.D12.7(1/2)
70(2-3/4)
110(4-11/32)
371(14-19/32)
394(15-1/2)
83
(3-9/32)
2
3
3
I.D19.05(3/4)
I.D19.05(3/4)
I.D19.05(3/4)
2
I.D6.35(1/4)
I.D9.52(3/8)
I.D9.52(3/8)
ARBLN14521
Gas pipe
I.D12.7(1/2)
70(2-3/4)
471(18-17/32)
517(20-11/32)
125
(4-29/32)
130(5-1/8)
I.D15.88(5/8)
I.D41.3(1-5/8)
I.D41.3
(1-5/8)
I.D41.3(1-5/8)
I.D38.1(1-1/2)
I.D38.1(1-1/2)
I.D38.1(1-1/2)
O.D38.1(1-1/2)
O.D15.88(5/8)
2
3
3
2
2
3
3
120(4-23/32)
120(4-23/32)
90(3-17/32)
I.D19.05(3/4)
I.D19.05(3/4)
I.D22.2(7/8)
I.D22.2(7/8)
O.D22.2(7/8)
I.D34.9(1-3/8)
I.D34.9(1-3/8)
I.D34.9(1-3/8)
O.D34.9(1-3/8)
I.D28.58(1-1/8)
O.D28.58(1-1/8)
I.D28.58(1-1/8)
Liquid pipe
I.D12.7(1/2)
O.D12.7(1/2)
I.D12.7
(1/2)
110(4-11/32)110(4-11/32)
41616-3/8)
444(17-15/32)
O.D15.88(5/8)
I.D15.88(5/8)
I.D19.05(3/4)
I.D15.88(5/8)
I.D15.88(5/8)
I.D19.05(3/4)
I.D19.05(3/4)
O.D19.05(3/4)
80(3-5/32)
2
3
1
2 3 3
96
(3-25/32)
I.D22.2(7/8)
I.D22.2(7/8)
I.D22.2(7/8)
I.D6.35(1/4)
I.D9.52(3/8)
I.D9.52(3/8)
Models Pipe
ARBLB14521
Low-Pressure Vapor Pipe
I.D38.1(1-1/2)
I.D41.3(1-5/8)
O.D34.9(1-3/8)
I.D41.3(1-5/8)
O.D38.1(1-1/2)
I.D19.05(3/4)
O.D22.2(7/8)
I.D15.88(5/8)
I.D12.7(1/2)
O.D15.88(5/8)
I.D22.2(7/8)
O.D28.58(1-1/8)
I.D19.05(3/4)
I.D34.9(1-3/8)
I.D41.3(1-5/8)
I.D38.1(1-1/2)
I.D38.1(1-1/2)
I.D34.9(1-3/8)
I.D28.58(1-1/8)
I.D28.58(1-1/8)
I.D22.2(7/8)
I.D34.9(1-3/8)
Liquid pipe
I.D15.88(5/8)
I.D19.05(3/4)
I.D22.2(7/8)
I.D22.2(7/8)
I.D22.2(7/8)
I.D12.7(1/2)
I.D12.7(1/2)
I.D9.52(3/8)
I.D9.52(3/8)
I.D6.35(1/4)
I.D19.05(3/4)
I.D19.05(3/4)
O.D19.05(3/4)
I.D15.88(5/8)
I.D15.88(5/8)
O.D15.88(5/8)
O.D12.7(1/2)
High-Pressure Vapor Pipe
O.D28.58(1-1/8)
I.D28.58(1-1/8)
I.D28.58(1-1/8)
I.D28.58(1-1/8)
I.D34.9(1-3/8)
O.D19.05(3/4)
I.D19.05(3/4)
I.D19.05(3/4)
I.D25.4(1)
I.D9.52
(3/8)
I.D22.2(7/8)
I.D12.7(1/2)
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 27
background
28
ENGLISH
[Unit:mm(inch)]
Header
Models Pipe
4 branch
ARBL054
Gas pipe
120(4-23/32)
150(5-29/32)
360(14-3/16)
120(4-23/32)
ID15.88(5/8)
ID12.7(1/2)
ID15.88(5/8)
ID19.05(3/4)
ID12.7(1/2)
ID15.88(5/8)
Liquid pipe
120(4-23/32)
120(4-23/32)
150(5-29/32)
360(14-3/16)
ID9.52(3/8)
ID6.35(1/4)
ID9.52(3/8)
ID12.7(1/2)
ID9.52(3/8)
ID6.35(1/4)
7 branch
ARBL057
Gas pipe
540(21-1/4)
120(4-23/32)
150(5-29/32)
120(4-23/32)
ID12.7(1/2)
ID15.88(5/8)
ID12.7(1/2)
ID15.88(5/8)
ID19.05(3/4)
ID15.88(5/8)
Liquid pipe
540(21-1/4)
120(4-23/32)
150(5-29/32)
120(4-23/32)
ID6.35(1/4)
ID9.52(3/8)
ID9.52(3/8)
ID12.7(1/2)
4 branch
ARBL104
Gas pipe
120(4-23/32)
150(5-29/32)
400(15-3/4)
160
ID19.05(3/4)
ID15.88(5/8)
ID22.2(7/8)
ID28.58(1-1/8) ID25.4(1)
ID15.88(5/8)
ID12.7(1/2)
Liquid pipe
120(4-23/32)
120(4-23/32)
150(5-29/32)
360(14-3/16)
ID9.52(3/8)
ID6.35(1/4)
ID9.52(3/8)ID12.7(1/2)
ID9.52(3/8)
ID6.35(1/4)
7 branch
ARBL107
Gas pipe
120(4-23/32)
150(5-29/32)
160
580(22-27/32)
ID19.05(3/4)
ID15.88(5/8)
ID15.88(5/8)
ID12.7(1/2)
ID22.2(7/8)ID28.58(1-1/8) ID25.4(1)
Liquid pipe
120(4-23/32)
150(5-29/32)
700(27-9/16)
120(4-23/32)
ID6.35(1/4)
ID9.52(3/8)
ID9.52(3/8)
ID6.35(1/4)
ID9.52(3/8)ID12.7(1/2)
Models Pipe
10 branch
ARBL1010
Gas pipe
120(4-23/32)
150(5-29/32)
160
760(29-29/32)
ID19.05(3/4)
ID15.88(5/8)
ID15.88(5/8)
ID12.7(1/2)
ID22.2(7/8)ID28.58(1-1/8) ID25.4(1)
Liquid pipe
120(4-23/32)
150(5-29/32)
720(28-11/32)
ID6.35(1/4)
ID9.52(3/8)
ID9.52(3/8)
ID6.35(1/4)
ID12.7(1/2)
ID9.52(3/8)
120(4-23/32)
10 branch
ARBL2010
Gas pipe
ID28.58(1-1/8)ID31.8(1-1/4) ID34.9(1-3/8)
120(4-23/32)
150(5-29/32)
182
775(30-1/2)
ID19.05(3/4)
ID15.88(5/8)
ID15.88(5/8)
ID12.7(1/2)
Liquid pipe
120(4-23/32)
150(5-29/32)
107
60*9=540(21-1/4)
700(27-9/16)
ID6.35(1/4)
ID9.52(3/8) ID19.05(3/4)ID15.88(5/8)
ID9.52(3/8)
ID6.35(1/4)
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 28
background
29
ENGLISH
This function is used for creating vacuum in the system after
compressor replacement, ODU parts replacement or IDU addition /
replacement.
Vacuum mode setting method
ARUM***B(D)TE5
ARUM***CTE5
Vacuum mode off method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“SVC” Push the ‘’ button
Select the Function using ‘’, ‘’ Button : :
“Se3” Push the ‘’ button
Start the vacuum mode : “VACC”
ODU Valve open
ODU EEV open
IDU EEV open
HR unit valve open, SC EEV open
DIP switch off and push the reset button on Master unit PCB
SW01C (Ɨ: Confirm /
Automatic Addressing)
SW02C (ȭ: backward)
SW04C (X : cancel)
DIP-SW01
7-Segment
SW01D (reset)
SW03C (ȯ: forward)
SW01C (Ɨ: Confirm /
Automatic Addressing)
SW02C (ȭ: backward)
SW04C (X : cancel)
DIP-SW01
7-Segment
SW01D (reset)
SW03C (ȯ: forward)
- Ensure that the branch pipes are attached vertically.
Slave
Master
Header
Slave
Master
Slave
Master
Slave
Master
Vertical Distribution
The others
Vacuum Mode
Slave
Master
Slave
Master
1st
1st
1st
Main pipe
Distribution
2nd
2nd
3rd
3rd
Main pipe
Distribution
Slave
Master
1st
3rd
3rd main pipe distribution
2nd
Horizontal Distribution
Distribution Method
ODU operation stops during vacuum mode. Compressor can't
operate.
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 29
background
30
ENGLISH
Series Installation (Heat Pump)
Liquid Pipe
No use (closed)
Gas Pipe
Liquid Pipe
No use (closed)
Gas Pipe
Slave 1 outdoor unit Master outdoor unit
Nitrogen Gas
Cylinder
Indoor
Unit
Liquid Pipe
Gas Pipe
Close
Close
Close
Close
Close
Close
NOTE
!
If the ambient temperature differs between the time when pressure is
applied and when the pressure drop is checked, apply the following
correction factor
There is a pressure change of approximately 0.01 Mpa(1.5 psi) for each
33.8 °F (1 °C) of temperature difference.
Correction= (Temp. at the time of pressurization – Temp. at the time of
check) X 0.1
For example: Temperature at the time of pressurization 3.8
MPa(551 psi) is 80.6 °F (27 °C)
24 hour later: 3.73 MPa(541 psi), 68 °F (20 °C)
In this case the pressure drop of 0.07 MPa
(10 psi) is because of temperature drop
And hence there is no leakage in pipe occurred.
WARNING
Use a vacuum pump or Inert(nitrogen) gas when doing leakage test
or air purge. Do not compress air or Oxygen and do not use
Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
!
Vacuum
Vacuum drying should be made from the service port provided on the outdoor
unit’s service valve to the vacuum pump commonly used for liquid pipe, gas
pipe and high/low pressure common pipe. (Make Vacuum from liquid pipe, gas
pipe and high/low pressure common pipe with the service valve closed.)
* Never perform air purging using refrigerant.
• Vacuum drying: Use a vacuum pump that can evacuate to -100.7 kPa
(-14.6 psi, 5 Torr, -755 mmHg).
- Evacuate the system from the liquid and gas pipes with a vacuum
pump for over 2 hrs and bring the system to -100.7 kPa(-14.6 psi).
After maintaining system under that condition for over 1 hr, confirm
the vacuum gauge rises. The system may contain moisture or leak.
- Following should be executed if there is a possibility of moisture
remaining inside the pipe.
(Rainwater may enter the pipe during work in the rainy season or
over a long period of time)
After evacuating the system for 2 hrs, give pressure to the system
to 0.05 MPa(7.3 psi) (vacuum break) with nitrogen gas and then
evacuate it again with the vacuum pump for 1hr to -100.7 kPa
(-14.6 psi)(vacuum drying). If the system cannot be evacuated to
-100.7 kPa(-14.6 psi) within 2 hrs, repeat the steps of vacuum break
and its drying. Finally, check if the vacuum gauge does not rise or
not, after maintaining the system in vacuum for 1 hr.
When inserting nitrogen
gas of high pressure, it
must be used with
regulator.
WARNING
Use a vacuum pump or Inert(nitrogen) gas when doing leakage test
or air purge. Do not compress air or Oxygen and do not use
Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
!
Series Installation (Heat Recovery)
Scale
Use a graviometer. (One that can measure
down to 0.1 kg (0.22 lbs)). If you are
unable to prepare such a high-precision
gravimeter you may use a charge cylinder.
Vacuum
pump
Vacuum
pump
Indoor unit
Slave 1 outdoor unit Master outdoor unit
Liquid pipe
High Pressure
Gas pipe
High Pressure
Gas pipe
Liquid pipe
Low Pressure
Gas pipe
Low Pressure
Gas pipe
Liquid side
Gas side
Close
Close
Close
Close
Close
Close
HR unit
Series Installation (Heat Pump)
Scale
Use a graviometer. (One that can measure
down to 0.1 kg (0.22 lbs)). If you are
unable to prepare such a high-precision
gravimeter you may use a charge cylinder.
Indoor unit
Liquid pipe
Gas pipe
Gas pipe
Liquid pipe
No use (closed)
No use (closed)
Liquid side
Gas side
Slave 1 outdoor unit Master outdoor unit
Close
Close
Close
Close
Close
Close
Leak test
Leak test should be made by pressurizing nitrogen gas to 3.8 MPa
(551.1 psi). If the pressure does not drop for 24 hours, the system
passes the test. If the pressure drops, check where the nitrogen leaks.
For the test method, refer to the following figure. (Make a test with
the service valves closed. Be also sure to pressurize liquid pipe, gas
pipe and high pressure gas pipe)
The test result can be judged good if the pressure has not be reduced
after leaving for about one day after completion of nitrogen gas
pressurization.
Series Installation (Heat Recovery)
Liquid Pipe
Low Pressure
Gas Pipe
High Pressure
Gas Pipe
Liquid Pipe
Low Pressure
Gas Pipe
High Pressure
Gas Pipe
Nitrogen Gas
Cylinder
Nitrogen Gas
Cylinder
Slave 1 outdoor unit Master outdoor unit
Close
Close
Close
Close
Close
Close
Indoor
Unit
Liquid Pipe
HR unit
Gas Pipe
Leak Test and Vacuum drying
When inserting nitrogen
gas of high pressure, it
must be used with
regulator.
To prevent the nitrogen from entering the refrigeration system in
the liquid state, the top of the cylinder must be at higher position
than the bottom when you pressurize the system.
Usually the cylinder is used in a vertical standing position.
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 30
background
31
ENGLISH
NOTE
!
Always add an appropriate amount of refrigerant. (For the refrigerant
additional charge)
Too much or too little refrigerant will cause trouble.
To use the Vacuum Mode (If the Vacuum mode is set, all valves of Indoor
units and Outdoor units will be opened.)
WARNING
When installing and moving the air conditioner to another site,
recharge after perfect evacuation.
- If a different refrigerant or air is mixed with the original
refrigerant, the refrigerant cycle may malfunction and the unit
may be damaged.
!
Be sure to give insulation work to refrigerant piping by covering liquid
pipe and gas pipe separately with enough thickness heat-resistant
polyethylene, so that no gap is observed in the joint between indoor
unit and insulating material, and insulating materials themselves. When
insulation work is insufficient, there is a possibility of condensation
drip, etc. Pay special attention to insulation work to ceiling plenum.
Heat insulation material
Pipe
Outer covering(Wind the connection part and cutting part of heat
insulation material with a finishing tape.)
Heat insulation
material
Adhesive + Heat - resistant
polyethylene foam + Adhesive tape
Outer
covering
Indoor Vinyl tape
Floor
exposed
Water-proof hemp cloth +
Bronze asphalt
Outdoor
Water-proof hemp cloth +
Zinc plate + Oily paint
NOTE
!
When using polyethylene cover as covering material, asphalt
roofing shall not be required.
Thermal insulation of refrigerant piping
Bad example
• Do not insulate gas or low pressure pipe and liquid or
highpressure pipe together.
• Be sure to fully insulate connecting portion.
These parts are not insulated.
Liquid pipe
Gas pipe
Power lines
Finishing tape
Insulating material
Communication lines
A
C
D
E
B
F
A
Good example
Liquid pipe
Gas pipe
Power lines
Insulating material
Communication lines
Communication lines
Separation
Power lines
E
D
D
B
A
C
A
B
E
B
I
A
B
D
C
1 m
(3.28 ft)
1 m
(3.28 ft)
D
F
G
B
G
D
B
H
I
J
A
F
Penetrations
Sleeve
Heat insulating material
Lagging
Caulking material
Band
Waterproofing layer
Sleeve with edge
Lagging material
Mortar or other incombustible caulking
Incombustible heat insulation material
When filling a gap with mortar, cover the penetration part with steel plate so
that the insulation material will not be caved in. For this part, use
incombustible materials for both insulation and covering. (Vinyl covering
should not be used.)
Inner wall (concealed) Outer wall Outer wall (exposed)
Floor (fireproofing)
Penetrating portion on fire
limit and boundary wall
Roof pipe shaft
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 31
background
32
ENGLISH
Caution
- Follow ordinance of your governmental organization for technical
standard related to electrical equipment, wiring regulations and
guidance of each electric power company.
-
Install the Outdoor Unit communication cable away from the power
source wiring so that it is not affected by electric noise from the power
source. (Do not run it through the same conduit.)
- Be sure to provide designated grounding work to Outdoor Unit.
- Give some allowance to wiring for electrical part box of Indoor and
Outdoor Units, because the box is sometimes removed at the time of
service work.
- Never connect the main power source to terminal block of
communication cable. If connected, electrical parts will be burnt out.
- Use the 2-core shielded wires or 2-core unshielded wires for
communication cable.( mark in the figure below) If communication
cable of different systems are wired with the same multiplecore
cable, the resultant poor transmitting and receiving will cause
erroneous operations. ( mark in the figure below)
- Only the communication cable specified should be connected to the
terminal block for Outdoor Unit communication.
WARNING
Be sure to have authorized electrical engineers do the electric
work using special circuits in accordance with regulations and this
installation manual.
If power supply circuit has a lack of capacity or electric work
deficiency, it may cause an electric shock or fire.
!
ELECTRICAL WIRING
Master Slave
Master Slave
Master Slave1 Slave2
Master Slave1 Slave2
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
2-core shielded cables or 2-core unshielded wires
Multi-Core Cable
Master Slave1 Slave2
Master Slave1 Slave2
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Master Slave
Master Slave
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal
block.
Round pressure terminal
Power cable
When none are available, follow the instructions below.
- Do not connect wiring of different thicknesses to the power terminal
block. (Slack in the power wiring may cause abnormal heat.)
- When connecting cable which is the same thickness, do as shown in
the figure below.
- For wiring, use the designated power cable and connect firmly, then
secure to prevent outside pressure being exerted on the terminal
block.
- Use an appropriate screwdriver for tightening the terinal screws. A
screwdriver with a small head will strip the head and make proper
tighterning impossible.
- Over-tightening the terminal screws may break them.
Be sure to correct the outdoor unit to earth. Do not connect ground
wire to any gas pipe, liquid pipe, lightening rod or telephone earth
line. If earth is incomplete, it may cause an electric shock.
CAUTION
!
• Use the 2-core shielded wires or 2-core unshielded wires for
communication cables. Never use them together with power cables.
• The conductive shielding layer of cable should be grounded to the
metal part of both units.
• Never use multi-core cable
• As this unit is equipped with an inverter, to install a phase leading
capacitor not only will deteriorate power factor improvement effect,
but also may cause capacitor abnormal heating. Therefore, never
install a phase leading capacitor.
• Make sure that the power unbalance ratio is not greater than 2 %.
If it is greater the units lifespan will be reduced.
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 32
background
33
ENGLISH
Front Panel
UXA
UXB
Main Board
External Board
Main power line
terminal block
(Take care of the phase
sequence of 3-phases
3-wires power system)
WARNING
The temperature sensor for outdoor air should not be exposed to
direct sunlight.
- Provide an appropriate cover to intercept direct sunlight.
!
NOTE
!
• The figures are based on assumed length of parallel cabling up
to 100 m [328 ft]. For length in excess of 100 m [328 ft] the
figures will have to be recalculated in direct proportion to the
additional length of cable involved.
• If the power supply waveform continues to exhibit some
distortion the recommended spacing in the table should be
increased.
- If the cable are laid inside conduits then the following point
must also be taken into account when grouping various cable
together for introduction into the conduits
- Power cable(including power supply to air conditioner) and
communication cables
must not be laid inside the same
- In the same way, when grouping the power wires and
communication cables should not be bunched together.
Separation of communication and power cables
- If communication and power cables are installed alongside each other
then there is a strong likelihood of operational faults developing due
to interference in the signal wiring caused by electrostatic and
electromagnetic coupling.
The tables below indicates our recommendation as to appropriate
spacing of communication and power cables where these are to be
run side by side
Communication and Power Cables
Communication cable
- Types : shielded wires or unshielded wires
- Cross section : 1.0 ~ 1.5 mm
2
(1.55 × 10
-3
~ 2.32 × 10
-3
in
2
)
- Maximum allowable temperature: 60 °C (140 °F)
- Maximum allowable cable length: under 1 000 m (3 281 ft)
Remote control cable
- Types : 3-core cables
Central control cable
Product type Cable type Diameter
ACP&AC Manager
2-core cable (Shielding cable)
1.0 ~ 1.5 mm
2
(1.55 × 10
-3
~
2.32 × 10
-3
in
2
)
AC Smart
2-core cable (Shielding cable)
1.0 ~ 1.5 mm
2
(1.55 × 10
-3
~
2.32 × 10
-3
in
2
)
Simple central controller
4-core cable (Shielding cable)
1.0 ~ 1.5 mm
2
(1.55 × 10
-3
~
2.32 × 10
-3
in
2
)
Current capacity of power cable Spacing
100 V or more
10 A 300 mm (11-13/16 inch)
50 A 500 mm (19-11/16 inch)
100 A 1 000 mm (39-3/8 inch)
Exceed 100 A 1 500 mm (59-1/16 inch)
Control box and connecting position of wiring
- Remove all of the screws at front panel and remove the panel by
pulling it forward.
- Connect communication cable between main and slave outdoor unit
through the terminal block.
- Connect communication cables between outdoor unit and indoor
units through the terminal block.
- When the central control system is connected to the outdoor unit, a
dedicated PCB must be connected between them.
- When connecting communication cable between outdoor unit and
indoor units with shielded cable, connect the shield ground to the
earth screw.
- Be sure to also make grounding connections to ground screws when
connecting shielded wires to the central control system.
In case of using the shielded wires, it should be grounded.
CAUTION
!
If apparatus is not properly earthed then there is always a risk of
electric shock, the grounding of the apparatus must be carried out by
a qualified person.
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 33
background
34
ENGLISH
Wiring of main power supply and equipment
capacity
- Use a separate power supply for the Outdoor Unit and Indoor Unit.
- Bear in mind ambient conditions (ambient temperature,direct
sunlight, rain water,etc.) when proceeding with the wiring and
connections.
- The cable size is the minimum value for metal conduit wiring. The
power cord size should be 1 rank thicker taking into account the line
voltage drops. Make sure the power-supply voltage does not drop
more than 10 %.
- Specific wiring requirements should adhere to the wiring regulations
of the region.
- Power supply cords of parts of appliances for outdoor use should not
be lighter than polychloroprene sheathed flexible cord.
- Don't install an individual switch or electrical outlet to disconnect
each of indoor unit separately from the power supply.
WARNING
• Follow ordinance of your governmental organization for
technical standard related to electrical equipment, wiring
regulations and guidance of each electric power company.
• Make sure to use specified cables for connections so that no
external force is imparted to terminal connections. If
connections are not fixed firmly, it may cause heating or fire.
• Make sure to use the appropriate type of overcurrent protection
switch. Note that generated overcurrent may include some
amount of direct current.
!
Field Wiring
208/230 V
Example Connection of Communication Cable
1 Outdoor Unit-3 Ø, 208/230 V
Switch
ELCB
Communication Line
(2 Wires Cable)
Power Line
(3 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
ELCB
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Outdoor Unit]
[Indoor Units]
Power supply
3 Phase 3 Wires
60 Hz 208/230 V
Power supply
1 Phase 60 Hz
208/230 V
(Main Switch)
Pull box
(Installer option)
Pull box
(Installer option)
Pull box
(Installer option)
HR unit
L(L1) N(L2)
R(L1)
S(L2) T(L3)
2 Outdoor Units-3 Ø, 208/230 V
When the power source is connected In series between the units.
When the power source is supplied to Each outdoor unit individually.
Communication Line
(2 Wires Cable)
Power Line
(3 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Master]
[Indoor Units]
(Main Switch)
[Slave]
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
nication L
es Cable
Com
Power
(2 Wires
(2 Wires C
r Line
(2 Wires Cab
[
Master]
[Sla
Power L
Wire
Power supply
3 Phase 3 Wires
60 Hz 208/230 V
Power supply
1 Phase 60 Hz
208/230 V
RST
Switch
ELCB
ELCB
L(L1) N(L2)
Switch
Communication Line
(2 Wires Cable)
Power Line
(3 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Master]
[Indoor Units]
Power supply
3 Phase 3 Wires
60 Hz 208/230 V
Power supply
1 Phase 60 Hz
208/230 V
(Main Switch)
[Slave]
Switch
ELCBELCB
Pull box
(Installer option)
Pull box
(Installer option)
Pull box
(Installer option)
Power Line
(2 Wires Cable)
HR unit
ELCB
L(L1) N(L2)
R(L1)
S(L2) T(L3)
R(L1)
S(L2) T(L3)
HR unit
3(A) 4(B) 3(A) 4(B) 3(A) 4(B) 3(A) 4(B)
AB
Master
Outdoor Unit
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
Between Indoor and Master Outdoor unit
WARNING
• Indoor unit ground lines are required for preventing electrical shock
accident during current leakage, Communication disorder by noise
effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect
each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an
integrated manner because this system consists of the equipment
utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase,
momentary blackout or the power goes on and off while the
product is operating, attach a reversed phase protection circuit
locally. Running the product in reversed phase may break the
compressor and other parts.
• When using shielded wires, perform a single-point grounding only
to the outdoor unit for grounding of communication wires.
!
• Some installation site may require attachment of an earth leakage
breaker. If no earth leakage breaker is installed, it may cause an
electric shock.
• Do not use anything other than breaker and fuse with correct
capacity. Using fuse and wire or copper wire with too large capacity
may cause a malfunction of unit or fire.
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 34
background
35
ENGLISH
Master
Outdoor Unit
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
Slave
Outdoor Unit
HR unit
AB
3(A) 4(B) 3(A) 4(B) 3(A) 4(B) 3(A) 4(B)
Master
Outdoor Unit
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
Between Indoor and Master Outdoor unit
• It is not the point to make ground connection.
- Make sure that terminal number of master and slave outdoor units
are matched.(A-A,B-B)
WARNING
• Indoor unit ground lines are required for preventing electrical shock
accident during current leakage, Communication disorder by noise
effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect
each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an
integrated manner because this system consists of the equipment
utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase,
momentary blackout or the power goes on and off while the
product is operating, attach a reversed phase protection circuit
locally. Running the product in reversed phase may break the
compressor and other parts.
!
3 Outdoor Units-3 Ø, 208/230 V
When the power source is connected In series between the units.
Communication Line
(2 Wires Cable)
Power Line
(3 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Master]
[Indoor Units]
(Main Switch)
[Slave1] [Slave2]
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Communic
(3 W
Po
(2 Wire
ne
Cable)
Power
(2 Wires
[
Master
]
[Slav
Power Line
2 Wires Ca
)
Switch
ELCB
ELCB
Power supply
3 Phase 3 Wires
60 Hz 208/230 V
Power supply
1 Phase 60 Hz
208/230 V
L(L1) N(L2)
R(L1)
S(L2) T(L3)
NOTE
!
- Field wiring diagram is to be used as a guidelineonly. Wiring
should comply with applicable local and national codes
- ELCB must have function to prevent electrical short and over
current at the same time.
- Use copper wires only.
- Unit must be grounded in compliance with the applicable local
and national codes.
- ELCB and fuse/breaker must install to the power line
Switch
Communication Line
(2 Wires Cable)
Power Line
(3 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Master]
[Indoor Units]
Power supply
3 Phase 3 Wires
60 Hz 208/230 V
Power supply
1 Phase 60 Hz
208/230 V
(Main Switch)
[Slave1] [Slave2]
Switch Switch
ELCB ELCB ELCB
Pull box
(Installer option)
Pull box
(Installer option)
Pull box
(Installer option)
Power Line
(2 Wires Cable)
HR unit
ELCB
L(L1) N(L2)
R(L1)
S(L2) T(L3)
R(L1)
S(L2) T(L3)
R(L1)
S(L2) T(L3)
When the power source is supplied to Each outdoor unit individually.
NOTE
!
- Field wiring diagram is to be used as a guidelineonly. Wiring
should comply with applicable local and national codes
- ELCB must have function to prevent electrical short and over
current at the same time.
- Use copper wires only.
- Unit must be grounded in compliance with the applicable local
and national codes.
- ELCB and fuse/breaker must install to the power line
Master
Outdoor Unit
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
Master
Outdoor Unit
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
Slave1
Outdoor Unit
HR unit
Slave2
Outdoor Unit
AB
3(A) 4(B) 3(A) 4(B) 3(A) 4(B) 3(A) 4(B)
Between Indoor and Master Outdoor unit
• It is not the point to make ground connection.
- Make sure that terminal number of master and slave outdoor units
are matched.(A-A,B-B)
WARNING
• Indoor unit ground lines are required for preventing electrical shock
accident during current leakage, communication disorder by noise
effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect
each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an
integrated manner because this system consists of the equipment
utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase,
momentary blackout or the power goes on and off while the
product is operating, attach a reversed phase protection circuit
locally. Running the product in reversed phase may break the
compressor and other parts.
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 35
background
36
ENGLISH
Between Indoor and Master Outdoor unit
460 V / 575 V
Example Connection of Communication Cable
1 Outdoor Unit-3 Ø, 460 V / 575 V
WARNING
• Indoor unit ground lines are required for preventing electrical shock
accident during current leakage, Communication disorder by noise
effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect
each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an
integrated manner because this system consists of the equipment
utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase,
momentary blackout or the power goes on and off while the
product is operating, attach a reversed phase protection circuit
locally. Running the product in reversed phase may break the
compressor and other parts.
!
Switch
ELCB
Communication Line
(2 Wires Cable)
Power Line
(3 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
ELCB
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Outdoor Unit]
[Indoor Units]
Power supply
3 Phase 3 Wires
60 Hz 460 V / 575 V
Power supply
1 Phase 60 Hz
208/230 V
(Main Switch)
Pull box
(Installer option)
Pull box
(Installer option)
Pull box
(Installer option)
HR unit
L(L1) N(L2)
R(L1)
S(L2) T(L3)
Master
Outdoor Unit
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
HR unit
AB
3(A) 4(B) 3(A) 4(B) 3(A) 4(B) 3(A) 4(B)
2 Outdoor Units-3 Ø, 460 V / 575 V
When the power source is connected In series between the units.
Switch
Communication Line
(2 Wires Cable)
Power Line
(3 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Master]
[Indoor Units]
Power supply
3 Phase 3 Wires
60 Hz 460 V / 575 V
Power supply
1 Phase 60 Hz
208/230 V
(Main Switch)
[Slave]
Switch
ELCBELCB
Pull box
(Installer option)
Pull box
(Installer option)
Pull box
(Installer option)
Power Line
(2 Wires Cable)
HR unit
ELCB
L(L1) N(L2)
R(L1)
S(L2) T(L3)
R(L1)
S(L2) T(L3)
Communication Line
(2 Wires Cable)
Power Line
(3 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Master]
[Indoor Units]
(Main Switch)
[Slave]
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
HR unit
Power supply
3 Phase 3 Wires
60 Hz 460 V / 575 V
Power supply
1 Phase 60 Hz
208/230 V
Switch
ELCB
ELCB
L(L1) N(L2)
R(L1)
S(L2) T(L3)
When the power source is supplied to Each outdoor unit individually.
NOTE
!
- Field wiring diagram is to be used as a guideline only. Wiring
should comply with applicable local and national codes
- ELCB must have function to prevent electrical short and over
current at the same time.
- Use copper wires only.
- Unit must be grounded in compliance with the applicable local
and national codes.
- ELCB and fuse/breaker must install to the power line
Master
Outdoor Unit
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
Slave
Outdoor Unit
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
Master
Outdoor Unit
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
HR unit
AB
3(A) 4(B) 3(A) 4(B) 3(A) 4(B) 3(A) 4(B)
Between Indoor and Master Outdoor unit
• It is not the point to make ground connection.
- Make sure that terminal number of master and slave outdoor units
are matched.(A-A,B-B)
WARNING
• Indoor unit ground lines are required for preventing electrical shock
accident during current leakage, Communication disorder by noise
effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect
each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an
integrated manner because this system consists of the equipment
utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase,
momentary blackout or the power goes on and off while the product
is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor
and other parts.
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 36
background
37
ENGLISH
Master
Outdoor Unit
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
Master
Outdoor Unit
SODU. B SODU. A IDU. B IDU. A CEN. B CEN. A DRY1 DRY2 GND 12V
Slave1
Outdoor Unit
HR unit
AB
Slave2
Outdoor Unit
3(A) 4(B) 3(A) 4(B) 3(A) 4(B) 3(A) 4(B)
Between Indoor and Master Outdoor unit
• It is not the point to make ground connection.
- Make sure that terminal number of master and slave outdoor units
are matched.(A-A,B-B)
WARNING
• Indoor unit ground lines are required for preventing electrical shock
accident during current leakage, Communication disorder by noise
effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect
each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an
integrated manner because this system consists of the equipment
utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase,
momentary blackout or the power goes on and off while the product
is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor
and other parts.
!
3 Outdoor Units-3 Ø, 460 V / 575 V
When the power source is connected In series between the units.
Switch
Communication Line
(2 Wires Cable)
Power Line
(3 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Master]
[Indoor Units]
Power supply
3 Phase 3 Wires
60 Hz 460 V / 575 V
Power supply
1 Phase 60 Hz
208/230 V
(Main Switch)
[Slave1] [Slave2]
Switch Switch
ELCB ELCB ELCB
Pull box
(Installer option)
Pull box
(Installer option)
Pull box
(Installer option)
Power Line
(2 Wires Cable)
HR unit
ELCB
L(L1) N(L2)
R(L1)
S(L2) T(L3)
R(L1)
S(L2) T(L3)
R(L1)
S(L2) T(L3)
Communication Line
(2 Wires Cable)
Power Line
(3 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Master]
[Indoor Units]
(Main Switch)
[Slave1] [Slave2]
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
HR unit
Switch
ELCB
ELCB
Power supply
3 Phase 3 Wires
60 Hz 460 V / 575 V
Power supply
1 Phase 60 Hz
208/230 V
L(L1) N(L2)
R(L1)
S(L2) T(L3)
When the power source is supplied to Each outdoor unit individually.
NOTE
!
- Field wiring diagram is to be used as a guideline only. Wiring
should comply with applicable local and national codes
- ELCB must have function to prevent electrical short and over
current at the same time.
- Use copper wires only.
- Unit must be grounded in compliance with the applicable local
and national codes.
- ELCB and fuse/breaker must install to the power line
Example) Connection of transmission wire
[BUS type]
- Connection of communication cable must be installed like below
figure between indoor unit to outdoor unit.
HR unit
HR unit
[STAR type]
- Abnormal operation can be caused by communication defect, when
connection of communication cable is installed like below figure.
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 37
background
38
ENGLISH
Example) Connection of power and communication cable (UXA)
Gap : Over
50 mm(1.97’’)
When connecting
Main power lines
/ Ground wire from left side
When connecting
Communication wires
/ Ground wire from left side
Main power
terminal block
Ground wire
Main power
terminal block
Insulation sleeves
attachments
Ground wire
Ground wire
ODU-IDU
Communication
cable
ODU-ODU
Communication
cable
Bottom Side
Main power
terminal block
Ground wire
When connecting
Communication wires
/ Ground wire from
front guide panel
When connecting
Main power lines
/ Ground wire from
front guide panel
Gap : Over
50 mm(1.97’’)
Front Side
Fix firmly with cable tie or
clamp cord not to be displaced
Main power line
connection
Communication/Ground
wire connection
Example) Connection of power and communication cable (UXB)
Main power
terminal block
Ground wire
Gap : Over
50 mm(1.97’’)
When connecting
Main power lines
/ Ground wire from left side
When connecting
Communication wires
/ Ground wire from left side
Bottom Side
Checking the setting of outdoor units
Checking according to DIP switch setting
- You can check the setting values of the Master outdoor unit from the
7 segment LED.
The DIP switch setting should be changed when the power is OFF.
Checking the initial display
The number is sequentially appeared at the 7 segment in 5 seconds
after applying the power. This number represents the setting condition.
[Main Board]
ARUM***B(D)TE5
DIP switch
7 segment
SW01C (Automatic
Addressing Setting)
Main power
terminal block
Insulation sleeves
attachments
Ground wire
ODU-IDU
Communication
cable
ODU-ODU
Communication
cable
Ground wire
Main power
terminal block
Ground wire
When connecting
Communication wires
/ Ground wire from
front guide panel
When connecting
Main power lines
/ Ground wire from
front guide panel
Gap : Over
50 mm(1.97’’)
Front Side
Fix firmly with cable tie
or clamp cord not to be
displaced
Main power line
connection
Communication/Ground
wire connection
It should be wiring power cables or communication cables to avoid
interference with the oil level sensor. Otherwise, That oil level sensor
would be operated abnormally.
CAUTION
!
It should be wiring power cables or communication cables to avoid
interference with the oil level sensor. Otherwise, That oil level sensor
would be operated abnormally.
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 38
background
39
ENGLISH
ARUM***CTE5
DIP switch
7 Segment
SW01C
(Automatic Addressing Setting)
Quick control Setting
In the factory setting, main PCB DIP switch setting is all “OFF”.
- Check and make sure that all the indoor unit model name are
ARNU******4.
- Change the main PCB DIP switch No. 3 “OFF ON” like below
picture.
- Push the reset button.
ARUM***B(D)TE5
7 segmentDIP Switch
Reset button
DIP switch
7-Segment
Reset button
• Initial display order
• Example) ARUM480BTE5
48 HP 208/230 V Heat Recovery system
(Master unit: 22 HP, Slave 1: 14 HP, Slave 2: 12 HP)
Order HP(Ton) Mean
8(6)~24(20) Master unit capacity
26(22)~44(36) Slave 1 unit capacity
46(38)~52(42) Slave 2 unit capacity
8(6)~52(42) Total capacity
3 Heat Recovery (Factory Setting)
46 460 V model
57 575 V model
22 208/230 V model
30 Full function
22 14 12 48 3 22 1
HP 8 10 12 14 18 20 22 24
TON 6 8 10 12 14 16 18 20
• Master Unit
h Heat Pump installation
Turn on the DIP s/w No 4.
The factory setting display is appeared “HR”.
Change “HR” into “HP” display pushing button and then push
confirm button.
Turn off the DIP s/w No 4. and Push reset button to restart the
system. (If you turn on the DIP s/w No 4, you can make sure “HR”
or “HP” display later.)
• Slave Unit
DIP switch
setting
ODU Setting
Slave 1
Slave 2
DIP switch
setting
ODU Setting
Heat Recovery
System (Factory
Setting)
DIP switch
setting
ODU Setting
Setting Heat pump
system or Heat Recovery
system (Installer Setting)
ARUM***CTE5
1,MFL68980308,영영 2018. 11. 13. 영영 3:23 Page 39
background
40
ENGLISH
Switch for setup of HR Unit
2 Series
Main function of SW02M
1 Selection of the method for addressing valves of an HR unit
(Auto/Manual)
2 Setting the zoning control
SW02M
ON
S/W
Selection
No.1
Method for addressing valves of an
HR unit (Auto/Manual)
No.2 Model of HR unit
No.3 Model of HR unit
No.4 Model of HR unit
No.5 Valve group setting
No.6 Valve group setting
No.7
Use only in factory
production (preset to
“OFF”)
Zoning
setting
(“ON”)
No.8
Use only in factory
production (preset to
“OFF”)
Auto Manual
Switch No.1 OnSwitch No.1 Off
DIP Switch setting
Normal
control
Zoning
control
SW01M
SW01M
Turn the DIP switch of
the zoning branch on.
Ex) Branch 1,2 are
zoning control.
* Number from left in sequence for less-than-8 branch model.
** PRHR043A / PRHR033A / PRHR023A : Master Only
* Zoning control
This function is used to connect multiple indoor units to one pipe.
SW02M
(DIP switch for setup of
The function of HR unit)
SW03M
SW04M
SW01M/SW03M/SW04M
(Switch for manual valve
addressing)
SW01M
SW05M
#1 valve housing
#4 valve housing
7-SEG
Setting For Heat Recovery Unit (Refer Only Heat
Recovery Installation)
[Heat Recovery (HR) Unit Board]
2 Series
Branch #1~4
Bypass
(from left)
SC EEV
ڸڹںڻڼڽھڿ
Branch #3,4
High/Low
(from top)
Branch #1,2
High/Low
(from top)
Branch #5~8
Bypass
(from left)
Branch #7,8
High/Low
(from top)
Branch #5,6
High/Low
(from top)
7-SEG
Main PCB (2EA, same P/No)
7-SEG
Liquid
Bypass
Valve
- SW02E : Use only SW
No.5
- SW01E : Branch #5~8
(from SW No.1)
- SW01C
- SW01D/SW01C/
SW02B/SW01B/SW02E
- SW01E : Branch #1~4 (from
SW No.1)
Branch No.
3 Series
Main PCB (Master) Main PCB (Slave)
SW Function
DIP
SW
SW02E
(8pin
DIP SW)
Selection of the method for
pipe detection
Selection of Master/Slave
Main PCB
Setting the Zoning Control
Selection of the No. of
connected branches
SW01E
(4pin
DIP SW)
Selection of the valve to
address
Rotary
SW
0
SW01D
(Left)
Selection of the Valve
Group Control
SW01C
(Right)
Manual addressing of
zoning indoor units
Setting to address HR units
Push
SW
SW02B
(Left)
Increase in the digit of 10
SW01B
(Right)
Increase in the digit of 1
3 Series
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 40
background
41
ENGLISH
Main function of SW02E
ON S/W Selection
No.1 Method for pipe detection of an HR Unit (Auto/Manual)
No.2
No. of connected branchesNo.3
No.4
No.5 Master/Slave (Main PCB) Setting
No.6 EEPROM factory initialization (4,5,6)
No.7
Use only in factory production
(preset to "OFF")
Zoning setting ("ON")
No.8
Use only in factory production
(preset to "OFF")
3 Selection of the model of HR unit
2 Series
3 Series
* Each model is shipped with the switches No.2 and No.3 pre-adjusted
as above in the factory.
(For 2 branches)
PRHR022A
(For 3 branches)
PRHR032A
(For 4 branches)
PRHR042A
Initial
Setting
1 branches
Connected
2 branches
Connected
3 branches
Connected
4 branches
Connected
1
2
3
1
2
1
3
2
4
PRHR023A
1
2
PRHR033A
1
2
3
PRHR043A
1
2
3
4
1 branch
Connected
2 branch
Connected
3 branch
Connected
4 branch
Connected
5 branch
Connected
6 branch
Connected
7 branch
Connected
8 branch
Connected
PRHR063A
1
2
3
4
5
6
PRHR083A
1
2
3
4
5
6
7
8
1 branch
Connected
2 branch
Connected
3 branch
Connected
4 branch
Connected
5 branch
Connected
6 branch
Connected
7 branch
Connected
8 branch
Connected
WARNING
• If you want to use a PRHR032A for 2 branches HR unit after
closing the 3rd pipes, set the DIP switch for 2 branches HR unit.
• If you want to use a PRHR042A for 3 branches HR unit after
closing the 4th pipes, set the DIP switch for 3 branches HR unit.
• If you want to use a PRHR042A for 2 branches HR unit after
closing the 3rd and 4th pipes, set the DIP switch for 2 branches
HR unit.
• The unused port must be closed with a copper cap, not with a
plastic cap.
!
WARNING
If you want to use a “Model” for “No. of using branch(es)” HR
Unit after closing the “Closing pipe No.”, set the DIP switch for
“No. of using branch(es)” HR Unit.
Ex) If you want to use a PRHR083A for 4 branches HR Unit after
closing the 5~8th pipes, set the DIP switch for 4 branches HR
Unit.
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 41
background
42
ENGLISH
4 Setting the Valve Group.
2 Series
NOTE
!
If the large capacity indoor units are installed, below Y branch pipe
should be used.
Y branch pipe
(Unit: mm [inch])
SW05M (Rotary S/W for addressing HR unit)
Must be set to '0' when installing only one HR unit.
When installing multiple HR units, address the HR units with
sequentially increasing numbers starting from '0'.
Ex) Installation of 3 HR units
1
2
3
4
1
2
3
4
1
2
3
4
AB AB AB
S/W No. Setup
No.1 Manual addressing of valve #1
No.2 Manual addressing of valve #2
No.3 Manual addressing of valve #3
No.4 Manual addressing of valve #4
SW03M
Increase in the digit of 10 of valve
address
SW04M
Increase in the last digit of valve
address
SW01M
SW03M
SW04M
2 Zoning setting
- Set the address of the valve of the HR unit to the central control
address of the connected indoor unit.
- SW01M : selection of the valve to address
SW03M : increase in the digit of 10 of valve address
SW04M : increase in the last digit of valve address
SW05M :Rotary S/W
- Prerequisite for manual valve addressing : central control address
of each indoor unit must be preset
differently at its wired remote control.
S/W No. Setup
No.1 Manual addressing of valve #1
No.2 Manual addressing of valve #2
No.3 Manual addressing of valve #3
No.4 Manual addressing of valve #4
SW03M
Increase in the digit of 10 of valve
address
SW04M Increase in the last digit of valve address
SW05M Manual addressing of zoning indoor units
SW01M
SW03M
SW04M
SW05M
SW01M/SW03M/SW04M (DIP S/W and tact S/W for
manual valve addressing)
1 Normal setting (Non-Zoning setting)
- Set the address of the valve of the HR unit to the central control
address of the connected indoor unit.
- SW01M: selection of the valve to address
SW03M: increase in the digit of 10 of valve address
SW04M: increase in the last digit of valve address
- Prerequisite for manual valve addressing : central control address
of each indoor unit must be preset differently at its wired remote
control.
Models Low pressure Gas pipe Liquid pipe
ARBLN
03321
O.D19.05
I.D 22.2
I.D 22.2
O.D19.05
I.D25.4
I.D28.58
I.D19.05
I.D22.2
I.D15.88
I.D19.05
I.D12.7
I.D12.7
I.D15.88
I.D19.05
I.D25.4
O.D19.05
I.D9.52
I.D12.7
I.D9.52
I.D6.35
I.D12.7
I.D9.52
I.D12.7
I.D6.35
* Setting the Valve Group
This function is used to connect one indoor unit to two pipes. (Large
capacity indoor unit over 56 kBtu must be connected to two pipes.)
DIP S/W setting Example
Not control
Indoor Unit
Indoor Unit
Indoor Unit
Indoor Unit
1
2
3
4
No.1, 2 Valve
Control
Indoor Unit
Indoor Unit
Large capacity indoor unit
1
2
3
4
No.2, 3 Valve
Control
Indoor Unit
Indoor Unit
Large capacity indoor unit
1
2
3
4
No.3, 4 Valve
Control
Large capacity indoor unit
Indoor Unit
Indoor Unit
1
2
3
4
No.1, 2 Valve
/
No.3, 4 Valve
Control
Large capacity indoor unit
Large capacity indoor unit
1
2
3
4
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 42
background
43
ENGLISH
3 Series
Main function of SW01D
- Selection of the Valve Group Control
NOTE
!
Use the Valve Group Control when 2 branches are connected with
only 1 indoor unit which has higher capacity than 61 kBtu.
NOTE
!
If the large capacity indoor units are installed, below Y branch pipe
should be used.
Valve Group
SW01D
Setting
Valve Group
SW01D
Setting
Not control 0 No. 5,6/7,8 Valve Control 8
No. 1,2 Valve Control 1 No. 1,2/5,6 Valve Control 9
No. 2,3 Valve Control 2 No. 1,2/7,8 Valve Control A
No. 3,4 Valve Control 3 No. 3,4/5,6 Valve Control B
No. 5,6 Valve Control 4 No. 3,4/7,8 Valve Control C
No. 6,7 Valve Control 5
No. 1,2/3,4/5,6 Valve
Control
D
No. 7,8 Valve Control 6
No. 1,2/3,4/6,7 Valve
Control
E
No. 1,2/3,4 Valve
Control
7
No. 1,2/3,4/7,8 Valve
Control
F
* Master Only
Models Low Pressure Gas Pipe Liquid pipe
ARBLB03321
413(16-1/4)
390(15-11/32)
I.D19.05(3/4)
I.D19.05(3/4)
I.D19.05(3/4)
I.D12.7(1/2)
I.D12.7
(1/2)
70(2-3/4)
I.D15.88(5/8)
I.D15.88(5/8)
I.D25.4(1)
I.D25.4(1)
O.D25.4(1)
80(3-5/32)
110(4-11/32)
83
(3-9/32)
1
2
3
3
O.D19.05(3/4)
O.D19.05(3/4)
1
2
I.D22.2(7/8)
I.D22.2(7/8)
I.D22.2(7/8)
I.D28.58(1-1/8)
I.D12.7(1/2)
I.D12.7(1/2)
I.D12.7(1/2)
74
(2-29/32)
332(13-1/16)
321(12-5/8)
I.D6.35(1/4)
I.D6.35
(1/4)
I.D9.52(3/8)
I.D9.52(3/8)
I.D9.52(3/8)
Models High Pressure Gas Pipe
ARBLB03321
I.D15.88(5/8)
I.D12.7(1/2)
I.D12.7(1/2)
70(2-3/4)
I.D25.4(1)
110(4-11/32)
I.D19.05(3/4)
I.D19.05(3/4)
2
3 2
3
O.D15.88(5/8)
444(17-15/32)
421(16-9/16)
96
(3-25/32)
I.D15.88
(5/8)
I.D22.2(7/8)
I.D22.2(7/8)
I.D22.2(7/8)
O.D15.88(5/8)
I.D19.05(3/4)
I.D9.52(3/8)
h Y branch pipe
[Unit : mm(inch)]
SW01C (Rotary S/W for addressing HR unit)
Must be set to '0' when installing only one HR unit.
When installing multiple HR units, address the HR units with
sequentially increasing numbers starting from '0'.
Maximum 16 HR Units can be installed.
Ex) Installation of 3 HR units
SW01B/SW01C/SW01E/SW02B
(DIP S/W and push S/W for Manual pipe detection)
- Set the address of the valve of the HR unit to the central control
address of the connected indoor unit.
- SW01E: selection of the valve to address
SW02B: increase in the digit of 10 of valve address
SW01B: increase in the last digit of valve address
SW01C: Manual addressing of zoning indoor units
(use for Zoning setting)
- Prerequisite for Manual pipe detection : central control address of
each indoor unit must be preset differently at its wired remote
control.
AB AB AB
* Master Only
SW01E
S/W No. Setup
No.1
Manual addressing of valve #1
(Master) / #5 (Slave)
No.2
Manual addressing of valve #2
(Master) / #6 (Slave)
No.3
Manual addressing of valve #3
(Master) / #7 (Slave)
No.4
Manual addressing of valve #4
(Master) / #8 (Slave)
SW02B
SW02B
Increase in the digit of 10 of valve
address
SW01B
SW01B
Increase in the last digit of valve
address
SW01B
SW01C
Manual addressing of zoning indoor
units
* Use for Zoning setting
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 43
background
44
ENGLISH
SW01E
SW #1 On : Select Valve #1
Master
ON
OFF
SW02B SW01B
Input the central control
address of Indoor unit
Master
SW01E
SW #1 Off : Finish Valve #1
Master
ON
OFF
SW01E
SW #2 On : Select Valve #6
Slave
ON
OFF
SW02B SW01B
Input the central control
address of Indoor unit
Slave
SW01E
SW #2 Off : Finish Valve #6
Slave
ON
OFF
1 Normal setting (Non-Zoning setting)
ex) Manual pipe detection of Valve #1, 6.
2 Zoning setting
SW01E
SW #1 On : Select Valve #5
Slave
ON
OFF
SW02B SW01B
SW01C
After selecting No.1 zoning
indoor unit, input the central
control address of indoor unit.
Slave
After selecting No.2 zoning
indoor unit, input the central
control address of indoor unit.
Setting SW01C to ‘0’After selecting No.3 zoning
indoor unit, input the central
control address of indoor unit.
SW01E
SW #1 Off : Finish Valve #5
Slave
ON
OFF
SW01E
SW #2 On : Select Valve #6
Slave
ON
OFF
SW02B SW01B
Input the central control
address of Indoor unit
Slave
SW01E
SW #2 Off : Finish Valve #6
Slave
ON
OFF
0
SW02B
SW01C
SW01B
Slave
1
SW01C
Slave
0
SW02B
SW01C
SW01B
Slave
2
ex) Manual pipe detection of Valve #5 with three zoning indoor units,
#6 without zoning unit.
NOTE
!
Use the Zoning Control when install two or more indoor units at 1
branch of HR Unit.
The indoor units controlled by Zoning Control can be selected
collectively as the cooling / heating mode.
DIP switch
7 segment
SW01C
(Automatic Addressing Setting)
Automatic Addressing
The address of indoor units would be set by Automatic
Addressing
- Wait for 3 minutes after supplying power.
(Master and Slave outdoor units, indoor units)
- Press RED button of the outdoor units for 5 seconds. (SW01C)
- A “88” is indicated on 7-segment LED of the outdoor unit PCB.
- For completing addressing, 2~7 minutes are required depending on
numbers of connected indoor units
-
Numbers of connected indoor units whose addressing is completed are
indicated for 30 seconds on 7-segment LED of the outdoor unit PCB
- After completing addressing, address of each indoor unit is indicated
on the wired remote control display window. (CH01, CH02,
CH03, ……, CH06 : Indicated as numbers of connected indoor units)
[Main Board]
ARUM***B(D)TE5
ARUM***CTE5
DIP switch
7 Segmen
t
SW01C
(Automatic Addressing Setting)
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 44
background
45
ENGLISH
The Procedure of Automatic Addressing
• Automatic addressing process end
Numbers of indoor unit connected are indicated for 30
seconds on 7-segment LED after completing process.
Indoor address number is displayed on wired remote controller or
indoor unit display window. It is not an error message, will
disappeared when on/off button is pressed on remote controller
ex) Display of 01, 02, ..., 15 means connection of 15 indoor units
and Automatic addressing is completed normally.
Automatic addressing process start
Waiting 3 minutes
Power On
Press RED Button for
5 seconds (SW01C)
7-segment LED = 88
Don’t press RED Button
(SW01C)
Waiting about 2~7 minutes
7-segment LED
OK
YES
NO Check the connections
of communication cable
= 88
Setting For Heat Recovery Unit (Refer Only Heat Recovery Installation)
Automatic pipe detection
1 Turn No.1 of DIP s/w SW02M of HR unit PCB off.
2 Confirm that the setting of No.2, 3 of SW02M corresponds with the
type of the valve connection.
3 Reset the power of HR unit PCB
4 Master Out door unit PCB DIP switch on : No.5
5 Select the mode using ‘’, ‘’ Button : “Idu” Push the ‘’ button
6 Select the “Id 5” function using ‘’, ‘’ Button :“Ath” or “”Atc”
Push the ‘’ button.
Outdoor temperature is over 15 °C(59 °F) : “Atc” Using (If it fail, use
“Ath”)
Outdoor temperature is below 15 °C(59 °F) : “Ath” Using (If it fail,
use “Atc”)
7 Select the mode using ‘’, ‘’ Button : “Idu” Push the ‘’ button
8 Select the “Id 6” function using ‘’, ‘’ Button :“StA” Push the
’ button
9 System is operated after ”88” is displayed on 7 segment of the
outdoor unit main PCB.
10 Pipe detection process is proceeded.
11 5~30 minutes are required depending on the number of the indoor
units and outdoor temperature.
12 The number of the indoor units connected is displayed on 7
segment of the outdoor unit main PCB for about 1 minute
- For a HR unit, the number of the indoor units connected to each
HR unit is displayed.
- '200' is displayed in case of auto pipe detecting error, and Auto
pipe detection process is completed after '88' is disappeared.
* Auto pipe detection function : the function that sets connection
relationship automatically between the indoor unit and HR unit.
WARNING
Execute auto addressing and auto pipe detection again whenever
the indoor PCB and HR unit PCB is replaced.
- Operation error occurs unless power is supplied to the indoor
and HR units.
Error No.200 occurs if the number of connected indoor units and
that of scanned indoor units are different.
• If
auto pipe detection process fails, complete it with manual pipe
detection (see Manual pipe detection part).
• If
auto pipe detection process is completed normally, manual
pipe detection is not required.
If you want to do auto pipe detection again after auto pipe
detection fails, do after reset of outdoor unit by all means.
During 5 minutes after pipe detection is completed, do not turn
off the main unit PCB to save the result of pipe detection
automatically.
!
CAUTION
• In replacement of the indoor unit PCB, always perform Automatic
addressing setting again (At that time, please check about using
Independent power module to any indoor unit.)
• If power supply is not applied to the indoor unit, operation error
occur.
• Automatic Addressing has to be performed after more than 3
minutes to improve indoor unit communition when initial power is
supplied.
• Please be sure that all the DIP switch (1~7) of master outdoor unit is
OFF before Automatic Addressing setting
!
Manual pipe detection
1 Enter the central control address into each indoor unit using its
wired remote controller.
2 Turn No.1 of DIP s/w SW02M of HR unit PCB on.
3 Reset the power of HR unit PCB.
4 On the HR unit PCB, manually set address of each valve of the HR
unit to the central control address of the indoor unit connected to
the valve.
5 Reset the power of outdoor unit PCB.
6 The number of the indoor unit installed is displayed after about 5
minutes.
Ex) HR The number of the indoor
7 Reset the power of outdoor unit PCB, HR unit.
8 Manual pipe detection is completed
WARNING
In case that central controller is not installed, firstly set up central
controller’s setting to make address setting of indoor units.
In case that central controller is installed, please set central
control address in wired remote control of indoor unit.
• Do not set central control address of indoor unit to ‘0xFF’. (If the
address is ‘0xFF’, pipe detection will not be completed properly.)
HR units’s manual pipe address is set by the central control
address of indoor units.
Address of valve which is not connected with indoor unit should
be set differently with the address of a valve which is indoor unit
connected. (If address is overlapped, valve will not work
properly)
If there occurs some error during pipe detection process, it
means pipe detection process is not properly finished.
If an error occurred, it means that manual pipe setting is not
completed.
During 5 minutes after pipe detection process is completed, do
not turn off the main outdoor unit’s PCB to save the result of
pipe detection automatically.
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 45
background
46
ENGLISH
Reset the power of HR unit PCB
Confirm that the setting of No.2, 3 of
SW02M corresponds with the valve
connection type
88' is displayed on 7-SEG of the outdoor
unit main PCB
Outdoor unit is operated for 5~60 minutes
The number of indoor units detected is
displayed for 30 seconds on the outdoor
unit PCB after outdoor unit stopped
Display error on outdoor unit PCB
Display error on HR unit PCB
Outdoor unit PCB : HR ơ HR unit
number ơ Valve number
HR unit : '200'
Check the HR unit and indoor unit
Does the setting
status satisfy indoor unit’s
configuration properly
during operation?
Confirm indoor unit’s address setting
Turn No.1 of DIP s/w SW02M of HR unit PCB off.
NO
YES
Master Outdoor unit’s PCB DIP switch on : No.5
Select the mode using ‘ȯ’, ‘ȭ’ Button :
“Idu” Push the ‘Ɨ’ button
Select the mode using ‘ȯ’, ‘ȭ’ Button :
“Idu” Push the ‘Ɨ’ button
Select the “Id 6” function using ‘ȯ’, ‘ȭ
Button :“StA” Push the ‘Ɨ’ button
Select the “Id 5” function using ‘ȯ’, ‘ȭ
Button :“Ath” or ”Atc” Push the ‘Ɨ’ button.
Outdoor temperature is over 15 °C(59 °F) :
Select “Atc” (if fails, use “Ath”)
Outdoor temperature is below 15 °C(59 °F)
: Select “Ath” (if fails, use “Atc”)
* It is possible to be generated mode
changing noise of heating and cooling
which is normal.
There is no mode changing noise at normal
operation.
Completion of auto pipe detection Process
Is the number
of indoor units connected and
displayed one equal?
Pipe detection error occurs for 30
seconds.
Check the installation status of
outdoor, indoor, HR unit
Incompletion of auto detection Process
Retry auto pipe detection Process
after fixing wrong installation
NO
YES
Flow chart of auto pipe detection Process
ARUM***B(D)TE5
ARUM***CTE5
SW01C (Ɨ: Confirm /
Automatic Addressing)
SW02C (ȭ: backward)
SW04C (X : cancel)
DIP-SW01
7-Segment
SW01D (reset)
SW03C (ȯ: forward)
SW01C (Ɨ: Confirm /
Automatic Addressing)
SW02C (ȭ: backward)
SW04C (X : cancel)
DIP-SW01
7-Segment
SW01D (reset)
SW03C (ȯ: forward)
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 46
background
47
ENGLISH
Completion of manual pipe detection Process
Reset the power of HR unit PCB.
Input the central control address at
each indoor unit using wired remote
controller.
Set the address of each valve manually
by referring indoor unit’s central control
address connected with.
Reset the power of outdoor unit PCB.
Wait for about 5 minutes.
The number of the indoor units connected
is displayed.
Ex)HR
The number of connected indoor units
Check the central control address of
indoor and HR unit.
Make sure that reset the outdoor
unit’s
power after setting central control
address of indoor units.
Is the number
of indoor units connected with the
outdoor unit and displayed number
equal?
Execute in case of Auto pipe detection
failure
Turn No.1 of SW02M of HR unit PCB on.
NO
YES
- Above setup must be done for all HR unit valves.
- The valve that is not connected with any indoor unit should be
addressed with any other number than used address numbers of the
valves connected with indoor units.
(The valves does not work if the address numbers are same.)
No. Display and setup Setup and Contents
1
- Operation: None
- Display: None
2
- Operation: Turn DIP S/W No.1 on to
address valve #1
- Display: Existing value saved in
EEPROM is displayed in 7-SEG.
3
- Operation: Set the digit of 10 to the
number in Group High data of the wired
remote control connected to the
corresponding indoor unit to the valve
#1 by pressing left tack S/W.
- Display: Digit increasing with the times
of pressing tack S/W is displayed in left
7-SEG
4
- Operation: Set the digit of 1 to the
number in Group Low data of the wired
remote control connected to the
corresponding indoor unit to the valve
#1 by pressing right tack S/W.
- Display: Digit increasing with the times
of pressing tack S/W is displayed in
right 7-SEG
5
- Operation: Turn DIP S/W No.1 off to
save the address of valve #1
- Display: "11" displayed in 7-SEG
disappears
7-SEG SW01M SW03M SW04M
7-SEG SW01M SW03M SW04M
7-SEG SW01M SW03M SW04M
7-SEG SW01M SW03M SW04M
7-SEG SW01M SW03M SW04M
Example of manual valve addressing (Non-
Zoning setting)
(In case that an indoor unit of central control address "11" is connected
to a valve #1 of an HR unit)
- Prerequisite for manual valve addressing: central control address of
each indoor unit must be preset differently at its wired remote
control.
Flow chart of manual addressing for pipe
detection
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 47
background
48
ENGLISH
- Above setup must be done for all HR unit valves.
- The valve that is not connected with any indoor unit should be
addressed with any other number than used address numbers of the
valves connected with indoor units.
(The valves does not work if the address numbers are same.)
No. Display and setup Setup and Contents
1
- Operation: None
- Display: None
2
- Operation : Turn DIP S/W No.1 on to
address valve #1
- Display : Existing value saved in
EEPROM is displayed in 7-SEG.
3
- Operation : Set the digit of 10(1) to the
number in Group High data of the wired
remote control connected to the
corresponding indoor unit to the valve
#1 by pressing left tack S/W.
- Display : Digit increasing with the times
of pressing tack S/W is displayed in left
7-SEG.
4
- Operation : SW05M : 1
- Display : Display former value.
5
- Operation : Setting No. using SW03M
and SW04M, SW05M : 1
- Display : Display setting value.
6
- Operation : Turn DIP S/W No.1 off to
save the address of valve #1
- Display : "11" displayed in 7-SEG
disappears.
7
- Operation : Return valve of addressing
HR unit.
- Display : None
7-SEG SW01M SW03M SW04M
0
SW05M
7-SEG SW01M SW03M SW04M
SW05M
0
7-SEG SW01M SW03M SW04M
SW05M
0
1
7-SEG SW01M SW03M SW04M
SW05M
7-SEG SW01M SW03M SW04M
SW05M
1
7-SEG SW01M SW03M SW04M
SW05M
1
7-SEG SW01M SW03M SW04M
SW05M
0
No. Display and setup Setup and Contents
1
- Operation: Turn DIP S/W No.1 on.
- Display: "11" is displayed in 7-SEG
2
- Operation: Turn DIP S/W No.1 off
- 7-SEG disappeared
7-SEG SW01M
7-SEG SW01M
No. Display and setup Setup and Contents
1
- Operation: more than 2 DIP switches
turned on.
- Display: "Er" is displayed in 7-SEG
7-SEG SW01M
ROTARY 01 ROTARY 02
0
0
The connected port number of HR
unit
The connected HR unit number
The auto addressing number of indoor
unit (digit of 1)
The auto addressing number of indoor
unit (digit of 10)
No. of Indoor unit.
No. of HR unit branch.
No. of HR unit.
ROTARY 01 ROTARY 02
7 segment
0
0
Setting method of Master indoor unit in zoning
1 Turn DIP switch 5,6,10 on at system off.
2 Set the left Rotary switch for HR unit.(Rotary switch No. "0" ‘ HR unit
No. "1")
3 Set the right Rotary switch for IDU unit.(Rotary switch No. "0" ‘ HR
unit branch No. "1")
4 Display the Master IDU No. of the HR unit on 7segment.(Default
display is "00" on 7segment)
5 Press the black button.(The IDU No. increase every 1 second in the
zoning )
6 Set the Master IDU.(Press the red button during 1.5 seconds stop
twinkling)
Method of checking the pipe detection result
at outdoor unit
1 Wait for 5 minutes, after Pipe detection is completed.
2 Turn on the No.10,14,16 DIP S/W of SUB PCB at master unit
3 Check the data on 7- segment, switching rotary 01,02.
Identification of Manual Valve ID (Address)
Method of checking the pipe detection result
at HR unit
In case that an indoor unit of central control address "11" is connected
to a valve #1 of an HR unit
Example of manual valve addressing (Zoning
setting)
(In case that an indoor unit of central control address "11" is connected
to a valve #1 of an HR unit)
Zoning control is connecting 2 or more indoor units at one pipe of HR
unit. In case of Zoning control, in order to set controls with multiple
indoor units connection uses the rotary switch. Namely, only the rotary
switch changes from same valve set condition and set indoor units
connection.
1 On DIP switch of the corresponding valves and sets the rotary
switch at 0.
2 Setting the number with tact switch.
3 In case of addition of indoor units to same port, increases 1 with the
rotary switch and sets number with tact switch.
4 In case of checking the number which the corresponding valve is
stored, turn on DIP switch and set the number of rotary switch.
5 Indoor units set available 7 per a port(rotary switch 0~6), in case of
setting above of 7 with rotary switch, it will display error.
6 Setting the rotary switch on original condition(HR unit number set
conditions) after all finishing a piping setting.
7 The rotary switch set value of above number of indoor units which
is connected with FF and prevents a malfunction.
(Example: The case where 3 indoor units is connected in piping 1,
sets from rotary switch 0,1,2 and 3,4,5 with FF set)
- Prerequisite for manual valve addressing: central control address of
each indoor unit must be preset differently at its wired remote
control.
• Waiting for 80 seconds after power on.
• The zoning information and Master IDU information remove from
EEPROM after Auto-addressing.
• If there is installed the central control, it is impossible setting of
Master IDU in zoning.
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 48
background
49
ENGLISH
Outdoor Units (External PCB)
Group Number setting
Group Number setting for Indoor Units
- Confirm the power of whole system(Indoor Unit, Outdoor Unit) is
OFF, otherwise turn off.
- The communication cables connected to CEN.A and CEN.B terminal
should be connected to central control of Outdoor Unit with care for
their polarity (A-A, B-B ).
- Turn the whole system on.
- Set the group and Indoor Unit number with a wired remote control.
- To control several sets of Indoor Units into a group, set the group ID
from 0 to F for this purpose.
Example) Group number setting
1
st
number indicate the group number
2nd number point out indoor unit number
SODU.B SODU.A IDU.B IDU.A CEN.B CEN.A DRY1 DRY2 GND 12V
B(D) A(C)
1 F
Group Indoor unit
Group recognizing the central controller
No.0 group (00~0F)
No.1 group (10~1F)
No.2 group (20~2F)
No.3 group (30~3F)
No.4 group (40~4F)
No.5 group (50~5F)
No.6 group (60~6F)
No.7 group (70~7F)
No.8 group (80~8F)
No.9 group (90~9F)
No. A group (A0~AF)
No. B group (B0~BF)
No. C group (C0~CF)
No. D group (D0~DF)
No. E group (E0~EF)
No. F group (F0~FF)
WARNING
• Valve address and central control address of its corresponding
indoor unit should be set identical in manual addressing.
!
Valve (04)
EX)
Valve (03)
Valve (02)
Valve (01)
Indoor unit (04)
Indoor unit (03)
Indoor unit (02)
Indoor unit (01)
Central control address
HR unit
Setting the optional function
Select the mode/function/option/value using ‘’, ‘’ Button and
confirm that using the ‘’ button after DIP switch No.5 is turned on.
ARUM***B(D)TE5 ARUM***CTE5
SW01C (Ɨ: Confirm /
Automatic Addressing)
SW02C (ȭ: backward)
SW04C (X : cancel)
DIP-SW01
7-Segment
SW01D (reset)
SW03C (ȯ: forward)
SW01C (Ɨ: Confirm /
Automatic Addressing)
SW02C (ȭ: backward)
SW04C (X : cancel)
DIP-SW01
7-Segment
SW04D (reset)
SW03C (ȯ: forward)
Optional Mode Selection Function Selection Option Selection
Remarks
Content
Display ()
Content
Display
(, )
Default
Optional
(, )
FDD
Automatic Refrigerant
Charging (Cooling)
--
* Refer FDD
guidance
Automatic Refrigerant
Charging (Heating)
--
Refrigerant Amount
Check (Cooling)
--
Refrigerant Amount
Check (Heating)
--
Automatic system check
mode (cooling or heating)
--
All IDU operation
(Cooling)
--
Compulsory
Operation
for 1 hour
All IDU operation
(Heating)
--
Installation
Cool & Heat
Selector
oFF
oFF,
oP1~oP2
Saving in
EEPROM
High Static Pressure
Compensation mode
oFF
oFF,
oP1~oP7
Night Low Noise
mode
oFF
oFF,
oP1~oP12
Overall Defrost
mode
North
America: oFF
Europe: oFF
Tropical: oN
on, oFF
ODU address setting
0 254
Snow Removal &
Rapid Defrost
oFF
oFF,
oP1~oP3
Airflow Adjusting
for IDU
(Heating capacity up)
oFF on, oFF
Target Pressure
Adjusting
oFF
oFF,
oP1~oP6
Low Ambient Kit
oFF on, oFF
High Efficiency
Mode (Cooling
Operation)
oFF on, oFF
Auto Dust Removal
Mode
oFF
oFF,
oP1~oP5
Compressor Max.
Frequency Limit
oFF
oFF,
oP1~oP9
ODU Fan Max.
RPM Limit mode
oFF
oFF,
oP1~oP7
Smart Load Control
Mode setting
oFF
oFF,
oP1~oP3
Humidity Reference
Mode setting
on on, oFF
Central Control
Connection at
Indoor Unit side
oFF oFF, on
Compressor Input
Current Limit mode
oFF
oFF,
oP1~oP10
Overall Defrost
Operating in Low
temperature
(Heating)
oFF on, oFF
Optional Base panel
Heater
oFF on, oFF
User
Comfort Cooling
Mode setting
EAch
* Refer
Comfort
Cooling
guidance
Saving in
EEPROM
Service
Vaccum Mode vACC -
1 time /
1 Selection
* Functions saved in EEPROM will be maintained continuously,
though the system power was reset.
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 49
background
50
ENGLISH
FAN Maximum RPM of each step
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn2” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“op1~op7” Push the ‘’ button
Start the Static pressure compensation mode :
Save the selected option value in EEPROM
Chassis UXA UXB
Max. RPM
Standard 880 1 000
Overload / Low
Temperature
880 1 150
op1 860 950
op2 840 900
op3 820 850
op4 800 800
op5 780 750
op6 760 700
op7 740 650
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn3” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“op1~op12” Push the ‘’ button
Start the Night low noise function :
Save the selected option value in EEPROM
Night Low Noise Function (Fn 3)
In cooling mode, this function makes the ODU fan operate at low RPM
to reduce the fan noise of ODU at night which has low cooling load.
Night low noise function setting method
High Static Pressure Compensation mode (Fn 2)
This function secures the air flow rate of ODU, in case static pressure
has been applied like using duct at fan discharge of ODU.
Static pressure compensation mode setting method
Function setting
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn1” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1”,“op2” Push the ‘’ button
Cool & Heat Selection mode is set
Cool & Heat selector (Fn 1)
Mode setting method
Switch Control Function
Switch
(Up)
Switch
(Down)
oFF op1(mode) op2(mode)
Right side
(On)
Left side
(On)
Not operate Cooling Cooling
Right side
(On)
Right side
(On)
Not operate Heating Heating
Left side
(Off)
- Not operate Fan mode Off
Switch (Up)
Switch (Down)
Left side
Right side
• To perform the otional funtion should be sure that All the IDU is off
mode, unless the function will not be performed.
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• If use a function, first install a Cool & Heat selector.
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 50
background
51
ENGLISH
Time Settings
Step Judgment Time(Hr) Operation Time(Hr)
op1 8 9
op2 6.5 10.5
op3 5 12
op4 8 9
op5 6.5 10.5
op6 5 12
op7 8 9
op8 6.5 10
op9 5 12
op10 Continuous operation
op11 Continuous operation
op12 Continuous operation
Noise
Step Noise(dBA)
op1 ~ op3, op10 -3
op4 ~ op6, op11 -6
op7 ~ op9, op12 -9
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn4” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“on” ~ “oFF” Push the ‘’ button
Overall defrost mode is set
Mode setting
- on: Operate overall defrost
- off: Operate partial defrost
Mode setting
setting Mode
oFF Not setting
op1 Snow removal mode
op2 Rapid defrost mode
op3 Snow removal mode. + Rapid defrost mode.
Snow removal & rapid defrost (Fn 6)
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn6” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1” ~ “op3” Push the ‘’ button
Mode is set
Setting the ODU address (Fn 5)
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn5” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“0” ~ “255” Push the ‘’ button
ODU address is set
Overall HEX defrost mode (Fn 4)
Mode setting method
• Request installer to set the function during installation.
• If ODU RPM changes, cooling capacity may go down.
CAUTION
!
• Ask an authorized technician to setting a function.
CAUTION
!
• Ask an authorized technician to setting a function.
• If use a function, first install a Central controller.
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 51
background
Setting
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“op1” ~ “op4” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn8” Push the ‘’ button
Target pressure is set
Select the Option using ‘’, ‘’ Button :
“HEAT” , “COOL” Push the ‘’ button
Mode
Purpose
Condensing
temperature
variation
Evaporating
temperature
variation
Heat Cool
op1 Increase capacity Increase capacity
+2 °C
(35.6 °F)
-3 °C
(37.4 °F)
op2
Decrease power
consumption
Increase capacity
+2 °C
(35.6 °F)
-1.5 °C
(-34.7 °F)
op3
Decrease power
consumption
Decrease power
consumption
-4 °C
(-39.2 °F)
+2.5 °C
(36.5 °F)
op4
Decrease power
consumption
Decrease power
consumption
-6 °C
(-42.8 °F)
-4.5 °C
(-40.1 °F)
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn10” Push the ‘’ button
High Efficiency Mode is set
Select the Option using ‘’, ‘’ Button :
“on”,“oFF” Push the ‘’ button
- Target low pressure will change according to ODU temperature
during the cooling operation.
52
ENGLISH
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn11” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1”~“op5” Push the ‘’ button
Auto Dust Removal Mode is set
Mode Setting
Setting
Operation
time
Operating
time
Repeat
cycle
Detail of function
op1
Stop
+2 hours
5 minutes 2 hours
After product stopped 2 hours,
fan operating 5 minutes.
(Repeated every 2 hours)
op2
stop
+5 minutes
3 minutes
Twice
in 2
hours
After product stopped 5
minutes, fan operating 3
minutes. (Limited to two
times within 2 hours)
op3
stop
+5 minutes
3 minutes 1 time
After product stopped 2
hours, fan operating 5
minutes. (Repeated every 2
hours)
op4
Stop
+1 minute
1 minute 1 time
After product stopped 5 minutes,
fan operating 3 minutes. (when io
module connection / one-time
operation)
op5
Stop
+1 minute
1 minute
Low
speed
After product stopped 1
minute, fan operating 1 minute.
(every time the product stops)
Auto Dust Removal Mode (Fn 11)
The ability to set reverse run outdoor fan to remove dust, heat
exchanger.
Mode setting method
High Efficiency Mode (Cooling Operation) (Fn 10)
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn9” Push the ‘’ button
Low Ambient Kit Mode is set
Select the Option using ‘’, ‘’ Button :
“on”,“oFF” Push the ‘’ button
h Reference for functional logic of I/O Module
Low Ambient Kit (Fn 9)
Mode setting method
Target pressure adjusting (Fn 8)
Mode setting method
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 52
background
53
ENGLISH
Function setting
Setting Frequency (Hz)
oFF -
op1 143 Hz
op2 135 Hz
op3 128 Hz
op4 120 Hz
op5 113 Hz
op6 105 Hz
op7 98 Hz
op8 90 Hz
op9 83 Hz
MAX. RPM Limit Setting
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn13” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1”~“op7” Push the ‘’ button
ODU Fan Max. RPM Limit Mode is set
Chassis UXA UXB
Fan MAX. RPM
Limit (RPM)
oFF 880 1 000
oP1 -20 -50
oP2 -40 -100
oP3 -60 -150
oP4 -80 -200
oP5 -100 -250
oP6 -120 -300
oP7 -140 -350
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn 12” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1”,“op9” Push the ‘’ button
Cool & Heat Selection mode is set
SLC(Smart Load Control) Mode
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn14” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1”~“op3” Push the ‘’ button
SLC(Smart Load Control) Mode is set
Setting Mode Detail of function
oFF Not Setting -
oP1 Smooth Mode Slowly control, a target pressure value
oP2 Normal Mode Normal control, a target pressure value
oP3 Peak Mode Fast control, a target pressure value
Mode setting
- on:using humidity sensor
- oFF:not setting
<Using of humidity sensor>
- When used cooling operation of SLC function,it will improve energy
effcience because evaporation temperature wll be decreased
- When used heating operation in case of high humidity condition,
deforest will be delayed because target high/low pressure will be
changed.
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn16” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“on” Push the ‘’ button
Humidity Reference Control mode is set
Humidity Reference Control (Fn 16)
Mode setting method
SLC (Smart Load Control) (Fn 14)
Function for set the variable target pressure which for the high
efficiency and comport operation depend on ODU load.
Mode setting method
ODU Fan Max. RPM Limit (Fn 13)
Mode setting method
Compressor Max. Frequency Limit (Fn 12)
Mode setting method
• Ask an authorized technician to setting a function.
• If use a function, first install a Central controller.
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 53
background
54
ENGLISH
Compressor Input Current Limit
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn20” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1”~”op10” Push the ‘’ button
Compressor Input Current Limit mode is set
Mode Compressor Input Current Limit
oFF 100 %
op1 95 %
op2 90 %
op3 85 %
op4 80 %
op5 75 %
op6 70 %
op7 65 %
op8 60 %
op9 55 %
op10 50 %
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn16” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“Fn19” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“on”,“oFF” Push the ‘’ button
Central Control Connection at Indoor
Unit side Mode is set
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn23” Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“on” Push the ‘’ button
Base pan Heater operation mode is set
Base pan Heater operation (Fn 23)
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Func” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn21” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Fn22” Push the ‘’ button
Overall Defrost Operating in Low Mode is set
Setting Detail of function
Defualt OFF
Setting ON/OFF Control
Overall Defrost Operating in Low temperature
(Heating) (Fn 22)
Mode setting method
Compressor Input Current Limit Mode (Fn 20)
System Input Current Control
Mode setting method
Central Control Connection at Indoor Unit side (Fn 19)
Mode setting method
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• If use a function, capacity may go down.
CAUTION
!
• Function to prevent freezing of ODU base pan in a cold area.
• Heater is accesory.(Sold separately)
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 54
background
55
ENGLISH
Setting of comfort cooling operation
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button :
“Idu” Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
“Id10” Push the ‘’ button
EEV pulse appearing
(seg1, seg2:Idu No./seg3, seg4:Mode)
Select the Function using ‘’, ‘’ Button :
Idu No. setting and Push the ‘’ button
Select the Function using ‘’, ‘’ Button :
Mode setting and Push the ‘’ button
*Mode can be set 0~3 (”0” is no setting)
Setting of comfort cooling operation
Mode setting Effect
0 No setting
1 Cooling capacity low,Power consumption low
2 Cooling capacity mid,Power consumption mid
3 Cooling capacity high,Power consumption high
Comfort Cooling operation (Id 10)
It is function to reduce the ODU energy consumption by the continuou
s operation without thermo off.
Mode setting method
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 55
background
56
ENGLISH
Self-Diagnosis Function
Error Indicator
- This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
- Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of outdoor unit control board as
shown in the table.
- If more than two troubles occur simultaneously, lower number of error code is first displayed.
- After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
1st,2nd,3rd LED of 7-segment indicates error number, 4th LED indicates unit number.(* = 1: Master, 2: Slave 1, 3: Slave 2)
Ex) 1051 : Error occurrence with error number 105 at No. 1 outdoor unit (=Master unit)
In case of indoor unit error occurrence, the error number is only shown at remote controller
without 7 segment LED of outdoor unit.
Ex) CH 01 : Error occurrence with error number 01 (at remote controller)
In case of compressor error occurrence, 7 segment LED of outdoor unit control board
will display its error number alternately with compressor number.
Ex) 213 C23 : It means that compressor error occurred with Error No. 21 at No. 3 Outdoor unit (=Slave 2)
* Refer to the DX-Venitilation manual for DX-Venitilation error code.
Error No. of Compressor
Error No.
Error No. of Unit
Repeat
Display Title Cause of Error
Indoor unit related error
0 1 - Air temperature sensor of indoor unit Air temperature sensor of indoor unit is open or short
0 2 - Inlet pipe temperature sensor of indoor unit Inlet pipe temperature sensor of indoor unit is open or short
0 3 -
Communication error : wired remote controller
indoor unit
Failing to receive wired remote controller signal in indoor unit PCB
0 4 - Drain pump Malfunction of drain pump
0 5 -
Communication error : outdoor unit indoor unit
Failing to receive outdoor unit signal in indoor unit PCB
0 6 - Outlet pipe temperature sensor of indoor unit Outlet pipe temperature sensor of indoor unit is open or short
08 -
Hydro Kit Hot water storage tank Temperature
sensor
Pipe temperature sensor is open or short
0 9 - Indoor EEPROM Error
In case when the serial number marked on EEPROM of
Indoor unit is 0 or FFFFFF
1 0 - Poor fan motor operation
Disconnecting the fan motor connector / Failure of indoor
fan motor lock
1 1 -
Communication error : Hydro Kit Indoor unit
Inv.PCB
Failing to receive Inv. PCB signal in indoor unit
1 2 - Hydro Kit Inv.PCB error Hydro Kit Inv.PCB error
1 3 - Hydro Kit Solar heat piping temperature sensor error Pipe temperature sensor is open or short
1 4 - Hydro Kit Indoor unit Flow switch error Flow switch flow detection error
1 5 - Hydro Kit Liquid pipe Strange overheat Error Temperature sensor defective or hot water inflow
16 -
Hydro Kit Indoor unit Inlet and Outlet pipe
Temperature sensor Error
Pipe temperature sensor is open or short
17 -
Hydro Kit Indoor unit Inlet pipe Temperature sensor
Error
Outside air Introduction duct Inlet pipe Temperature
sensor Error
Pipe temperature sensor is open or short
18 -
Hydro Kit Indoor unit Outlet pipe Temperature
sensor Error
Pipe temperature sensor is open or short
2 3 0 - Error in refrigerant leakage detection
Occurs when a refrigerant leakage sensor is detecting refrigerant
leakage
237 -
Poor communication between the outdoor unit and
the indoor unit
The indoor unit could not receive the communication signal
from the outdoor unit for at least 3 consecutive minutes
238 -
Poor communication between the controlling part of
the outdoor unit and the indoor unit.
The controlling part of the outdoor unit could not receive the signal
for controlling the indoor unit
Outdoor unit related error
2 1 * Master Outdoor Unit Inverter Compressor IPM Fault Master Outdoor Unit Inverter Compressor Drive IPM Fault
2 2 *
Inverter PCB Input Over Current(RMS) of Master
Outdoor Unit
Master Outdoor Unit Inverter PCB Input Current excess (RMS)
2 3 *
Master Outdoor Unit Inverter Compressor DC Link
Low or High Voltage
System is turned off by Master Outdoor Unit DC Link Low/High
Voltage.
2 4 * Master Outdoor Unit High Pressure Switch System is turned off by Master Outdoor Unit high pressure switch.
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 56
background
57
ENGLISH
Display Title Cause of Error
2 5 *
Master Outdoor Unit Input Voltage High/ Low
Voltage
Master Outdoor Unit input voltage is over 537 V or below 247 V
(ARUM***LTE5)
Master Outdoor Unit input voltage is over 310 V or below 143 V
(ARUM***BTE5)
Master Outdoor Unit input voltage is over 598 V or below 320 V
(ARUM***DTE5)
Master Outdoor Unit input voltage is over 776 V or below 373 V
(ARUM***CTE5)
2 6 *
Master Outdoor Unit Inverter Compressor Start
Failure
The first start failure by Master Outdoor Unit Inverter Compressor
abnormality or Compressor locked
2 9 *
Master Outdoor Unit Inverter Compressor Over
Current
Master Outdoor Unit Inverter Compressor Fault or some bits in
pipe.
3 2 *
Master Outdoor Unit Inverter Compressor1 High
Discharge Temperature
Master Outdoor Unit Inverter Compressor1 High Discharge
Temperature
3 3 *
Master Outdoor Unit Inverter Compressor2 High
Discharge Temperature
Master Outdoor Unit Inverter Compressor2 High Discharge
Temperature
3 4 * High Pressure of Master Outdoor Unit High Pressure of Master Outdoor Unit
3 5 * Low Pressure of Master Outdoor Unit Low Pressure of Master Outdoor Unit
40*
Master Outdoor Unit Inverter Compressor CT
Sensor Fault
Master Outdoor Unit Inverter Compressor CT Sensor open or short
4 1 *
Master Outdoor Unit Inverter Compressor1
Discharge Temperature Sensor Fault
Master Outdoor Unit Inverter Compressor Discharge Temperature
Sensor open or short
4 2 * Master Outdoor Unit Low Pressure Sensor Fault Master Outdoor Unit Low Pressure Sensor open or short
4 3 * Master Outdoor Unit High Pressure Sensor Fault Master Outdoor Unit High Pressure Sensor open or short
4 4 * Master Outdoor Unit Air Temperature Sensor Fault Master Outdoor Unit Air Temperature Sensor open or short
4 5 *
Master Outdoor Unit Heat Exchanger Temperature
Sensor (Front side) Fault
Master Outdoor Unit Heat Exchanger Temperature Sensor(Front
side) open or short
4 6 *
Master Outdoor Unit Suction Temperature Sensor
Fault
Master Outdoor Unit Suction Temperature Sensor open or short
4 7 *
Master Outdoor Unit Inverter Compressor2
Discharge Temperature Sensor Fault
Master Outdoor Unit Inverter Compressor2 Discharge Temperature
Sensor open or short
4 9 *
Master Outdoor Unit Faulty IPM Temperature
Sensor
Master Outdoor Unit IPM Temperature Sensor short/open
50*
Omitting connection of R, S, T power of Master
Outdoor Unit
Omitting connection of Master outdoor unit
5 1 * Excessive capacity of indoor units
Excessive connection of indoor units compared to capacity of
Outdoor Unit
52*
Communication error : inverter PCB Main PCB
Failing to receive inverter signal at main PCB of Master Outdoor
Unit
53*
Communication error : indoor unit Main PCB of
Outdoor Unit
Failing to receive indoor unit signal at main PCB of Outdoor Unit.
57*
Communication error : Main PCB inverter PCB
Failing to receive signal main PCB at inverter PCB of Master
Outdoor Unit
6 0 * Inverter PCB EEPROM Error of Master Outdoor Unit Access Error of Inverter PCB of Master Outdoor Unit
62*
Master Outdoor Unit Inverter Heatsink High
Temperature
System is turned off by Master Outdoor Unit Inverter Heatsink High
Temperature
65*
Master Outdoor Unit Inverter Heatsink Temperature
Sensor Fault
Master Outdoor Unit Inverter Heatsink Temperature Sensor open
or short
6 7 * Master Outdoor Unit Fan Lock Restriction of Master Outdoor Unit
7 1 * Inverter CT Sensor Error of Master Outdoor Unit Inverter CT Sensor open or short of Master Outdoor Unit
7 5 * Master Outdoor Unit Fan CT Sensor Error Master Outdoor Unit Fan CT Sensor open or short
7 7 * Master Outdoor Unit Fan Over Current Error Master Outdoor Unit Fan Current is over 6A
7 9 * Master Outdoor Unit Fan Start Failure Error
The first start failure by Master Outdoor Unit Fan abnormality or
Fan locked
8 6 * Master Outdoor Unit Main PCB EEPROM Error
Communication Fail Between Master Outdoor Unit Main MICOM
and EEPROM or omitting EEPROM
8 7 * Master Outdoor Unit Fan PCB EEPROM Error
Communication Fail Between Master Outdoor Unit Fan MICOM
and EEPROM or omitting EEPROM
1 0 4*
Communication Error Between Master Outdoor
Unit and Other Outdoor Unit
Failing to receive Slave Unit signal at main PCB of Master
Outdoor Unit
1 0 5* Outdoor Unit Fan PCB Communication Error Failing to receive fan signal at main PCB of Outdoor unit
1 0 6* Outdoor Unit Fan IPM Fault Error Instant Over Current at Outdoor Unit Fan IPM
Outdoor unit related error
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 57
background
58
ENGLISH
Checking procedure of limiting concentration
Check concentration limit along following steps and take appropriate
measure depending on the situation.
Calculate amount of all the replenished refrigerant [kg (lbs)] per each
refrigerant system.
Concentration limit is the limit of Freon gas concentration where
immediate measures can be taken without hurting human body
when refrigerant leaks in the air. The Concentration limit shall be
described in the unit of [kg/m
3
(lbs/ft
3
)] (Freon gas weight per unit
air volume) for facilitating calculation.
Concentration limit: 0.44 kg/m
3
(0.028 lbs/ft
3
) (R410A)
Amount of additional
replenished refrigerant
Total amount of refrigerant
in in the system [kg (lbs)]
+
=
Note : In case one refrigerant facility is
divided into 2 or more refrigerant
systems and each system is
independent, amount of replenished
refrigerant of each system shall be
adopted.
Amount of pre-charged
refrigerant per single
Amount of replenished
refrigerant at factory shipment
Amount of additionally
replenished refrigerant
depending on piping
length or piping
diameter by customer
Outdoor unit
(No.1 system)
Flow of
refrigerant
Indoor unit
Room where refrigerant leaks
(Refrigerant of the whole No.1
system flows out.)
CAUTION FOR REFRIGERANT LEAK
The installer and system specialist shall secure safety against leakage
according to local regulations or standards.
The following standards may be applicable if local regulations are not
available.
Introduction
Though the R410A refrigerant is harmless and incombustible itself ,
the room to equip the air conditioner should be large to such an extent
that the refrigerant gas will not exceed the concentration limit even if
the refrigerant gas leaks in the room.
Concentration limit
h : HR unit # : HR unit number
Display Title Cause of Error
Outdoor unit related error
1 0 7* Outdoor Unit Fan DC Link Low Voltage Error Outdoor Unit Fan DC Link Input Voltage is under 380 V
1 1 3* Outdoor Unit Liquid pipe Temperature Sensor Error Liquid pipe temperature sensor of Outdoor Unit is open or short
1 1 4*
Outdoor Unit Subcooling Inlet Temperature Sensor
Error
Outdoor Unit Subcooling Inlet Temperature Sensor Error
115 *
Outdoor Unit Subcooling Outlet Temperature
Sensor Error
Outdoor Unit Subcooling Outlet Temperature Sensor Error
1 1 6 * Outdoor Unit Oil Level Sensor Error Oil Level Sensor of Outdoor Unit is open or short
145 *
Outdoor unit Main Board - External Board
communication Error
Outdoor unit Main Board - External Board communication Error
1 5 0 * Outdoor Unit Discharge Superheat not satisfied
Outdoor Unit Compressor Discharge Superheat not satisfied
during 5 Min.
151 *
Failure of operation mode conversion at Outdoor
Unit
Failure of operation mode conversion at Outdoor Unit
153 *
Outdoor Unit Heat Exchanger Temperature Sensor
(upper part) Fault
Outdoor Unit Heat Exchanger Temperature Sensor (upper part)
Fault
154 *
Outdoor Unit Heat Exchanger Temperature Sensor
(lower part) Fault
Outdoor Unit Heat Exchanger Temperature Sensor(lower part)
open or short
182 *
Outdoor unit External Board Main-Sub Micom
communication Error
Outdoor Unit Main Board Main-Sub Micom communication failed
1 8 7 * Hydro - Kit P,HEX bursting error
Inlet water temperature is below 5 degree or water temperature
error during defrosting operation.
1 9 3 * Outdoor Unit Fan Heatsink High Temperature
System is turned off by Outdoor Unit Fan Heatsink High
Temperature
194 *
Outdoor Unit Fan Heatsink Temperature Sensor
Fault
Outdoor Unit Fan Heatsink Temperature Sensor open or short
HR Unit related error
2 0 0 1 Searching pipe Error Failure of automatic addressing of valves
201
#HR + h
HR unit1 Liqiud sensor error Liquid pipe sensor of HR unit open or short
202
#HR + h
HR unit1 Sub Cooling Pipe sensor error Sub Cooling Pipe In sensor of HR unit open or short
203
#HR + h
HR unit1 Sub Cooling Pipe Out sensor error Sub Cooling Pipe Out sensor of HR unit. open or short
204
#HR + h
Communication error Failing to receive HR unit signal at outdoor unit
205
#HR + h
Communication error between HR unit and the
upgraded 485 modem.
4 series upgraded 485 communication error between
HR unit and HR unit modem
206
#HR + h
Duplicate address error of HR unit
When the HR unit address is set duplicated at the 4 series
upgraded 485 communication
207
#HR + h
Communication error between Master and Slave
Main PCB of HR Unit
When fail to communication between Master and Slave Main PCB
of HR Unit
208
#HR + h
Communication error of EEPROM of HR Unit When fail to communication of EEPROM of HR Unit
Network error
2 4 2 * Network error of cntral controller Communication wiring defect
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 58
background
59
ENGLISH
Calculate minimum room capacity
Calculate room capacity by regarding a portion as one room or the
smaller room.
- With partition and with opening
which serve as passage of air to
adjoining room
- Without partition
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Opening
Partition
In the case of opening
without door, or 0.15 %
or more openings
(to floor space) both
above and below door)
- With partition and without opening which serve as passage of air to
adjoining room
Calculate refrigerant concentration
Total amount of
replenishedrefrigerant in
refrigerant facility [kg(lbs)]
Volume of smallest room
whereindoor unit is installed
[m
3
(ft
3
)]
- In case the result of calculation exceeds the concentration limit, perform the
same calculations by shifting to the second smallest, and the third smallest
rooms until at last the result is below the concentration limit.
In case the concentration exceeds the limit
When the concentration exceeds the limit, change original plan or take
one of the countermeasures shown below:
• Countermeasure 1
Provide opening for ventilation.
Provide 0.15 % or more size of opening to floor space both above
and below door, or provide opening without door.
• Countermeasure 2
Provide gas leak alarm linked with mechanical ventilator.
• Countermeasure 3
Reducing the outdoor refrigerant qty by dividing into smaller
separate system.
= Maximum concentration limit
[kg/m
3
(lbs/ft
3
)]
(R410A)
Outdoor unit
Indoor unit
Smallest
room
Countermeasure 2
Gas leak alarm
Mechanical ventilator
Countermeasure 1
Opening effective to ventilation
Indoor unit
Pay a special attention to the place, such as a basement, etc.
where refrigerant can stay, since refrigerant is heavier than air.
INSTALLATION GUIDE AT THE
SEASIDE
• Periodic (1 times per 6 months) cleaning of the dust or salt
particles stuck on the heat exchanger Is necessary by using
clean water
In case, to install the outdoor unit on the seaside, set up a windbreak
not to be exposed to the sea wind.
- It should be strong enough like concrete to prevent the sea wind
from the sea.
- The height and width should be more than 150 % of the outdoor unit.
- It should be kept more than 70 cm (2.3 ft) of distance between
outdoor unit and the windbreak for smooth air flow.
Select a well-drained place.
Sea wind
Windbreak
Selecting the location(Outdoor Unit)
If the outdoor unit is to be installed close to the seaside, direct
exposure to the sea wind should be avoided. Install the outdoor unit on
the opposite side of the sea wind direction.
Sea wind
Sea wind
• Air conditioners should not be installed in areas where corrosive
gases, such as acid or alkaline gas, are produced.
• Do not install the product where it could be exposed to sea
wind (salty wind) directly. It can result corrosion on the product.
Corrosion, particularly on the condenser and evaporator fins,
could cause product malfunction or inefficient operation.
• If outdoor unit is installed close to the seaside, it should avoid
direct exposure to the sea wind. Otherwise it needs additional
anticorrosion treatment on the heat exchanger.
CAUTION
!
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 59
background
60
ENGLISH
• Product Name : Air conditioner
• Model Name :
• Additional information : Serial number is refer to the bar code on the
product.
Product Sales Name Model Factory Name
ARUx***yTE5 series
x = N (Heat Pump), V (Cooling Only),
M (Heat Recovery / Heat Pump)
y = B (208/230 V)
D (460 V)
C (575 V)
*** = Numeric; (Cooling capacity)
Product information
Model Designation
1,MFL68980308,영영 2018. 11. 13. 영영 3:24 Page 60

Specifications

LG Electronics ARUM241DTE5 Questions and Answers

Questions and Answers

Related Products